WHAT IT IS

The EWPC 961/S is a temperature

controller specifically designed for

refrigeration applications.

The instrument is equipped with a

RS-485 port for the purpose of con-

necting it into a Televis system.

HOW IT IS MADE

• Dimensions: front 74×32 mm

(2.913×1.260″), depth 67 mm

(2.637″)

• Mounting: flush panel mount with

mounting bracket

• Protection: the instrument front-

panel is waterproof IP65; an op-

tional snap-on cover can be

supplied to provide additional pro-

tection of the rear terminal block

• Connections: screw terminal block

2

(2.5 mm

; one wire each terminal

only, in compliance with VDE

norms)

• Display: 12.5 mm LED (0.50″)

• Output: one (1) SPDT relay 8(3)A

250VA

• Input: PTC probe

• Serial connection: RS-485 serial

port for connection to the Televis

system

• Televis system compatibility: soft-

ware release 2.0.4 or greater

• Resolution: 1 °C (°F)

• Accuracy: better than 0.5% of full

scale

• Power supply: 12…24 VA/C

EWPC 961/S

freezer control with Televis output

GENERAL DESCRIPTION

The EWPC 961/S is a temperature con-

troller specifically designed for refrigeration

applications and provides time control for

off-cycle defrost management. It incorpo-

rates an output relay for compressor con-

trol and a PTC sensor input. Furthermore,

the instrument is equipped with a RS-485

port for the purpose of connecting it into a

Televis system. A number of parameters are

displayed alphanumerically to set up the in-

strument for each specific application.

The EWPC 961/S is supplied in the popu-

lar «32×74» ELIWELL housing.

OPERATION

The EWPC 961/S is designed to operate

strictly as a cooling control, which means

that the switching differential is positive: the

compressor cuts off at setpoint and is

started at a temperature of set plus differ-

ential. The on-board microprocessor pro-

vides several timing functions for the

defrost; the defrost cycle as well the de-

frost cycle duration are user selectable.

At the start of each defrost cycle, the com-

pressor is simply stopped, regardless of

the temperature control circuit.

In addition, the EWPC 961/S offers several

system protection features, all easy to un-

derstand and easy to program This instru-

ment is compatible with Televis software rel

2.4 or greater. In case its use with different

software releases is required contact your

supplier or Eliwell Customers’ Service.

FRONT KEYPAD

SET: push and release to display the set-

point for 5 seconds. During this period the

«SET» status light is on and the setpoint

can be changed with the «UP» or «DOWN»

button only. The system will automatically

switch to normal display after 5 seconds

upon release of buttons and the new value

will be memorized.

UP: used to increase the setpoint value, as

well as the parameter when in program-

ming. When held down for a few seconds,

the change rate accelerates.

DOWN: same functions, except to de-

crease a value.

DEFROST: push to initiate a manual de-

frost cycle (override of programmed defrost

start; programmed time resets to zero).

Manual defrost can not be started while in

setpoint or in parameter programming

mode.

This button must be activated for 5 sec-

onds to start a defrost; the «DEF» status

light will come on and the compressor is

stopped.

Led «COMP»: status light of the internal

compressor relay. It is ON when the com-

pressor is ON.

Led «SET»: it is on during Setpoint display

and programming; it blinks during parame-

ter programming.

Led «DEF»: status light of the defrost. It is

on during automatic defrost; it blinks dur-

ing manual defrost.

PARAMETER PROGRAMMING

Programming is easily accessed by holding

the «SET» button down for more than

5 seconds; the first parameter is displayed

while the status light «SET» remains blink-

ing during the programming period.

Other parameters are accessed with the

«UP» and «DOWN» button. With the «SET»

button, the actual setting of each parame-

ter is displayed. To change a parameter

setting, push the «SET» plus the «UP» (or

«DOWN»). The system will automatically re-

turn to its normal operating mode a few

seconds after the programming procedure

is completed or interrupted.

DESCRIPTION OF PARAMETERS

diF: diFferential.

Switching differential (histeresis); it will al-

ways be set with positive value (make on

rise).

  Название Инструкция Комментарий

Eliwell IC901 NTC-PTC Eliwell IC 901 NTC-PTC Eliwell IC901 NTC-PTC Eliwell IC 901 — одноступенчатый контроллер температуры. IC901 – прибор с одной точкой срабатывания (работает как в режиме нагревания / охлаждения. Снабжен входным PTC датчиком (NTC может быть выбран параметром) и выходным реле для управления нагрузкой

Eliwell IC 902 NTC-PTC Eliwell IC 902 NTC-PTC Eliwell IC 902 NTC-PTC IC 902 обладает одним функциональным выходом. Для контроля за состоянием и программированием прибора имеется дисплей и четыре кнопки управления

Eliwell IC 915 LX NTC-PTC Eliwell IC 915 LX NTC-PTC Eliwell IC 915 LX NTC-PTC IC 915 LX – контроллер с двумя точками срабатывания, использующийся для контроля температуры. Cнабжен входом под датчики термостатов PTC/NTC

Eliwell ID 961 Eliwell ID 961 Eliwell ID 961 ID 961 — для холодильных установок средней температуры. Температурные датчики РТС / NTC (на выбор) и выходным реле для управления компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 961 LX Eliwell ID 961 LX Eliwell ID 961 LX ID 961 LX — для холодильных установок средней температуры. Cнабжены входом под температурные датчики РТС (NTC может выбираться параметром) и выходным реле для управления компрессором. Продолжительность разморозки определяется временными интервалами остановки компрессора

Eliwell ID 970 Eliwell ID 970 Eliwell ID 970 ID 970 — для холодильных установок средней или низкой температуры. Датчики PTC / NTC, два выходных реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 970 LX Eliwell ID 970 LX Eliwell ID 970 LX ID 970 LX — для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC и двумя выходными реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 971 Eliwell ID 971 Eliwell ID 971 ID 971 — контроллер для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC, два реле для управления компрессором и оттайкой

Eliwell ID 971 LX Eliwell ID 971 LX Eliwell ID 971 LX ID 971 LX — для холодильных систем два реле, два датчика, цифровой вход. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Работа вентилятора контроллером не программируется

Eliwell ID 974 Eliwell ID 974 Eliwell ID 974 ID 974 — для вентилируемых холодильных установок средней и низкой температуры. Датчики PTC / NTC. Три реле для управления компрессором, вентилятором и оттайкой. Оттайка задается по времени или по достижению температуры испарителя

Eliwell ID 974 LX Eliwell ID 974 LX Eliwell ID 974 LX ID 974 LX — для вентилируемых холодильных установок средней и низкой температуры, два входа для датчиков PTC (или NTC); три реле для управления процессором, вентилятором и оттайкой; цикл оттайки задается по времени или по достижению температуры испарителя

Eliwell ID 975 LX Eliwell ID 975 LX Eliwell ID 975 LX ID 975 LX — для вентилируемых холодильных установок средней и низкой температуры. Два датчика PTC / NTC. Четыре выходных реле предназначены для управления компрессором, вентилятором, разморозкой и авариями. Аварийное реле может быть запрограммировано для дополнительной нагрузки

Eliwell ID 985 LX Eliwell ID 985 LX Eliwell ID 985 LX ID 985 LX — для вентилируемых холодильных установок средней и низкой температуры. Три температурных датчика PTC / NTC. Четыре выходных реле для управления компрессором, вентилятором, разморозкой и авариями (причем аварийное реле может быть запрограммировано для дополнительной нагрузки)

Eliwell ID 961-971-974 Plus Eliwell ID 961-971-974 Plus Eliwell ID 961-971-974 Plus ID PLUS 961 — 971 — 974 Электронные контроллеры статических и вентилируемых холодильных установок

Eliwell EW 961 - 974 Eliwell EW961-974(аналог ID974) Eliwell EW 961 — 974 EW961-974 — для невентилируемых холодильных установок средней температуры. Температурные датчики PTC / NTC. Реле для управления холодильным компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 983-985 LX Eliwell ID 983-985 LX EliwellI D 983-985S E CK, ID 983-985 E LX ID 983-985 LX — для холодильных систем четыре программируемых реле, три датчика NTC / PTC, два цифровых входа. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Возможен вариант использования в режиме один компрессор два воздухоохладителя. Подключается к сети LINK.

Eliwell Energy XT Eliwell Energy XT Eliwell Energy XT Energy XT — серия программируемых контроллеров фирмы Eliwell, работающих в сферах кондиционирования и хладопроизводства. Energy XT, построен на базе 16-битного микропроцессора

Eliwell EWCM 900 S Eliwell EWCM 900 S Eliwell EWCM 900 S EWCM 900/S — предназначен для управления машинным залом холодильной установки, в котором находятся компрессоры простого действия, многоступенчатые или различной мощности. Эти приборы также предназначены для управления вентиляторами конденсаторного агрегата. EWCM 900/S с 11 релейными выходами, может быть с входом под напряжением или же с температурным входом (зондом NTC).

Eliwell EWDR 902 Eliwell EWDR 902 Eliwell EWDR 902 EWDR 902 представляет собой серию микропроцессорных, полностью программируемых контроллеров с одной точкой срабатывания. Три различные версии разработаны для следующих применений: EWDR 902/T — для температуры; EWDR 902/R — для относительной влажности; EWDR 902/P — для давления

Eliwell EWDR 905 Eliwell EWDR 905 Eliwell EWDR 905 EWDR 905 представляет собой серию микропроцессорных, полностью программируемых контроллеров с двумя точками срабатывания или Нейтральной Зоной. Три различные версии разработаны для следующих применений: EWDR 905/T — для температуры; EWDR 905/R — для относительной влажности; EWDR 905/P — для давления

Eliwell EWCM 400 Eliwell EWCM 400 Eliwell EWCM 400 Серия EWCM 400 — контроллеры невысокой стоимости, специально разработанные для управления машинным залом холодильной системы. Они могу управлять максимум четырьмя простыми компрессорами и вентиляторами конденсатора установки

Eliwell EWDR 976 NTC Eliwell EWDR 976 NTC Eliwell EWDR 976 NTC

EWDR 976 NTC – контроллер, разработанный для управления разморозкой нескольких испарителей одной холодильной системы, управляемой только одним прибором серии DIGIFROST® (называемым Мастером) в котором должно иметься реле разморозки и датчик температуры испарителя (EWLC 74, EWPX 971, EWPX 185…).

Eliwell EWDR 975 Eliwell EWDR 975 Eliwell EWDR 975

EWDR 975 – контроллер, специально разработанный для холодильных установок. Он используется в сочетании с другим холодильным контроллером серии DIGIFROST® (за исключением EWPC 961/970 и ID 961/970) для систем с двойным контуром охлаждения, т.е. два компрессора и два испарителя

Eliwell Energy XT PRO Eliwell Energy XT PRO Eliwell Energy XT PRO Energy XT PRO — серия свободно программируемых контроллеров фирмы Eliwell, которые легко подстраиваются под требования потребителя, работающих в сферах кондиционирования и хладопроизводства. Energy XT PRO, построен на базе 16-битного микропроцессора

Eliwell EWTR HR PR 920 Eliwell EWTR HR PR 920 Eliwell EWTR HR PR 920

EWTR 920 – это серия полностью программируемых приборов для применений с двумя рабочими точками; выхода управляются по принципу Вкл./Выкл. Существуют 3 различных версии контроллеров для Температуры EWTR 920, Относительной Влажности EWHR 920 и Давления EWPR 920.

Eliwell EWDR 984 Eliwell EWDR 984 Eliwell EWDR 984 EWDR 984 – для вентилируемых холодильных установок, 3 входа под температурные датчики NTC/PTC, 2 конфигурируемых цифровых входа. Три реле для управления компрессором, разморозкой и вентилятором. Дополнительный конфигурируемый выход 12В/ 20мА для аварий или т.п. Разморозка осуществляется остановкой компрессора на заданное время или достижения порогового значения температуры испарителя

Eliwell IWC 720-730 Eliwell IWC 720-730 Eliwell IWC 720-730 IWC720-730 — для оборудования вентилируемых холодильных установок при нормальной или низкой температуре. Настраивается в зависимости от потребностей контроля и управления. Контролирует до трех входов для датчиков температуры. Предусматривает до шести выходных реле для управления компрессором, размораживания, вентиляторов испарителя, сигнализации, регулятора включения и выключения, а также для вспомогательного производства

Eliwell IWС 720-730 RUS Eliwell IWС 720-730 RUS Eliwell IWС 720-730 RUS

Eliwell IWC 740-750 Eliwell IWC 740-750 Eliwell IWC 740-750 IWС 740-750 — электронный регулятор для «вентилируемых» холодильных агрегатов

Eliwell EWDR 984 LX Eliwell EWDR 984 LX Eliwell EWDR 984 LX EWDR 984 LX — 3 входа под температурные датчики NTC / PTC, два конфигурируемых цифровых входа и три реле. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Звуковая сигнализация по температурных авариях. Монтаж на DIN-рейку

Eliwell EWRC 300 500 NT Eliwell EWRC 300 500 NT Eliwell EWRC 300 500 NT Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации. Приборы серии Coldface имеют 3 или 5 конфигурируемых реле в зависимости от модели, 2 конфигурируемых цифровых входа для реле двери и других целей. Имеются модели с часами и годовым календарем и с поддержанием функции записи событий в соответствии с протоколом HACCP.

Eliwell_EWRC_300_500_5000NT Eliwell EWRC 300 500 5000 NT Eliwell_EWRC_300_500_5000NT Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации

Если вы только что купили новый роутер ewpc 961 и не знаете, как его подключить, не переживайте. В этой статье мы предоставим вам пошаговую инструкцию по установке и настройке роутера, чтобы вы могли наслаждаться быстрым и стабильным интернет-соединением.

Важно знать, что правильная установка вашего роутера — это ключ к обеспечению безопасности и функциональности вашей сети. Поэтому убедитесь, что вы следуете всем инструкциям, приведенным в данной статье.

Перед тем, как начать подключение, необходимо убедиться, что все компоненты роутера на месте. В комплекте должно быть: роутер, сетевой кабель, блок питания и инструкция по эксплуатации.

Содержание

  1. Как подключить роутер ewpc 961?
  2. Шаг 1: Проверьте комплектацию
  3. Шаг 2: Подключите роутер
  4. Шаг 3: Настройте роутер
  5. Шаг 4: Подключите другие устройства
  6. Шаг 5: Проверьте соединение
  7. Шаг 1: Распаковка роутера
  8. 1.1 Проверьте комплектацию
  9. 1.2 Откройте упаковку
  10. 1.3 Проверьте роутер на наличие повреждений
  11. Шаг 2: Подключение к интернету
  12. 1. Подключение кабеля Ethernet
  13. 2. Проверка наличия интернет-соединения
  14. 3. Настройка параметров подключения
  15. 4. Подключение по Wi-Fi
  16. Шаг 3: Подключение к компьютеру
  17. 1. Подключите роутер к компьютеру с помощью LAN-кабеля.
  18. 2. Установите соединение.
  19. 3. Проверьте подключение.
  20. Шаг 4: Настройка интернета
  21. 1. Настройка WAN-соединения
  22. 2. Настройка беспроводной сети
  23. Шаг 5: Настройка Wi-Fi
  24. 1. Вход в меню настройки Wi-Fi
  25. 2. Настройка Wi-Fi
  26. 3. Сохранение настроек
  27. Шаг 6: Обновление прошивки
  28. 1. Проверьте версию текущей прошивки
  29. 2. Скачайте обновление прошивки
  30. 3. Обновите прошивку роутера
  31. 4. Проверьте версию новой прошивки
  32. Шаг 7: Проверка подключения
  33. 1. Пинг до маршрутизатора
  34. 2. Проверка интернет-подключения
  35. Вопрос-ответ
  36. Как подключить роутер к компьютеру?
  37. Как установить пароль на роутер?
  38. Что делать, если пароль на роутер был потерян?
  39. Как подключить мобильный телефон к роутеру?
  40. Как узнать IP-адрес роутера?
  41. Как перезагрузить роутер?
  42. Что делать, если роутер не подключается к интернету?

Как подключить роутер ewpc 961?

Шаг 1: Проверьте комплектацию

Перед началом подключения роутера ewpc 961, удостоверьтесь, что полностью распаковали комплект и проверили наличие всех необходимых компонентов, включая роутер, блок питания, кабель Ethernet и документацию.

Шаг 2: Подключите роутер

Подключите роутер к электрической сети, используя блок питания, который входит в комплект поставки. Затем подключите роутер к модему или кабелю Ethernet из вашей стены. Проверьте, что роутер правильно подключен к интернету, проверив индикатор связи.

Шаг 3: Настройте роутер

Подключите компьютер к роутеру через кабель Ethernet или Wi-Fi. Затем введите IP-адрес роутера (обычно 192.168.0.1) в браузере и нажмите Enter. Введите имя пользователя и пароль администратора, которые указаны в документации. Настройте необходимые параметры, такие как имя сети Wi-Fi и пароль, установите ограничения доступа, настройте защиту брандмауэра и т.д.

Шаг 4: Подключите другие устройства

Теперь вы можете подключить все свои устройства к вашей новой Wi-Fi-сети. Введите пароль, который вы настроили на предыдущем шаге, на своих устройствах для подключения к Wi-Fi.

Шаг 5: Проверьте соединение

После того, как все устройства успешно подключены к Wi-Fi сети, проверьте соединение на каждом устройстве, чтобы удостовериться, что все работает надлежащим образом. Если у вас возникнут проблемы с подключением устройств, обратитесь к документации или к службе поддержки.

Шаг 1: Распаковка роутера

1.1 Проверьте комплектацию

Перед началом подключения убедитесь, что в комплекте находятся все необходимые элементы:

  • Роутер EWPC 961
  • Блок питания
  • Кабель Ethernet
  • Инструкция по эксплуатации

1.2 Откройте упаковку

Осторожно распакуйте коробку, снимите все защитные элементы и достаньте роутер.

1.3 Проверьте роутер на наличие повреждений

Внимательно осмотрите роутер на наличие механических повреждений или следов падений. В случае обнаружения повреждений, свяжитесь с продавцом.

Убедитесь, что все входы и выходы на роутере не заблокированы, и устройство готово к установке.

Шаг 2: Подключение к интернету

1. Подключение кабеля Ethernet

Для подключения роутера к интернету необходимо подключить кабель Ethernet, который будет идти от провайдера интернет-услуг до WAN-порта роутера. Обычно кабель Ethernet имеет специальный коннектор RJ-45 на конце. Подключите его к соответствующему порту роутера.

2. Проверка наличия интернет-соединения

После подключения кабеля Ethernet необходимо проверить наличие интернет-соединения. Для этого откройте веб-браузер и введите адрес любого сайта. Если страница загрузилась без ошибок, значит интернет-соединение работает.

3. Настройка параметров подключения

Если веб-страница не загружается, необходимо проверить наличие ошибок в настройках подключения к интернету. Для этого зайдите в раздел настроек роутера, который отвечает за подключение к интернету и укажите параметры, полученные от вашего интернет-провайдера.

4. Подключение по Wi-Fi

Если необходимо подключить устройства к интернету по Wi-Fi, необходимо настроить беспроводную сеть в разделе настроек роутера. Для этого выберите параметры беспроводной сети и установите пароль для доступа к ней. После этого вы сможете подключаться к беспроводной сети с любого устройства, поддерживающего Wi-Fi.

Шаг 3: Подключение к компьютеру

1. Подключите роутер к компьютеру с помощью LAN-кабеля.

Для начала подключите один конец кабеля в порт LAN на задней панели роутера, а другой конец в порт Ethernet на вашем компьютере. Обычно предпочтительнее подключать кабель прямо к компьютеру, а не через Wi-Fi. Это обеспечивает более стабильную и надежную связь.

2. Установите соединение.

Когда кабель подключен с обеих сторон, компьютер должен автоматически определить новое устройство и установить соединение. Если этого не происходит автоматически, то необходимо проверить работу сетевой карты и правильность установки драйверов.

3. Проверьте подключение.

Чтобы проверить, что настройка прошла успешно, откройте любой браузер и попробуйте зайти на любой сайт. Если вы не можете получить доступ к Интернету, возможно, что настройки сетевого адаптера не корректны. В таком случае обратитесь к документации, чтобы узнать как необходимо сконфигурировать сеть.

Теперь вы готовы к настройке роутера ewpc 961 и внесению всех нужных настроек! Но прежде чем приступать к дальнейшим действиям, обязательно ознакомьтесь с инструкцией по подключению и настройке устройства, чтобы избежать проблем при работе.

Шаг 4: Настройка интернета

1. Настройка WAN-соединения

Для того чтобы подключиться к интернету, необходимо сконфигурировать WAN-соединение. Для этого требуется знать следующую информацию:

  • Тип подключения: PPPoE, Dynamic IP, Static IP или PPTP.
  • Логин и пароль для подключения к интернет-провайдеру в случае PPPoE или PPTP.
  • Адрес IP, маска подсети, шлюз по умолчанию и DNS-серверы для Static IP.

После ввода всех необходимых данных, сохраните настройки и перезапустите роутер, если это требуется.

2. Настройка беспроводной сети

Для того чтобы пользоваться беспроводным интернетом, настройте беспроводную сеть:

  • Выберите желаемый канал Wi-Fi.
  • Настройте защиту сети: выберите режим шифрования, задайте пароль для доступа к сети.
  • Назначьте имя (SSID) для вашей беспроводной сети.

Сохраните настройки и перезапустите роутер, если это требуется.

Шаг 5: Настройка Wi-Fi

1. Вход в меню настройки Wi-Fi

Для входа в меню настройки Wi-Fi необходимо открыть браузер, в строке адреса ввести IP-адрес роутера — 192.168.0.1, затем ввести логин и пароль.

2. Настройка Wi-Fi

Далее необходимо выбрать вкладку «Wireless» и начать настройку Wi-Fi модуля. Здесь можно указать имя сети (SSID), установить пароль, выбрать тип шифрования (например, WPA2) и другие параметры.

Рекомендуется устанавливать сложные пароли для защиты сети и избегать использования имени и фамилии в SSID сети, чтобы не давать злоумышленникам возможность идентифицировать устройство.

3. Сохранение настроек

После проведения всех настроек необходимо сохранить изменения, нажав кнопку «Save» или «Применить».

Для подключения устройств к Wi-Fi роутера, нужно выбрать соответствующую сеть в списке доступных сетей на устройстве и ввести пароль (если он был установлен).

Шаг 6: Обновление прошивки

1. Проверьте версию текущей прошивки

Перед обновлением прошивки необходимо узнать, какая версия прошивки установлена на вашем роутере. Для этого зайдите в настройки роутера через веб-браузер, выберите вкладку «Общие настройки» и в разделе «Системная информация» найдите строку с названием «Версия прошивки». Запишите эту информацию, она может понадобиться для сравнения со сведениями о доступных обновлениях.

2. Скачайте обновление прошивки

Для загрузки обновления прошивки перейдите на официальный сайт производителя. Найдите на странице скачивания раздел, содержащий файлы прошивки для вашего конкретного устройства. Обычно, файлы прошивки имеют расширение bin или img. Выберите соответствующий файл и загрузите его на свой компьютер.

3. Обновите прошивку роутера

Чтобы обновить прошивку вашего роутера, зайдите в настройки устройства через веб-браузер, выберите вкладку «Система» и в разделе «Обновление прошивки» нажмите кнопку «Обзор». Откройте файл прошивки, который вы загрузили с официального сайта производителя, и нажмите кнопку «Обновить». Во время обновления ваш роутер может отключиться и перезагрузиться несколько раз. Это нормально — не выключайте устройство во время процесса обновления!

4. Проверьте версию новой прошивки

После того, как прошивка роутера обновлена, проверьте еще раз версию прошивки в настройках устройства. Ее номер должен измениться на новую версию. Если это произошло, значит обновление прошло успешно.

Шаг 7: Проверка подключения

После того, как вы настроили свой роутер EWPC 961 и подключили его к интернету, нужно убедиться, что подключение работает корректно.

Для этого можно выполнить следующие действия:

1. Пинг до маршрутизатора

Откройте командную строку на компьютере и введите команду ping, указав IP-адрес вашего роутера. Если пинг прошел успешно, то вы увидите ответы от роутера. Если ответов нет, то нужно проверить подключение кабелей и настройки роутера.

2. Проверка интернет-подключения

Откройте веб-браузер на компьютере и попробуйте зайти на любой сайт. Если сайт открывается, то значит интернет-подключение работает корректно. Если же сайт не открывается, то нужно проверить настройки роутера и провайдера интернет-услуг.

Если оба теста выполнены успешно, значит ваш роутер EWPC 961 успешно подключен и работает корректно. Если же возникли проблемы, то нужно следовать инструкциям по настройке и подключению, либо обратиться к специалисту.

Вопрос-ответ

Как подключить роутер к компьютеру?

Для подключения необходимо использовать сетевой кабель, подсоединить один конец к порту WAN на роутере, а другой конец к сетевой карте на компьютере.

Как установить пароль на роутер?

Чтобы установить пароль, нужно зайти в настройки роутера через браузер, найти вкладку Security или Конфиденциальность, выбрать опцию «Установить пароль» и задать новый пароль.

Что делать, если пароль на роутер был потерян?

Если вы потеряли пароль на роутер, то вам нужно будет выполнить сброс настроек. Для этого необходимо удерживать кнопку Reset на роутере 10-15 секунд, после чего настройки будут сброшены на заводские.

Как подключить мобильный телефон к роутеру?

Для подключения телефона к роутеру нужно включить WiFi на телефоне, выбрать сеть, созданную роутером, и ввести пароль, если он был установлен.

Как узнать IP-адрес роутера?

Чтобы узнать IP-адрес роутера, нужно зайти в командную строку на компьютере и ввести команду «ipconfig» для Windows или «ifconfig» для MacOS и Linux. IP-адрес роутера будет указан в разделе Default Gateway.

Как перезагрузить роутер?

Чтобы перезагрузить роутер, нужно зайти в настройки роутера через браузер, найти вкладку System или Система, выбрать опцию «Перезагрузить» и подтвердить действие.

Что делать, если роутер не подключается к интернету?

Если роутер не подключается к интернету, нужно проверить подключение кабелей, убедиться, что настройки роутера верные, проверить соединение провайдера и выполнить перезагрузку оборудования.

  1. 11.09.2017, 14:18


    #1

    а.борисыч вне форума


    Мастер


    По умолчанию EWPC-961/N

    доброго дня коллеги! помогите найти инструкцию именно на EWPC-961/N


  2. 11.09.2017, 14:42


    #2


  3. 11.09.2017, 14:53


    #3

    а.борисыч вне форума


    Мастер


    По умолчанию


  4. 02.03.2018, 22:50


    #4

    'crbvjc вне форума


    Новичок

    Аватар для 'crbvjc


    По умолчанию

    Нету , к сожалению , его в архиве ….


  5. 03.03.2018, 05:41


    #5

    SerB вне форума


    флибустьерю потихоньку..

    Аватар для SerB



  6. 03.03.2018, 06:44


    #6

    Вьюга4 вне форума


    Демагог с Большой буквы )

    Аватар для Вьюга4


    По умолчанию

    Цитата Сообщение от а.борисыч
    Посмотреть сообщение

    доброго дня коллеги! помогите найти инструкцию именно на EWPC-961/N

    а.борисыч, у меня было 4 таких подшефных блока — все они, примерно после 20-летней эксплуатации,, в течение 3-4 лет загорелись. Это ещё хорошо, что финал был удачный!


Похожие темы

  1. Ответов: 0

    Последнее сообщение: 25.05.2012, 19:05

  2. Ответов: 0

    Последнее сообщение: 25.05.2012, 19:03

  3. Ответов: 0

    Последнее сообщение: 23.08.2011, 00:41

  4. Ответов: 3

    Последнее сообщение: 16.03.2011, 19:54

  5. Ответов: 3

    Последнее сообщение: 11.09.2009, 01:16

Социальные закладки

Социальные закладки
  • Отправить на Google

    Google


Ваши права

  • Вы не можете создавать новые темы
  • Вы не можете отвечать в темах
  • Вы не можете прикреплять вложения
  • Вы не можете редактировать свои сообщения
  •  
  • BB коды Вкл.
  • Смайлы Вкл.
  • [IMG] код Вкл.
  • [VIDEO] код Вкл.
  • HTML код Выкл.

Правила форума

WHAT IT IS

The EWPC 961/S is a temperature

controller specifically designed for

refrigeration applications.

The instrument is equipped with a

RS-485 port for the purpose of con-

necting it into a Televis system.

HOW IT IS MADE

• Dimensions: front 74×32 mm

(2.913×1.260″), depth 67 mm

(2.637″)

• Mounting: flush panel mount with

mounting bracket

• Protection: the instrument front-

panel is waterproof IP65; an op-

tional snap-on cover can be

supplied to provide additional pro-

tection of the rear terminal block

• Connections: screw terminal block

2

(2.5 mm

; one wire each terminal

only, in compliance with VDE

norms)

• Display: 12.5 mm LED (0.50″)

• Output: one (1) SPDT relay 8(3)A

250VA

• Input: PTC probe

• Serial connection: RS-485 serial

port for connection to the Televis

system

• Televis system compatibility: soft-

ware release 2.0.4 or greater

• Resolution: 1 °C (°F)

• Accuracy: better than 0.5% of full

scale

• Power supply: 12…24 VA/C

EWPC 961/S

freezer control with Televis output

GENERAL DESCRIPTION

The EWPC 961/S is a temperature con-

troller specifically designed for refrigeration

applications and provides time control for

off-cycle defrost management. It incorpo-

rates an output relay for compressor con-

trol and a PTC sensor input. Furthermore,

the instrument is equipped with a RS-485

port for the purpose of connecting it into a

Televis system. A number of parameters are

displayed alphanumerically to set up the in-

strument for each specific application.

The EWPC 961/S is supplied in the popu-

lar «32×74» ELIWELL housing.

OPERATION

The EWPC 961/S is designed to operate

strictly as a cooling control, which means

that the switching differential is positive: the

compressor cuts off at setpoint and is

started at a temperature of set plus differ-

ential. The on-board microprocessor pro-

vides several timing functions for the

defrost; the defrost cycle as well the de-

frost cycle duration are user selectable.

At the start of each defrost cycle, the com-

pressor is simply stopped, regardless of

the temperature control circuit.

In addition, the EWPC 961/S offers several

system protection features, all easy to un-

derstand and easy to program This instru-

ment is compatible with Televis software rel

2.4 or greater. In case its use with different

software releases is required contact your

supplier or Eliwell Customers’ Service.

FRONT KEYPAD

SET: push and release to display the set-

point for 5 seconds. During this period the

«SET» status light is on and the setpoint

can be changed with the «UP» or «DOWN»

button only. The system will automatically

switch to normal display after 5 seconds

upon release of buttons and the new value

will be memorized.

UP: used to increase the setpoint value, as

well as the parameter when in program-

ming. When held down for a few seconds,

the change rate accelerates.

DOWN: same functions, except to de-

crease a value.

DEFROST: push to initiate a manual de-

frost cycle (override of programmed defrost

start; programmed time resets to zero).

Manual defrost can not be started while in

setpoint or in parameter programming

mode.

This button must be activated for 5 sec-

onds to start a defrost; the «DEF» status

light will come on and the compressor is

stopped.

Led «COMP»: status light of the internal

compressor relay. It is ON when the com-

pressor is ON.

Led «SET»: it is on during Setpoint display

and programming; it blinks during parame-

ter programming.

Led «DEF»: status light of the defrost. It is

on during automatic defrost; it blinks dur-

ing manual defrost.

PARAMETER PROGRAMMING

Programming is easily accessed by holding

the «SET» button down for more than

5 seconds; the first parameter is displayed

while the status light «SET» remains blink-

ing during the programming period.

Other parameters are accessed with the

«UP» and «DOWN» button. With the «SET»

button, the actual setting of each parame-

ter is displayed. To change a parameter

setting, push the «SET» plus the «UP» (or

«DOWN»). The system will automatically re-

turn to its normal operating mode a few

seconds after the programming procedure

is completed or interrupted.

DESCRIPTION OF PARAMETERS

diF: diFferential.

Switching differential (histeresis); it will al-

ways be set with positive value (make on

rise).

 
Название
Инструкция
Комментарий

Eliwell IC901 NTC-PTC

Eliwell IC 901 NTC-PTC

Eliwell IC901 NTC-PTC

Eliwell IC 901 — одноступенчатый контроллер температуры. IC901 – прибор с одной точкой срабатывания (работает как в режиме нагревания / охлаждения. Снабжен входным PTC датчиком (NTC может быть выбран параметром) и выходным реле для управления нагрузкой

Eliwell IC 902 NTC-PTC

Eliwell IC 902 NTC-PTC

Eliwell IC 902 NTC-PTC

IC 902 обладает одним функциональным выходом. Для контроля за состоянием и программированием прибора имеется дисплей и четыре кнопки управления

Eliwell IC 915 LX NTC-PTC

Eliwell IC 915 LX NTC-PTC

Eliwell IC 915 LX NTC-PTC

IC 915 LX – контроллер с двумя точками срабатывания, использующийся для контроля температуры. Cнабжен входом под датчики термостатов PTC/NTC

Eliwell ID 961

Eliwell ID 961

Eliwell ID 961

ID 961 — для холодильных установок средней температуры. Температурные датчики РТС / NTC (на выбор) и выходным реле для управления компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 961 LX

Eliwell ID 961 LX

Eliwell ID 961 LX

ID 961 LX — для холодильных установок средней температуры. Cнабжены входом под температурные датчики РТС (NTC может выбираться параметром) и выходным реле для управления компрессором. Продолжительность разморозки определяется временными интервалами остановки компрессора

Eliwell ID 970

Eliwell ID 970

Eliwell ID 970

ID 970 — для холодильных установок средней или низкой температуры. Датчики PTC / NTC, два выходных реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 970 LX

Eliwell ID 970 LX

Eliwell ID 970 LX

ID 970 LX — для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC и двумя выходными реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 971

Eliwell ID 971

Eliwell ID 971

ID 971 — контроллер для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC, два реле для управления компрессором и оттайкой

Eliwell ID 971 LX

Eliwell ID 971 LX

Eliwell ID 971 LX

ID 971 LX — для холодильных систем два реле, два датчика, цифровой вход. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Работа вентилятора контроллером не программируется

Eliwell ID 974

Eliwell ID 974

Eliwell ID 974

ID 974 — для вентилируемых холодильных установок средней и низкой температуры. Датчики PTC / NTC. Три реле для управления компрессором, вентилятором и оттайкой. Оттайка задается по времени или по достижению температуры испарителя

Eliwell ID 974 LX

Eliwell ID 974 LX

Eliwell ID 974 LX

ID 974 LX — для вентилируемых холодильных установок средней и низкой температуры, два входа для датчиков PTC (или NTC); три реле для управления процессором, вентилятором и оттайкой; цикл оттайки задается по времени или по достижению температуры испарителя

Eliwell ID 975 LX

Eliwell ID 975 LX

Eliwell ID 975 LX

ID 975 LX — для вентилируемых холодильных установок средней и низкой температуры. Два датчика PTC / NTC. Четыре выходных реле предназначены для управления компрессором, вентилятором, разморозкой и авариями. Аварийное реле может быть запрограммировано для дополнительной нагрузки

Eliwell ID 985 LX

Eliwell ID 985 LX

Eliwell ID 985 LX

ID 985 LX — для вентилируемых холодильных установок средней и низкой температуры. Три температурных датчика PTC / NTC. Четыре выходных реле для управления компрессором, вентилятором, разморозкой и авариями (причем аварийное реле может быть запрограммировано для дополнительной нагрузки)

Eliwell ID 961-971-974 Plus

Eliwell ID 961-971-974 Plus

Eliwell ID 961-971-974 Plus

ID PLUS 961 — 971 — 974 Электронные контроллеры статических и вентилируемых холодильных установок

Eliwell EW 961 - 974

Eliwell EW961-974(аналог ID974)

Eliwell EW 961 — 974

EW961-974 — для невентилируемых холодильных установок средней температуры. Температурные датчики PTC / NTC. Реле для управления холодильным компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора

Eliwell ID 983-985 LX

Eliwell ID 983-985 LX

EliwellI D 983-985S E CK, ID 983-985 E LX

ID 983-985 LX — для холодильных систем четыре программируемых реле, три датчика NTC / PTC, два цифровых входа. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Возможен вариант использования в режиме один компрессор два воздухоохладителя. Подключается к сети LINK.

Eliwell Energy XT

Eliwell Energy XT

Eliwell Energy XT

Energy XT — серия программируемых контроллеров фирмы Eliwell, работающих в сферах кондиционирования и хладопроизводства. Energy XT, построен на базе 16-битного микропроцессора

Eliwell EWCM 900 S

Eliwell EWCM 900 S

Eliwell EWCM 900 S

EWCM 900/S — предназначен для управления машинным залом холодильной установки, в котором находятся компрессоры простого действия, многоступенчатые или различной мощности. Эти приборы также предназначены для управления вентиляторами конденсаторного агрегата. EWCM 900/S с 11 релейными выходами, может быть с входом под напряжением или же с температурным входом (зондом NTC).

Eliwell EWDR 902

Eliwell EWDR 902

Eliwell EWDR 902

EWDR 902 представляет собой серию микропроцессорных, полностью программируемых контроллеров с одной точкой срабатывания. Три различные версии разработаны для следующих применений: EWDR 902/T — для температуры; EWDR 902/R — для относительной влажности; EWDR 902/P — для давления

Eliwell EWDR 905

Eliwell EWDR 905

Eliwell EWDR 905

EWDR 905 представляет собой серию микропроцессорных, полностью программируемых контроллеров с двумя точками срабатывания или Нейтральной Зоной. Три различные версии разработаны для следующих применений: EWDR 905/T — для температуры; EWDR 905/R — для относительной влажности; EWDR 905/P — для давления

Eliwell EWCM 400

Eliwell EWCM 400

Eliwell EWCM 400

Серия EWCM 400 — контроллеры невысокой стоимости, специально разработанные для управления машинным залом холодильной системы. Они могу управлять максимум четырьмя простыми компрессорами и вентиляторами конденсатора установки

Eliwell EWDR 976 NTC

Eliwell EWDR 976 NTC

Eliwell EWDR 976 NTC

EWDR 976 NTC – контроллер, разработанный для управления разморозкой нескольких испарителей одной холодильной системы, управляемой только одним прибором серии DIGIFROST® (называемым Мастером) в котором должно иметься реле разморозки и датчик температуры испарителя (EWLC 74, EWPX 971, EWPX 185…).

Eliwell EWDR 975

Eliwell EWDR 975

Eliwell EWDR 975

EWDR 975 – контроллер, специально разработанный для холодильных установок. Он используется в сочетании с другим холодильным контроллером серии DIGIFROST® (за исключением EWPC 961/970 и ID 961/970) для систем с двойным контуром охлаждения, т.е. два компрессора и два испарителя

Eliwell Energy XT PRO

Eliwell Energy XT PRO

Eliwell Energy XT PRO

Energy XT PRO — серия свободно программируемых контроллеров фирмы Eliwell, которые легко подстраиваются под требования потребителя, работающих в сферах кондиционирования и хладопроизводства. Energy XT PRO, построен на базе 16-битного микропроцессора

Eliwell EWTR HR PR 920

Eliwell EWTR HR PR 920

Eliwell EWTR HR PR 920

EWTR 920 – это серия полностью программируемых приборов для применений с двумя рабочими точками; выхода управляются по принципу Вкл./Выкл. Существуют 3 различных версии контроллеров для Температуры EWTR 920, Относительной Влажности EWHR 920 и Давления EWPR 920.

Eliwell EWDR 984

Eliwell EWDR 984

Eliwell EWDR 984

EWDR 984 – для вентилируемых холодильных установок, 3 входа под температурные датчики NTC/PTC, 2 конфигурируемых цифровых входа. Три реле для управления компрессором, разморозкой и вентилятором. Дополнительный конфигурируемый выход 12В/ 20мА для аварий или т.п. Разморозка осуществляется остановкой компрессора на заданное время или достижения порогового значения температуры испарителя

Eliwell IWC 720-730

Eliwell IWC 720-730

Eliwell IWC 720-730

IWC720-730 — для оборудования вентилируемых холодильных установок при нормальной или низкой температуре. Настраивается в зависимости от потребностей контроля и управления. Контролирует до трех входов для датчиков температуры. Предусматривает до шести выходных реле для управления компрессором, размораживания, вентиляторов испарителя, сигнализации, регулятора включения и выключения, а также для вспомогательного производства

Eliwell IWС 720-730 RUS

Eliwell IWС 720-730 RUS

Eliwell IWС 720-730 RUS

Eliwell IWC 740-750

Eliwell IWC 740-750

Eliwell IWC 740-750

IWС 740-750 — электронный регулятор для «вентилируемых» холодильных агрегатов

Eliwell EWDR 984 LX

Eliwell EWDR 984 LX

Eliwell EWDR 984 LX

EWDR 984 LX — 3 входа под температурные датчики NTC / PTC, два конфигурируемых цифровых входа и три реле. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Звуковая сигнализация по температурных авариях. Монтаж на DIN-рейку

Eliwell EWRC 300 500 NT

Eliwell EWRC 300 500 NT

Eliwell EWRC 300 500 NT

Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации. Приборы серии Coldface имеют 3 или 5 конфигурируемых реле в зависимости от модели, 2 конфигурируемых цифровых входа для реле двери и других целей. Имеются модели с часами и годовым календарем и с поддержанием функции записи событий в соответствии с протоколом HACCP.

Eliwell_EWRC_300_500_5000NT

Eliwell EWRC 300 500 5000 NT

Eliwell_EWRC_300_500_5000NT

Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации

  1. 20.06.2015, 03:25

    #1

    Комильфо вне форума


    Новичок


    По умолчанию Eliwell EWPlus 961: установка температуры

    Здравствуйте!!!

    Подскажите, пожалуйста, как настроить нужную температуру на контролере.

    Дело в том, что есть витрина с колбасой и на контролере температура не опускается ниже 10, а надо как минимум 5.
    Нашла инструкцию, но, естественно, не разобралась с ней (точнее попробовала изменить рабочую точку, но увы… Сначала температура понижалась (где-то до 7 упала), а на утро снова стала 10)

    Пожалуйста, подскажите, что делать. Желательно пошагово, а то боюсь не разобраться в профессиональном сленге.


  2. 20.06.2015, 04:18

    #2

    юкон на форуме


    Мастер


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Сначала температура понижалась (где-то до 7 упала), а на утро снова стала 10)

    У вас проблемы с холодом, а не с настройками, срочно нужен мастер.


  3. 20.06.2015, 06:52

    #3

    МОРОЗ КРАСНЫЙ НОС вне форума


    морозильщик

    Аватар для МОРОЗ КРАСНЫЙ НОС


    По умолчанию

    И по реже в него за колбасой заглядывать, может и наберёт.


  4. 20.06.2015, 06:57

    #4

    R13a вне форума


    Мастер

    Аватар для R13a


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Пожалуйста, подскажите, что делать. Желательно пошагово, а то боюсь не разобраться в профессиональном сленге.

    Вызвать холодильщика , который и неисправность определит и устранит её.

    Цитата Сообщение от юкон
    Посмотреть сообщение

    У вас проблемы с холодом, а не с настройками, срочно нужен мастер.


  5. 20.06.2015, 08:05

    #5

    Alexholod вне форума


    Местный


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Дело в том, что есть витрина с колбасой и на контролере температура не опускается ниже 10, а надо как минимум 5.

    Так на контроллере высвечивается температура в настоящий момент и то, что она не опускается до требуемой не означает, что надо её настраивать. надо делать диагностику и ТО, а там как карты лягут. Вызывай мастера и нечего тебе в настройках контроллера лазить не для тебя он мастерами настраивается.


  6. 20.06.2015, 21:02

    #6

    БАРИН вне форума


    Пользователь


    По умолчанию

    уважаемая . пригласите мастера и не мучайте контролер


  7. 20.06.2015, 21:17

    #7

    Вьюга4 вне форума


    Демагог с Большой буквы )

    Аватар для Вьюга4


    По умолчанию

    Шаг первый: убедиться что настроено — нажать дважды кнопку «Set» (первая надпись будет на экране также «Set»).
    Шаг второй: убедиться что имеем — нажать один раз кнопку «Set», и потом один раз нажать кнопку «стрелка вниз», и после появления надписи «РВ1» и снова нажать кнопку «Set». Появившееся на экране значение указывает на ту температуру, которую холодильный агрегат достигает.
    Если значение «Set» не равно значению «РВ1» более, чем на три градуса, то перепроверить несколько раз в течение 4-х часов и при наличии серьезного расхождения вызвать обслугу на предмет лечения холодильной установки.
    Для колбасы у нас нужно +3…


  8. 20.06.2015, 21:48

    #8

    R13a вне форума


    Мастер

    Аватар для R13a


    По умолчанию

    Цитата Сообщение от Вьюга4
    Посмотреть сообщение

    Для колбасы у нас нужно +3…

    У нас +2 . СЭС со своими термометрами ходит , так что лучше перебдеть.


  9. 20.06.2015, 22:37

    #9

    muravei77 вне форума


    сервисник

    Аватар для muravei77


    По умолчанию

    Цитата Сообщение от R13a
    Посмотреть сообщение

    У нас +2

    вы не РФ??)) плюс 2-6 в этом интервале «гастроном» гуд..

    Если масла нету в репе, то и в тумбочке не будет… )


  10. 20.06.2015, 22:57

    #10

    Вьюга4 вне форума


    Демагог с Большой буквы )

    Аватар для Вьюга4


    По умолчанию

    Цитата Сообщение от R13a
    Посмотреть сообщение

    У нас +2 . СЭС со своими термометрами ходит , так что лучше перебдеть.

    Тут есть технологическая заморочка, на которую «попадают» многие продавцы — желая подольше хранить колбасы, они «накручивают» побольше холода, в результате каждое утро перебирают в витрине колбасы с целью удаления белого налета)))) При +3 такого не наблюдается.


  11. 20.06.2015, 23:39

    #11

    фреон22 вне форума


    Местный


    По умолчанию

    Приколбасах ставлю 0 -3 копченые полукопченые косяков небыло самое главное не окисляится.


  12. 20.06.2015, 23:46

    #12

    Вьюга4 вне форума


    Демагог с Большой буквы )

    Аватар для Вьюга4


    По умолчанию

    Цитата Сообщение от фреон22
    Посмотреть сообщение

    Приколбасах ставлю 0 -3 копченые полукопченые косяков небыло самое главное не окисляится.

    Это сильно зависит от расположения датчика room (точнее — от общераспространенной в твоей местности линейки техники). Есть и в моих кругах витрины под колбасы, работающие при минус 1, и при 0…+2 имеются, но их количество незначительно.
    Как пример — самарские витрины Север, работают на колбасе и молочке только с дифф.= 4. Любые попытки уменьшить дифф., сразу приволдят к расхождению ткмпературы на «+» в экспозиции, и на «-» в запаснике. Вариантов нет, проверено неоднократно — если нужна одинаковая температура во всей витрине, то только дифф = 4, и чтобы изменить это, нужно только перемещая в другое место датчик, + калибровка.
    И не один раз приходилось вначале убеждать не ставить ниже +3, а через месяц приезжать на вызов, и за отдельную копейку менять значение на оптимальное))))


  13. 21.06.2015, 00:07

    #13

    фреон22 вне форума


    Местный


    По умолчанию

    Налето короче с весны до осени ставлю на колбасы копченые и полукопченые 0-3 пока косков небыло но это в ка мере среднен температур.В прилавки до нуля .


  14. 21.06.2015, 04:10

    #14

    Комильфо вне форума


    Новичок


    По умолчанию

    Не знаю, может быть кому-то поможет, но вроде проблема решена…
    Мы на ночь его выключили (естественно переместив все продукты в другие холодильники), утром везде вокруг была вода, лоток для воды полный, но это не беда.
    Включили, и вот уже часа 4 держится температура 5-5.2


  15. 21.06.2015, 04:17

    #15

    Комильфо вне форума


    Новичок


    По умолчанию

    Цитата Сообщение от Вьюга4
    Посмотреть сообщение

    Шаг первый: убедиться что настроено — нажать дважды кнопку «Set» (первая надпись будет на экране также «Set»).
    Шаг второй: убедиться что имеем — нажать один раз кнопку «Set», и потом один раз нажать кнопку «стрелка вниз», и после появления надписи «РВ1» и снова нажать кнопку «Set». Появившееся на экране значение указывает на ту температуру, которую холодильный агрегат достигает.
    Если значение «Set» не равно значению «РВ1» более

    Спасибо большое!
    Все проверила, все нормально


  16. 21.06.2015, 06:21

    #16

    LEO351 вне форума


    Рождённый в СССР

    Аватар для LEO351


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Спасибо большое!
    Все проверила, все нормально

    Ого, сэт понажимала и все починилось?


  17. 21.06.2015, 07:58

    #17

    ref вне форума


    Холодильщик — люблю тепло

    Аватар для ref


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Не знаю, может быть кому-то поможет, но вроде проблема решена..

    До следующего «зашубливания» испарителя.

    Кто понял жизнь, тот не спешит…
    Ремонт холодильников в Литве — Висагинас и соседние районы. http://refer.lt


  18. 21.06.2015, 08:09

    #18

    R13a вне форума


    Мастер

    Аватар для R13a


    По умолчанию

    Когда в витрину , на которой указана норма выкладки в 100 килограмм запихивают пол тонны колбасы , упирая её в испаритель и удивляются тому , что температуру не набирает и очень быстро зашубливается , я не поясняю уже ничего , тыкаю в инструкцию к витрине и беру деньги за вызов , если это происходит регулярно в одних и тех же магазинах . Просто говорить уже надоело.


  19. 21.06.2015, 08:55

    #19

    Комильфо вне форума


    Новичок


    По умолчанию

    Цитата Сообщение от LEO351
    Посмотреть сообщение

    Ого, сэт понажимала и все починилось?

    Ну да… Двух высших хватило понажимать
    А если без детского стеба, то человек понятно объяснил что именно посмотреть, и за это ему спасибо


  20. 21.06.2015, 09:07

    #20

    ref вне форума


    Холодильщик — люблю тепло

    Аватар для ref


    По умолчанию

    Цитата Сообщение от Комильфо
    Посмотреть сообщение

    Ну да… Двух высших хватило понажимать

    Еще бы инструкцию на витрину проштудировать, а не на контролере кнопочки жамкать.
    А там, вполне достаточно умения вдумчиво читать и выполнять инструкцию))

    Кто понял жизнь, тот не спешит…
    Ремонт холодильников в Литве — Висагинас и соседние районы. http://refer.lt


Похожие темы

  1. Ответов: 3

    Последнее сообщение: 15.10.2019, 18:11

  2. Ответов: 14

    Последнее сообщение: 03.09.2018, 23:31

  3. Ответов: 15

    Последнее сообщение: 21.01.2016, 21:13

  4. Ответов: 57

    Последнее сообщение: 07.06.2014, 11:26

Социальные закладки

Социальные закладки
  • Отправить на Google

    Google


Ваши права

  • Вы не можете создавать новые темы
  • Вы не можете отвечать в темах
  • Вы не можете прикреплять вложения
  • Вы не можете редактировать свои сообщения
  •  
  • BB коды Вкл.
  • Смайлы Вкл.
  • [IMG] код Вкл.
  • [VIDEO] код Вкл.
  • HTML код Выкл.

Правила форума

Электроподключение прибора

Внимание! Никогда не производите электрические подключения на запитанном приборе.

Для электрических подключений прибор имеет винтовые терминалы под кабели сечением до 2,5 мм2   (для силовых подключений один провод на клемму). Нагрузочная способность клемм указана на этикетке.. Не превышайте допустимых токов нагрузки, для более мощных нагрузок  используете соответствующие контакторы. Убедитесь в соответствии используемого источника питания указанному на этикетке. Датчики неполярные и их можно удлинять  двухжильным кабелем (помните, что удлинение кабелей снижает электромагнитную устойчивость прибора, поэтому уделяйте особое внимание прокладке кабелей). Кабели датчиков, источника питания и шины TTL должны быть разнесены с силовыми кабелями (кабелями силовых нагрузок).

Панель управления и элементы индикации

Панель управления и элементы индикации

Кнопки

Индикаторы

Доступ и работа с меню

Ресурсы организованы в два меню, доступ к которому открывается коротким нажатием  на кнопку set («Меню состояния») или удержанием кнопки set  более 5-ти секунд («Меню программирования»).set

Если ни одна из кнопок не нажимается в течение 15 секунд (задержка) или была коротко нажата кнопка, то последние изменения подтверждаются, и осуществляется возврат к предыдущему дисплею (на уровень выше).

Список возможных неисправностей

E1 Ошибка датчика Pb1 (объем) значение вне допустимого рабочего диапазона датчик закорочен или оборван На дисплее появляется метка E2 Загорается иконка аварии Аварии по пределам блокируются Компрессор работает по значениям параметров Ont и OFt проверьте тип датчика (только NTC) проверьте подключение датчика замените неисправный датчик
E2 Ошибка датчика Pb2 (испаритель) значение вне допустимого рабочего диапазона датчик закорочен или оборван На дисплее появляется метка E2 Загорается иконка аварии Разморозка завершается по времени (dEt) Вентилятор работает по запросу компрессора (вместе с ним) проверьте тип датчика (только NTC) проверьте подключение датчика замените неисправный датчик
AH1 Верхний предел по температуре датчика Pb1 • значение с  Pb1 > HAL дольше времени “tAO”. (смотри таблицу «Аварии по пределам») В папке аварий AL появляется метка AH1 Регулирование без изменений • Подождите пока температура с датчика Pb1 не опустится ниже предела HAL на величину дифференциала AFd
AL1 Нижний предел по температуре датчика Pb1 • значение с Pb1 < LAL дольше времени “tAO”. (смотри таблицу «Аварии по пределам») В папке аварий AL появляется метка AL1 Регулирование без изменений • Подождите пока температура с датчика Pb1 не  поднимется выше предела LAL на величину дифференциала AFd
EA Внешняя авария • Активизирован цифровой вход, настроенный как внешняя авария (смотри значения для H11) В папке аварий AL появляется метка EA Загорается иконка аварии Регулирование блокируется. если EAL=y • устраните причину срабатывания цифрового входа внешней аварии.
Opd Авария открытой двери • Активизирован цифровой вход, настроенный как реле двери (смотри значения для H11) дольше времени tdO) Во время отсчета tdO аварии по пределам блокируются, а по ее иссечении: В папке аварий AL появляется метка Opd Загорается иконка аварии Регулирование блокируется закройте дверь камеры аварии по пределам начнут обслуживаться по истечении задержки OAO после закрытия двери
Ad2 Завершение Разморозки по времени • Разморозка завершилась по времени, т.е. значение с датчика Pb2 не достигло значения dSt – температуры прерывания цикла В папке аварий AL появляется метка Ad2 Загорается иконка аварии • дождитесь запуска очередного цикла Разморозки для автоматического сброса

Ручная разморозка

Для ручного запуска цикла разморозки удерживайте нажатой кнопку  set не менее 5 секунд. Если условий для разморозки нет (например, не истекла задержка OdO ≠ 0 или в моделях ID971 и ID974: температура датчика испарителя Pb2 выше температуры завершения разморозки dSt), то дисплей мигнет 3 раза для указания вам на то, что операция выполнена быть не может.

Схема подключения

EW96

схема подключения EW961

EW971

схема подключения EW971

EW974

схема подключения EW974

Примечание: таблица программируемых параметров доступна в файле ниже.

Скачать руководство по эксплуатации.

2

(2.5 mm

; one wire each terminal only).

Display: 12.5 mm LED (0.50″).

Push buttons: located on front panel.

Data storage: non-volatile EEPROM

memory.

Operating temperature: –5…65 °C

(23…149 °F).

Storage temperature: –30…75 °C

(–22…167 °F).

Output: one (1) SPDT relay 8(3)A 250V a.

Input: PTC probe.

Resolution: 1 °C (°F).

Accuracy: better than 0.5% of full scale.

Power supply (depending on model):

12 Va/c ±15% or 24 Va/c ±15%.

DISCLAIMER

This manual and its contents remain the

sole property of Invensys Controls Italy

s.r.l., and shall not be reproduced or dis-

tributed without authorization. Although

great care has been exercised in the

preparation of this document, Invensys

Controls Italy s.r.l., its employees or its

vendors, cannot accept any liability what-

soever connected with its use. Invensys

Controls Italy s.r.l. reserves the right to

make any changes or improvements with-

out prior notice.

Invensys Controls Italy s.r.l

via dell’Industria, 15 Zona Industriale Paludi

32010 Pieve d’Alpago (BL) ITALY

Telephone +39 0437 986111

Facsimile +39 0437 986066

Email info@climate-eu.invensys.com

Internet http:/www.climate-eu.invensys.com

1/2001 eng

cod. 9IS40120

3

EWPC 961 1/2001 eng