Контроллер danfoss erc 112c инструкция

Danfoss ERC 112 User Manual

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

User Guide

Electronic Refrigeration Controller

ERC 112

This user guide is intended to be used by OEMs for the purpose of

programming ERC 112. It may also be useful for technicians. However, it is not

intended as a user guide for end users.

www.danfoss.com/erc

loading

Related Manuals for Danfoss ERC 112

Summary of Contents for Danfoss ERC 112

  • Page 1
    Electronic Refrigeration Controller ERC 112 This user guide is intended to be used by OEMs for the purpose of programming ERC 112. It may also be useful for technicians. However, it is not intended as a user guide for end users. www.danfoss.com/erc…
  • Page 2
    User Guide | ERC 112 Refrigeration Controller Introduction Temperature control for refrigeration appliances. Application Front panel mounting. The latest generation CPU, plenty of memory Advantages and high-end electronic components allow for a uniquely versatile software. Three separate password-protected user levels can be used to control more than 300 different parameters to fit all individual requirements.
  • Page 3: Typical Application

    User Guide | ERC 112 Refrigeration Controller Typical application Glass Door Merchandiser No-frost freezer/sub-zero cooler S3, S4 are optional S2, S3, S4 are optional Gastro No-frost freezer/Cooler S3, S4 are optional S2, S3, S4 are optional © Danfoss | DCS (vt) | 2019.07…

  • Page 4: Product Overview

    User Guide | ERC 112 Refrigeration Controller Product overview Display The ERC 112 is an electronic refrigeration controller with an LED display especially developed for bottle coolers and commercial fridges and freezers. It is particularly suited for OEM customers where time, easy and reliable installation and high quality need to go hand in hand with flexibility.

  • Page 5: Quick Programming

    User Guide | ERC 112 Refrigeration Controller Quick programming Software for PC KoolProg Software from Danfoss for programming the ERC-controller via a PC rather than with the front panel buttons. https://www.danfoss.com/en/service-and- support/downloads/dcs/koolprog/ USB gateway USB gateway The USB Gateway is a laboratory tool, offering fast and easy programming of any ERC controller connected directly to the PC.

  • Page 6: Technical Specs

    FLA2/LRA12, TV-1 8 A resistive, 2(2) A Max 10 A total «DO4-6» Danfoss NTC sensors and Danfoss ECO accessories (Light, Motion and Door sensors) Probes Danfoss Pt 1000 ohm/0°C Modular connector system for OEM customers, with optional output screw terminal adapter;…

  • Page 7
    User Guide | ERC 112 Refrigeration Controller Connections ERC 112C (3 relays) (Inputs and outputs are configurable) ERC 112D (4 relays) Note S4 Port can also be used to connect other sensors and Door sensor. © Danfoss | DCS (vt) | 2019.07…
  • Page 8: Code Numbers

    User Guide | ERC 112 Refrigeration Controller Code numbers Type I-Pack Type I-Pack Qty. Code no. Qty. Code no. ERC 112C, Red LED, without 080G3202 -100 – 200 °C, Pt 1000 buzzer S4, 1000 mm, 3-pole 080G3350 ERC 112D, Red LED, without…

  • Page 9: Manual Operation With Buttons (Direct Access)

    User Guide | ERC 112 Refrigeration Controller Operation The controller can be configured in four ways: All these tools are supplied separately. Programming Tools Using: For technical literature and further information, • KoolProg and KoolKey as Gateway please contact your local Danfoss representative.

  • Page 10: Fan Settings

    Min. -100.0°C In standard operation the set point is changed by simply pressing the Max. 200.0°C «temperature up/down» buttons on ERC 112; for laboratory and Default 2.0°C assembly line you may opt for software controlled set point adjustment (speed improvement) «SPr»…

  • Page 11
    User Guide | ERC 112 Refrigeration Controller «FSt» Fan Minimum Stop time Minimum stop time for fan protection. Min. 0 s Max. 960 s Default 10 s «FdC» Fan Δt cut in (This parameter is only applicable with Automatic fan control «Aut» mode.) Min.
  • Page 12
    User Guide | ERC 112 Refrigeration Controller «Pdi» Pull Down Defrost Interval This is the time between defrost cycles during pull down. It is measured in hours and can be up to 48 hours. Min. 0 hour During pull down, this setting overrides the defrost interval and defrost time settings (see the defrost section).
  • Page 13
    User Guide | ERC 112 Refrigeration Controller «dot» Drip OFF Time This parameter can be set to between 0 and 60 minutes and defines how long the delay is between the heater being switched Min. 0 min OFF and the compressor starting again.
  • Page 14: Compressor Settings

    User Guide | ERC 112 Refrigeration Controller Compressor settings «uPt» Voltage protection «no»: no voltage protection. «yES»: voltage protection activated based on voltage related settings. Min. no Max. yes Default no «uLi» Minimum cut-in voltage/uLi. Minimum cut-out voltage/uLo. Maximum voltage/uHi Min.

  • Page 15
    The controller can have its display intensity (brightness) set in one of Min. 2 two ways: Max. 10 A) With a Danfoss ambient light sensor attached, the brightness of the Default 10 display is adjusted automatically according to the ambient light level (see the assignments section).
  • Page 16: Display Unit

    User Guide | ERC 112 Refrigeration Controller «CFu» Display Unit This parameter sets the display to Fahrenheit or Celsius. Switching from Min. °C one to the other will cause all temperature settings to be automatically Max. °F updated accordingly. Default °C «trS»…

  • Page 17
    User Guide | ERC 112 Refrigeration Controller «SdF» Show Defrost If set to «yES», this parameter causes the display to show DEF when the Min. no system is in defrost mode. If set to «nO», the temperature continues to Max. yes be displayed.
  • Page 18
    User Guide | ERC 112 Refrigeration Controller «Pdd» Pull down delay Normally, it is not necessary or desirable to sound an alarm during a pull Min. 0 min down (the initial phase of reaching the desired temperature). This Max. 960 min Default 240 min parameter prevents the high temperature alarm «HAt»…
  • Page 19
    Default 2.0 K ECO strategy NOTE: some of these parameters require the installation of the Danfoss Ambient Light Sensor. The Danfoss USB Gateway in combination with «KoolProg Software» allows for real time measurement of the current light intensity. Danfoss recommends test- ing and adjusting «SLd»…
  • Page 20
    User Guide | ERC 112 Refrigeration Controller «Euu» EWU active on/OFF Enable or disable early wake up. Min. no Max. yes Default yes «CLH» Shop close hour Shop is assumed to be closed when staying in ECO mode longer than shop close hour.
  • Page 21
    Please contact your local Danfoss representative for information about default settings. NOTE: coded sensors will impact on the number of possible configurations. For instance: Danfoss supplies only 2-pole defrost sensors, so input «S3» will most likely be used as a defrost/evaporator temperature sensor input. «S1C» S1 Config/S1C…
  • Page 22
    User Guide | ERC 112 Refrigeration Controller «diC» DI Config This is the digital input used for a digital sensor or bus communications. Default non «non»: not used. «doC»: door contact, contact closed when door closed. «doo»: door contact, contact open when door closed.
  • Page 23
    You may not therefore have access to change all the passwords. Passwords are entered by using the up and down arrow buttons. Min. 0 Max. 999 Danfoss advises against using passwords which are easy to remember Default 0 or enter, for example 111, 222, 123 etc. «PS3″…
  • Page 24
    User Guide | ERC 112 Refrigeration Controller «HAr» HW version Danfoss hardware version number. «onL» OrderNoLow Danfoss order code number. «onH» OrderNoHigh Danfoss order code number. «oEL» OEM code Low «oEn» OEM code Middle «oEH» OEM code High «PAr» Parameter version OEM parameter version number [requires EKA copy key update].
  • Page 25: Troubleshooting

    User Guide | ERC 112 Refrigeration Controller Troubleshooting Problem Probable cause Remedy Compressor does not start Waiting for compressor delay timer Check CoP->CSt Defrost in progress Check CoP ->Pot /Pod Line voltage to compressor too low Check dEF ->dit, dot or too high Check CoP->uLi, uLo, uHi…

  • Page 26: Typical Applications

    User Guide | ERC 112 Refrigeration Controller Typical applications Glass Door Merchandiser, No-frost freezer/sub-zero cooler Note: this is a typical (default) wiring diagram since both inputs (AI/DI’s) and outputs (DO’s) can be assigned differently. Please see «ASi», assignment ERC 112D…

  • Page 27
    User Guide | ERC 112 Refrigeration Controller Gastro No-frost freezer ERC 112D Controller Red LED with buzzer 080G3213 Red LED with buzzer 080G3217 Temperature Sensor for Temperature Sensor for Temperature Sensor for Cabinet Temperature Evaporator Temperature Condenser Temperature Door input…
  • Page 28: Application Matrix

    User Guide | ERC 112 Refrigeration Controller Application Matrix ERC 112 Output Input Application ERC type Standard beverage Condenser or Ambient Door or Motion ERC 112C Comp Lamp Control Defrost cooler Light or Motion detection detection Sub-zero beverage Condenser or Ambient…

  • Page 29: Sensor Placement

    User Guide | ERC 112 Refrigeration Controller Sensor placement Control sensor The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set point. The sensor is also used for the displayed temperature.

  • Page 30: Condenser Sensor

    User Guide | ERC 112 Refrigeration Controller Condenser sensor The condenser sensor is used to protect the compressor against high pressure when the condenser is blocked or the condenser fan fails. Condenser sensor Place the sensor at the liquid side of the condenser.

  • Page 31
    User Guide | ERC 112 Refrigeration Controller © Danfoss | DCS (vt) | 2019.07 BC200686422115en-000802 | 31…
  • Page 32
    © Danfoss | DCS (vt) | 2019.07 BC200686422115en-000802 | 32…

Электронный холодильный контроллер ERC112 со светодиодным дисплеем, специально разработанный для охладителей бутылок, коммерческих холодильников и морозильников. Он особенно подходит для ОЕМ клиентов, так как время, простая и надежная установка и высокое качество важны наряду с гибкостью. Дисплей может быть красным или синим. Контроллер доступен с верхней левой кнопкой «ECO» или «Оттайка». Нижняя левая кнопка может быть «Свет», «Отключение» или «Ускоренное охлаждение».

Документация

Контроллер может настраиваться тремя способами: используя «Программу», при помощи док-станции или вручную посредством кнопок на фронтальной панели. «Программа», лицензированная Данфосс, предлагает простую настройку параметров посредством USB шлюза. Программа поставляется отдельно; для получения технической литературы и дополнительной информации контактируйте с местным представительством Данфосс.
Док-станция поставляется отдельно. Для получения технической литературы и дополнительной информации контактируйте с местным представительством Данфосс.

Входы 5 входов: 4 аналоговых (цифровые), 1 цифровой; назначение определяется пользователем
Световой датчик ЕСО от Данфосс Дверной датчик: все типы, пользовательские
Воздух / испаритель / конденсатор Датчик движения
Выходы   UL60730 EN60730
«DO1» (Реле компрессора) 120 В перем. ток: 16 A резистивная/FLA16/LRA72
240 В перем. ток: 10 A резистивная/FLA10/LRA60
16(16) A
«DO4» 8 A резистивная, FLA2/LRA12, TV-1 8A резистивная, 2(2) A
«DO5» FLA2/LRA12, TV-1 8A резистивная, 2(2) A
«DO6» FLA2/LRA12, TV-1 8A резистивная, 2(2) A
    Макс. 10 А всего «DO4-6»
Датчики Danfoss NTC и ЭКО аксессуары
Разъемы Модульная система разъёмов для ОЕМ-клиентов с опциональным адаптером с винтовыми клеммами.
Тип входного разъёма: Rast 2.5 Edge. Тип выходного разъёма: Rast 5 Standard
Программирование Программирование с помощью док-станции ERC от Данфосс
Сборка 3 типа: фронтальный монтаж; клипсы; полностью интегрированное решение (требуется определённый ОЕМ-дизайн монтажного отверстия)
Дисплей Светодиодный, 3-х цифровой, десятичная точка и многофункциональные иконки; шкала ˚С/˚F
Клавиатура 4 кнопки (IP65), 2 слева, 2 справа; программируемые пользователем
Рабочие условия от 0˚С до 55˚С, относительная влажность 93%
Условия хранения от -40˚С до 85˚С, относительная влажность 93%
Диапазон измерения от -40˚С до 85˚С
Защита Передняя панель: IP65, задняя часть: защита от воды и пыли в соответствии с IP31, доступность на задней панели разъёмов вводит ограничение IP00
Окружающая среда Степень загрязнения II, без конденсации
Огнестойкость и пожарозащищённость Категория D (UL94-V0)
Категория ЭМС Категория I
Рабочие циклы Реле компрессора: более чем 175 000 при полной нагрузке (16А(16А))
Сертификация R290/R600a: заключение о соответствии
EN/IEC 60335- 2-24, приложение СС и EN/IEC 60335-2-89, приложение BB Жаропрочный провод в соответствии с EN/IEC 60335- 1
I EC/EN 60730
UL60730
NSF
CQC
EAC
Эти сертификаты имеют силу только при использовании разрешенных аксессуаров

Описание ERC 112С, Контроллер температуры — 080G3206

Напряжение питания 230 В перем.тока 50Гц; 1,5 ВА
Управление компрессором да
Управление оттаиванием да
Поддержка сетевых карт нет
Гарантийные обязательства Изготовитель/продавец гарантирует соответствие контроллеров техническим требованиям при соблюдении потребителем условий транспортирования, хранения и эксплуатации.Гарантийный срок эксплуатации и хранения контроллеров – 12 месяцев с даты продажи, указанной в транспортных документах, или 18 месяцев с даты производства.Срок службы оборудования при соблюдении рабочих диапазонов согласно паспорту/инструкции по эксплуатации и проведении необходимых сервисных работ — 10 лет с даты продажи, указанной в транспортных документах.
температура среды при эксплуатации 0 до +55 °С
Число испарителей 1
Управление вентилятором да
Управление светом да
Количество цифровых входов 1
температура среды при хранении от -40 до +85 °С
Количество входов 4 Входа 3 аналоговых и 1 цифровой – назначаются пользователем
Количество реле 3 (компрессор: 16A остальные реле: 8A)
Модель ERC112C
Назначение изделия Контроллеры температуры типа ERC модификации 112 (далее – контроллеры типа ERC) используются для управления испарителем холодильной установки для поддержания заданной температуры, а также для управления его режимом оттаивания, и управления дополнительными функциями холодильного оборудования.
Количество аналоговых выходов 0
Встроенная сетевая карта нет
Количество аналоговых входов 3
Комплектность В комплект поставки входят:-контроллер температуры типа ERC;-инструкция.

Технические характеристики ERC 112С, Контроллер температуры — 080G3206

Встроенная сетевая карта нет
Количество аналоговых входов 3
Количество аналоговых выходов
Количество входов 4 Входа 3 аналоговых и 1 цифровой – назначаются пользователем
Количество реле 3 (компрессор: 16A остальные реле: 8A)
Количество цифровых входов 1
Модель ERC112C
Напряжение питания 230 В перем.тока 50Гц; 1,5 ВА
Поддержка сетевых карт нет
температура среды при хранении от -40 до +85 °С
температура среды при эксплуатации 0 до +55 °С
Управление вентилятором да
Управление компрессором да
Управление оттаиванием да
Управление светом да
Число испарителей 1