EN-Instruction sheet
Technical highlights
y Pre-programmed — ready to use
y Compressor protection against instable voltage
y High condensing temperature protection
y Compact design — total depth is only 46 mm
y Real 16A power relay — up to 2.5 HP compressors
y Automatically controlled brightness of large-size LED display
y Fully compatible with flammable refrigerants (R290)
y Moisture protection (housing & coating)
y Advanced defrost algorithms
Technical specifications
FEATURES
DESCRIPTION
100 VAC — 240 VAC 50-60 Hertz, automatic switch mode
Power supply
power supply
Rated power
Less than 0.5 W
Danfoss NTC Air temperature probes
2 analogue inputs
Danfoss NTC Condenser
temperature probes (optional)
Output compressor
16 (16A) EN60730; 16 (16A) CQC;
16A (16A FLA/72A LRA) UL60730
relay
LED display, 3 digits, decimal point and
Display
multi functionality icons, °C scale
Operating
0 °C to 55 °C, 93% rH
conditions
Storage conditions
-40 °C to 85 °C, 93% rH
Measurement range -40 °C to 85 °C
Front: IP65/Rear: water and dust protection
Protection
corresponds to IP31, accessibility of connectors limit
rear part rating to IP00
Pollution degree III
Environmental
(can be mounted inside a refrigerated cabinet),
non-condensing
Resistance to heat
Category D (UL94-V0)
& fire
EMC category
Category I
Compressor relay:
Operating cycles
more than 175,000 at full load ((16A) 16A)
R290/R600a: EN/IEC 60079-15:2005,
Glow wire according to EN/IEC 60335-1,
Approvals
IEC/EN 60730, UL60730, NSF, CQC, GOST R 60730
Note: These approvals are only valid when using the
accessories listed in this document
Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014
ERC 101 kit
Installation
y Insert the ERC 101 in to the cabinet
y Attach the clips to each side of the
ERC 101
Input/output
DO
1(o1)
DO1:
2
L
UL: 16FLA 72LRA,
3
N
IEC: 16(16)A
Input/
Cabinet
Evapor.
Conden.
Sensors
Sensors
Sensors
Sensors
S1
S2
1
2
3
DO & Input/Sensors
Dimensions mm
^
^
78.25 mm
ERC 101
controller
100-240VAc +/-10% 50/60Hz
OT 55
S1
S2
71 mm
30 mm
47.25 mm
rear mounting
51.25 mm
DKRCC.EI.RL0.A3.02/520H8599
Display/operation
Press BRIEFLY to defrost
Press the button
5 seconds to ON/OFF
The green def symbol is list
when in defrost mode
Press: variable direct function defrost
Sub function: BACK
Press: upper left button BACK
to return to parameter group
To select: press the lower
left button (OK)
Press: variable direct functionON/OFF
Sub function: OK
Operation menu
Press 5 sec both right buttons
to access the menu
1) Parameter groups
^
^
^
Scroll through the
menu group
^
Higher left button to exit
Lower left button to con rm
2) Parameter name
Higher left button to exit
Lower left button to con rm
IMPORTANT NOTE
The inputs are not galvanic separated and are connected directly to
the mains supply! For that reason, door-switches, sensors as well as the cables must fulfil the reinforced
insulation requirements.
Safety info
Risk of electrocution!
For mounting: do not connect mains power until the controller is correctly mounted.
For unmounting: disconnect the power supply before unmounting
^
Press UP/DOWN to
adjust setpoint
^
Flasching
Press any button to acknowlege
Press: tempearture setpoint
sub function: UP
Press and hold for 5 seconds
^
to enter the menu
Press: UP/DOWN to scroll
^
through the menu
Press: tempearture setpoint
sub function: DOWN
^
Scroll through the
^
3) Parameter value
1
Danfoss серия ERC — холодильные контроллеры Danfoss | Управление Холодом
Types of Manuals:
The main types of Danfoss ERC 101 kit instructions:
- User guide — rules of useing and characteristics
- Service manual — repair, diagnostics, maintenance
- Operation manual — description of the main functions of equipment
Controller Instructions by Danfoss:
-
Carel UltraCella
UltraCella EVD Modules accessoriesPower Module – accessory121231212322121211N22121211111212111121222A1212Connection to option modulesNpower supply, compressor fan, actuatorsprobes, digital inputs20029087,5107,547,547,53015626032100FieldBus24 VacBMSR6R5R4R3R2R1230 V20 A maxEN60730-1UL 873250 VR5 — R612 (10) A12 A …
UltraCella Controller, 2
-
Siemens SINAMICS G120
___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________ SINAMICS SINAMICS G120 Smart Access Operating Instructions 04/2018 A5E43332487 Fundamental safety instructions 1 Product overview 2 Installing 3 Accessing the Web pages …
SINAMICS G120 Inverter, 58
-
weintek MT-508SV4
1 MT-500 series MT-508SV4, MT-508SE4, MT-509LV4 Installation Instruction 1.0 Installation and Startup Guide Install Environment Where Used The MT-500 Series is designed for use in a factory environment. It is designed to operate from 32 to 113 °F (0 to 45 °C) temperatures, as found in most industrial environme …
MT-508SV4 Controller, 2
-
CyberPower BR850ELCD
BR650ELCD / BR850ELCD / BR1000ELCD / BR1200ELCD User’s Manual K01-C0000110-00 This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read and follow all instructions carefully during installation and operation of the unit. Read thi …
BR850ELCD UPS, 2
-
Color Kinetics iColor Player
Installation InstructionsINSTRUCTIONS D’INSTALLATION INSTRUCCIONES DE INSTALACIÓN ISTRUZIONI PER L’INSTALLAZIONE INSTALLATIE-INSTRUCTIES INSTALLATIONSANWEISUNGEN インストール手順 安装指示A Must be installed by a qualified electrician in accordance with all national and local electrical …
iColor Player Controller, 4
-
Siemens LMV51 Series
Valid for the following software versions:LMV51… : V01.90Int. LC: V01.40AZL51… : V01.70CC1P7550en29. 05. 2002Siemens Building TechnologiesHVAC ProductsLMV51…Burner Control with integrated Fuel / Air RatioControl and Load Control for Forced-draft BurnersBasic Documentation …
LMV51 Series Controller, 157
- Home
- Brands
- Danfoss Manuals
- Danfoss ERC 101 kit
- Danfoss ERC 101 kit Instruction Sheet
Download or browse on-line these Instruction Sheet for Danfoss ERC 101 kit Controller.
Danfoss ERC 101 kit Manual Information:
This manual for Danfoss ERC 101 kit, given in the PDF format, is available for free online viewing and download without logging on. |
Download Manual |
Summary of Contents:
|
MAKING MODERN LIVING POSSIBLE
EN-Instruction sheet
Menu
Parameters
Cod
Description
Setpoint
Stp
Setpoint
Thermostat
tHE
Thermostat settings
Setpoint adjustment
SPr
Current setpoint adjustment value diF * SPr
ratio
Differential
diF
Thermostat differential
Air temperature
tAD
Air Temp Adjust
adjust
Alarm
ALA
Alarm setting
High temperature
Alarm is activated above this temperature
HAt
alarm
(Celsius )
Low temperature
Alarm is activated below this temperature
LAt
alarm
(Celsius )
Compressor
CoP
Compressor Setting
Minimum time compressor must run 0-30
Min run time
Crt
minutes
Minimum time compressor must idle 0-30
Min Stop time
CSt
minutes
Maximum time compressor must idle 0-480
Max OFF time
Cot
minutes
Compressor run time if temperature sensor is
Error run time
Ert
not working (0-60 minutes )
Compressor stop time if temperature sensor is
Error stop time
ESt
not working (0-60 minutes )
Minimum cut-in
When compressor is OFF:
uLi
voltage
lowest compressor start voltage (0-270 V)
Minimum cut-out
When compressor is ON:
uLo
voltage
lowest operation voltage (0-270 V)
When compressor is ON:
Maximum voltage
uHi
highest operation voltage (0-270 V)
Delay in seconds between power ON &
Power ON delay
Pod
compressor being activated
Defrost
dEF
Defrost Setting
No: defrost function is disabled,
Defrost type
dFt
nat: OFF-cycle defrost (natural defrost)
Temp at which defrost stop
Terminating temp
dtt
(evap temperature or cabinet temperature)
The minimum time in hours between the start
Def Min Interval
dii
of each defrost cycle
The maximum time in hours between the
Def Max Interval
dAi
start of each defrost cycle
The minimum duration of a defrost cycle
Def Min time
dit
in minutes
The maximum duration of a defrost cycle
Def Max time
dAt
in minutes
Condenser
Con
Condenser protection settings
Protection
Condenser Alarm
If condenser sensor exceeds this temperature,
CAL
Limit
alarm is activated
Condens er Block
If this temperature is exceeded, compressor
CbL
Lim it
will be stopped
Temperature at which compressor may start
Condenser OK limit
CoL
after a stop due to exceeding CbL
Temperature below which the compressor is
Condenser Low Temp
CLL
not allowed to start
Display
diS
Display setting
Lock-time After
dLt
Display lock time after defrost [0-60 min]
defrost
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifica-
tions already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014
ERC 101 kit
De-
Assignments
Min
Max Unit
fault
-50
80
C
2
S2 Application
0.0
1.0
—
0.0
DO1 configuration
0.0
20.0
K
2.0
Password level1
0.0
20.0
K
0
Password level2
Service
-50.0
80.0
C
15.0
Voltage value
-50.0
80.0
C
-50.0
Relay 1 counter
Interval counter
Defrost time counter
0
30
min
0
Firmware version
0
30
min
0
Hardware version
0
480
min
0
Problem solving
0
60
min
0
Problem
0
60
min
0
Compressor does not start
0
270
Vac
0
0
270
Vac
0
E01 or E02 is shown on display
Display alternates between «Con» and
0
270
Vac
270
temperature
Display alternates between «Hi» and
0
300
Sec
180
temperature
Display alternates between «Lo» and
temperature
no
nat
—
nat
0
25
C
7
0
96
hours 6
0
96
hours 7
0
240
min
10
0
480
min
30
0
85
C
75
0
85
C
85
0
85
C
60
-50
20
C
-5
0
60
min
5
Assignments of inputs and outputs
Application to be controlled with Sensor
C. (nC=Not Connected, Sco= Temp control,
S2A
nC
Con
—
EuA= Evap temp, Con=Cond temp {condenser
cleaning})
Relay output 1. compressor (CoP)
o1C
CoP
HeT
—
2. Heater HeT
PS1
Shop owner Most common parameters
0
999
—
Service technician all parameters with read
PS2
permission and possibility to change a
0
999
—
number of parameters
Service
uAC
Current main power supply voltage
0
270
Vac
Thousands of cycles of compressor relay since
rL1
0
999
1000
manufacture
int
Compressor run time since last defrost
0
999
min
dnt
Duration of last defrost cycle [min]
0
999
min
Fir
Danfoss software version number
—
—
—
HAr
Danfoss hardware version number
—
—
—
Probable cause
Remedy
Waiting for compressor delay timer
Check CoP->CSt
Line voltage to compressor too low or too high Check CoP->uLi, uLo, uHi
E01: Sensor «S1» defective
Replace sensor
E02: Sensor «S2» defective
Condenser temperature exceeds the
Clean condenser,
temperature set in condenser settings menu
Check Con->CAL, CbL
Temperature too high
Check ALA->HAt
Temperature too low
Check ALA-> LAt
DKRCC.EI.RL0.A3.02/520H8599
nc
CoP
0
0
—
—
—
—
—
—
2