cod. 9IS42060
GB
rel. 1/05
USER INTERFACE
The user has a display and four keys for
controlling status and programming of the
instrument.
KEYS AND MENUS
UP key
Scrolls through the menu items
Increases the values
Activates manual defrost
DOWN key
Scrolls through the menu items
Decreases the values
Programmable by parameter
fnc key
ESC function (exit)
fnc
Programmable by parameter
set key
Accesses the setpoint
set
Accesses the menus
Confirms the commands
Displaying the alarms (if present)
ID961
At start-up the instrument performs a
Lamp Test; for few seconds the display and
the leds blink, in order to verify their
integrity and correct operation. The instru-
ment has two main menus: the «Machine
Status» and «Programming» menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the «set» key («Machine Status»
menu) or by holding down the «set» key
for more than 5 seconds («Programming»
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
«set» key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions.
LED
Position
Related Function
Compressor or relay 1
Defrost
Alarm
Setpoint
ID 961
electronic controllers for refrigerating units
If you do not use the keyboard for over
15 seconds (time-out) or if you press the
«fnc» key once, the last value shown on
the display is confirmed and you return to
the previous screen mask.
MACHINE STATUS MENU
(See Machine Status Menu)
To access the «Machine Status» menu
Press and quickly release the «set» key.
If alarms are not present, the label «SEt»
appears. By using the «UP» and «DOWN»
keys you can scroll through the other fold-
ers in the menu:
-Pb1: probe 1 value folder;
-SEt: Setpoint setting folder.
Set Setting
Access the «Machine Status» menu by
pressing and quickly releasing the «set»
key. The label of the «Set» folder appears.
To display the Setpoint value press the
«set» key again.
f nc
The value appears on the display.
To change the Setpoint value, use the «UP»
and «DOWN» keys within 15 seconds.
set
If the parameter is LOC = y the Setpoint
cannot be changed.
Displaying Probes
By pressing the «set» key when the appro-
priate label appears, the value of the
probe associated to it is displayed.
PROGRAMMING MENU
(See Programming Menu)
To enter the «Programming» menu, press
the «set» key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter «PA1»), and (if the
password is correct) the label of the first
folder will follow.
To scroll through the other folders, use
the «UP» and «DOWN» keys.
If the password is wrong, the display will
show the PA1 label again.
To enter the folder, press «set». The label
of the first visible parameter appears. To
scroll through the other parameters, use
the «UP» and «DOWN» keys; to change the
parameter, press and release «set», then
Status
ON when the compressor is started up; blinking in case of delay,
protection or blocked enabling
ON when defrosting; blinking in case of manual
enabling
ON when the alarm is enabled; blinking when the alarm is silenced
On for setting Setpoint
set the desired value using the «UP» and
«DOWN» keys, and confirm with the «set»
key to move to the next parameter.
PLEASE NOTE: It is suggested to switch-
off and switch-on again the instrument
everytime it is changed the configuration
of the parameters: this prevents malfunc-
tioning on regulation and delay time
occuring.
PASSWORD
The password «PA1» allows access to pro-
gramming parameters. In the standard
configuration password is not present.
To enable (value≠0) and assign it the
desired value, access the «Programming»
menu, within the folder with the «diS»
label. If password is enabled, you will see
it at the entrance of the «Programming»
menu (see the «Programming Menu» sec-
tion).
MANUAL ACTIVATION OF THE
DEFROSTING CYCLE
To manually activate the defrosting cycle,
press the «UP» key for 5 seconds.
COPY CARD
The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters. The operation is performed as fol-
lows:
Format
This command allows copy card format-
ting, an operation recommended in case
of first use.
Warning: if the copy card has been pro-
grammed, using the «Fr» the data entered
are erased. This operation cannot be can-
celled.
Upload
This operation loads the programming
parameters from the instrument.
Download
This operation downloads to the instru-
ment the programming parameters.
The operations are performed accessing
the folder identified by the «FPr» label and
selecting, according to the case, «UL», «dL»
or «Fr» commands; the operation is con-
firmed by pressing the «set» key. If the
operation is successful an «y» is displayed,
on the contrary, if it fails a «n» will be dis-
played.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instru-
ment.
Электроподключение прибора
Внимание! Никогда не производите электрические подключения на запитанном приборе.
Для электрических подключений прибор имеет винтовые терминалы под кабели сечением до 2,5 мм2 (для силовых подключений один провод на клемму). Нагрузочная способность клемм указана на этикетке.. Не превышайте допустимых токов нагрузки, для более мощных нагрузок используете соответствующие контакторы. Убедитесь в соответствии используемого источника питания указанному на этикетке. Датчики неполярные и их можно удлинять двухжильным кабелем (помните, что удлинение кабелей снижает электромагнитную устойчивость прибора, поэтому уделяйте особое внимание прокладке кабелей). Кабели датчиков, источника питания и шины TTL должны быть разнесены с силовыми кабелями (кабелями силовых нагрузок).
Панель управления и элементы индикации
Кнопки
Индикаторы
Доступ и работа с меню
Ресурсы организованы в два меню, доступ к которому открывается коротким нажатием на кнопку set («Меню состояния») или удержанием кнопки set более 5-ти секунд («Меню программирования»).set
Если ни одна из кнопок не нажимается в течение 15 секунд (задержка) или была коротко нажата кнопка, то последние изменения подтверждаются, и осуществляется возврат к предыдущему дисплею (на уровень выше).
Список возможных неисправностей
E1 | Ошибка датчика Pb1 (объем) | значение вне допустимого рабочего диапазона датчик закорочен или оборван | На дисплее появляется метка E2 Загорается иконка аварии Аварии по пределам блокируются Компрессор работает по значениям параметров Ont и OFt | проверьте тип датчика (только NTC) проверьте подключение датчика замените неисправный датчик |
E2 | Ошибка датчика Pb2 (испаритель) | значение вне допустимого рабочего диапазона датчик закорочен или оборван | На дисплее появляется метка E2 Загорается иконка аварии Разморозка завершается по времени (dEt) Вентилятор работает по запросу компрессора (вместе с ним) | проверьте тип датчика (только NTC) проверьте подключение датчика замените неисправный датчик |
AH1 | Верхний предел по температуре датчика Pb1 | • значение с Pb1 > HAL дольше времени “tAO”. (смотри таблицу «Аварии по пределам») | В папке аварий AL появляется метка AH1 Регулирование без изменений | • Подождите пока температура с датчика Pb1 не опустится ниже предела HAL на величину дифференциала AFd |
AL1 | Нижний предел по температуре датчика Pb1 | • значение с Pb1 < LAL дольше времени “tAO”. (смотри таблицу «Аварии по пределам») | В папке аварий AL появляется метка AL1 Регулирование без изменений | • Подождите пока температура с датчика Pb1 не поднимется выше предела LAL на величину дифференциала AFd |
EA | Внешняя авария | • Активизирован цифровой вход, настроенный как внешняя авария (смотри значения для H11) | В папке аварий AL появляется метка EA Загорается иконка аварии Регулирование блокируется. если EAL=y | • устраните причину срабатывания цифрового входа внешней аварии. |
Opd | Авария открытой двери | • Активизирован цифровой вход, настроенный как реле двери (смотри значения для H11) дольше времени tdO) | Во время отсчета tdO аварии по пределам блокируются, а по ее иссечении: В папке аварий AL появляется метка Opd Загорается иконка аварии Регулирование блокируется | закройте дверь камеры аварии по пределам начнут обслуживаться по истечении задержки OAO после закрытия двери |
Ad2 | Завершение Разморозки по времени | • Разморозка завершилась по времени, т.е. значение с датчика Pb2 не достигло значения dSt – температуры прерывания цикла | В папке аварий AL появляется метка Ad2 Загорается иконка аварии | • дождитесь запуска очередного цикла Разморозки для автоматического сброса |
Ручная разморозка
Для ручного запуска цикла разморозки удерживайте нажатой кнопку set не менее 5 секунд. Если условий для разморозки нет (например, не истекла задержка OdO ≠ 0 или в моделях ID971 и ID974: температура датчика испарителя Pb2 выше температуры завершения разморозки dSt), то дисплей мигнет 3 раза для указания вам на то, что операция выполнена быть не может.
Схема подключения
EW96
EW971
EW974
Примечание: таблица программируемых параметров доступна в файле ниже.
Скачать руководство по эксплуатации.
Датчик температуры POLETRON EL 961 с одним датчиком Предназначены для холодильных установок средней температуры Они снабжены входом под температурные датчики РТС (NTC может выбираться параметром) и выходным реле для управления компрессором Продолжительность циклов разморозки определяется временными интервалами остановки компрессора Считываемое датчиком значение отображается на 2-х цифровом дисплее Все версии имеют TTL порт для карточки копирования Корпус полимерный пластик PC+ABS UL94 V-0, стекло из поликарбоната, кнопки из термопласта Размеры передняя панель 72×34мм, глубина 60 мм Монтаж шаблон отверстия в панели 29×71мм Диапазон данных на дисплее –50…110 (NTC) или –50…140 (PTC) °С 3 1/2 цифры + знак Аналоговый вход 1 вход NTC или PTC (выбирается параметром) Последовательный порт TTL порт для соединения с Copy Card Цифровые выходы 1 реле: типа SPDT 8(3) А 250В перем. ток Диапазон измерений — 50…140 °С Точность не менее 0.5% от шкалы+1 цифра Разрешение 1 или 0,1 °С Мощность 3 В
Характеристики товара
Применимость товара к моделям бытовой техники
Применяется для вентилируемых среднетемпературных и низкотемпературных холодильных установок
Для покупки товара в нашем интернет-магазине выберите понравившийся товар и добавьте его в корзину. Далее перейдите в Корзину и нажмите на «Оформить заказ» или «Быстрый заказ».
Когда оформляете быстрый заказ, напишите телефон и пожелания к заказу. Вам перезвонит менеджер и уточнит условия заказа. По результатам разговора вам придет подтверждение оформления товара на почту или через СМС. Теперь останется только ждать доставки и радоваться новой покупке.
Оформление заказа в стандартном режиме выглядит следующим образом. Заполняете полностью форму по последовательным этапам: адрес, способ доставки, оплаты, данные о себе. Нажмите кнопку «Оформить заказ».
Оплачивайте покупки удобным способом. В интернет-магазине доступно 2 варианта оплаты:
- Оплата наличными при самовывозе из магазинов в городах: Краснодар, Екатеринбург, Аксай, Элиста, Светлоград.
- Безналичный расчет при любом способе доставки: карты Visa, Master Card и карты МИР. Чтобы оплатить покупку, система перенаправит вас на сервер системы Ю-Касса, где нужно ввести номер карты, срок действия и имя держателя.
Доставка заказов осуществляется со склада в Светлограде по 1 127 городам России (18 179 пунктов выдачи).
Выполняем доставку только в регионы, которые можно выбрать на сайте,
в регионы Дальнего Востока и Республики Тыва доставка рассчитывается индивидуально менеджером.
Получить заказ можно в любом из пунктов выдачи СДЭК или Почта России в вашем городе, выбранном при оформлении заказа на сайте.
- Время доставки зависит от времени размещения заказа и дальности вашего региона от г. Светлоград.
- Как правило, доставка товара занимает от 3 до 7 дней по всей России.
Воспользоваться доставкой можно только розничному клиенту при полной оплате заказа на сайте любым удобным способом. Для оптовых клиентов существуют особые условия сотрудничества, подробности у персонального менеджера.
Мы можем отправить товар любой транспортной компанией на ваш выбор, при этом доставка до пункта приёма товаров будет бесплатная. Оплата доставки выполняется в кассе выбранной транспортной компании отдельно при получении товара.
-
Описание
-
Детали
Датчик температуры (Контроллер) EL 961 POLETRON с одним датчиком
RF07A16
Описание
Предназначенные для вентилируемых холодильных установок средней и низкой температуры
Передняя панель: 77мм*36мм
Монтажное отверстие: 29мм*71мм
Вес | 0,25 кг |
---|---|
Габариты | 11 × 11 × 11 см |
cod. 9IS42060
GB
rel. 1/05
USER INTERFACE
The user has a display and four keys for
controlling status and programming of the
instrument.
KEYS AND MENUS
UP key
Scrolls through the menu items
Increases the values
Activates manual defrost
DOWN key
Scrolls through the menu items
Decreases the values
Programmable by parameter
fnc key
ESC function (exit)
fnc
Programmable by parameter
set key
Accesses the setpoint
set
Accesses the menus
Confirms the commands
Displaying the alarms (if present)
ID961
At start-up the instrument performs a
Lamp Test; for few seconds the display and
the leds blink, in order to verify their
integrity and correct operation. The instru-
ment has two main menus: the «Machine
Status» and «Programming» menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the «set» key («Machine Status»
menu) or by holding down the «set» key
for more than 5 seconds («Programming»
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
«set» key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions.
LED
Position
Related Function
Compressor or relay 1
Defrost
Alarm
Setpoint
ID 961
electronic controllers for refrigerating units
If you do not use the keyboard for over
15 seconds (time-out) or if you press the
«fnc» key once, the last value shown on
the display is confirmed and you return to
the previous screen mask.
MACHINE STATUS MENU
(See Machine Status Menu)
To access the «Machine Status» menu
Press and quickly release the «set» key.
If alarms are not present, the label «SEt»
appears. By using the «UP» and «DOWN»
keys you can scroll through the other fold-
ers in the menu:
-Pb1: probe 1 value folder;
-SEt: Setpoint setting folder.
Set Setting
Access the «Machine Status» menu by
pressing and quickly releasing the «set»
key. The label of the «Set» folder appears.
To display the Setpoint value press the
«set» key again.
f nc
The value appears on the display.
To change the Setpoint value, use the «UP»
and «DOWN» keys within 15 seconds.
set
If the parameter is LOC = y the Setpoint
cannot be changed.
Displaying Probes
By pressing the «set» key when the appro-
priate label appears, the value of the
probe associated to it is displayed.
PROGRAMMING MENU
(See Programming Menu)
To enter the «Programming» menu, press
the «set» key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter «PA1»), and (if the
password is correct) the label of the first
folder will follow.
To scroll through the other folders, use
the «UP» and «DOWN» keys.
If the password is wrong, the display will
show the PA1 label again.
To enter the folder, press «set». The label
of the first visible parameter appears. To
scroll through the other parameters, use
the «UP» and «DOWN» keys; to change the
parameter, press and release «set», then
Status
ON when the compressor is started up; blinking in case of delay,
protection or blocked enabling
ON when defrosting; blinking in case of manual
enabling
ON when the alarm is enabled; blinking when the alarm is silenced
On for setting Setpoint
set the desired value using the «UP» and
«DOWN» keys, and confirm with the «set»
key to move to the next parameter.
PLEASE NOTE: It is suggested to switch-
off and switch-on again the instrument
everytime it is changed the configuration
of the parameters: this prevents malfunc-
tioning on regulation and delay time
occuring.
PASSWORD
The password «PA1» allows access to pro-
gramming parameters. In the standard
configuration password is not present.
To enable (value≠0) and assign it the
desired value, access the «Programming»
menu, within the folder with the «diS»
label. If password is enabled, you will see
it at the entrance of the «Programming»
menu (see the «Programming Menu» sec-
tion).
MANUAL ACTIVATION OF THE
DEFROSTING CYCLE
To manually activate the defrosting cycle,
press the «UP» key for 5 seconds.
COPY CARD
The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters. The operation is performed as fol-
lows:
Format
This command allows copy card format-
ting, an operation recommended in case
of first use.
Warning: if the copy card has been pro-
grammed, using the «Fr» the data entered
are erased. This operation cannot be can-
celled.
Upload
This operation loads the programming
parameters from the instrument.
Download
This operation downloads to the instru-
ment the programming parameters.
The operations are performed accessing
the folder identified by the «FPr» label and
selecting, according to the case, «UL», «dL»
or «Fr» commands; the operation is con-
firmed by pressing the «set» key. If the
operation is successful an «y» is displayed,
on the contrary, if it fails a «n» will be dis-
played.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instru-
ment.
cod. 9IS42060
GB
rel. 1/05
USER INTERFACE
The user has a display and four keys for
controlling status and programming of the
instrument.
KEYS AND MENUS
UP key
Scrolls through the menu items
Increases the values
Activates manual defrost
DOWN key
Scrolls through the menu items
Decreases the values
Programmable by parameter
fnc key
ESC function (exit)
fnc
Programmable by parameter
set key
Accesses the setpoint
set
Accesses the menus
Confirms the commands
Displaying the alarms (if present)
ID961
At start-up the instrument performs a
Lamp Test; for few seconds the display and
the leds blink, in order to verify their
integrity and correct operation. The instru-
ment has two main menus: the «Machine
Status» and «Programming» menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the «set» key («Machine Status»
menu) or by holding down the «set» key
for more than 5 seconds («Programming»
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
«set» key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions.
LED
Position
Related Function
Compressor or relay 1
Defrost
Alarm
Setpoint
ID 961
electronic controllers for refrigerating units
If you do not use the keyboard for over
15 seconds (time-out) or if you press the
«fnc» key once, the last value shown on
the display is confirmed and you return to
the previous screen mask.
MACHINE STATUS MENU
(See Machine Status Menu)
To access the «Machine Status» menu
Press and quickly release the «set» key.
If alarms are not present, the label «SEt»
appears. By using the «UP» and «DOWN»
keys you can scroll through the other fold-
ers in the menu:
-Pb1: probe 1 value folder;
-SEt: Setpoint setting folder.
Set Setting
Access the «Machine Status» menu by
pressing and quickly releasing the «set»
key. The label of the «Set» folder appears.
To display the Setpoint value press the
«set» key again.
f nc
The value appears on the display.
To change the Setpoint value, use the «UP»
and «DOWN» keys within 15 seconds.
set
If the parameter is LOC = y the Setpoint
cannot be changed.
Displaying Probes
By pressing the «set» key when the appro-
priate label appears, the value of the
probe associated to it is displayed.
PROGRAMMING MENU
(See Programming Menu)
To enter the «Programming» menu, press
the «set» key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter «PA1»), and (if the
password is correct) the label of the first
folder will follow.
To scroll through the other folders, use
the «UP» and «DOWN» keys.
If the password is wrong, the display will
show the PA1 label again.
To enter the folder, press «set». The label
of the first visible parameter appears. To
scroll through the other parameters, use
the «UP» and «DOWN» keys; to change the
parameter, press and release «set», then
Status
ON when the compressor is started up; blinking in case of delay,
protection or blocked enabling
ON when defrosting; blinking in case of manual
enabling
ON when the alarm is enabled; blinking when the alarm is silenced
On for setting Setpoint
set the desired value using the «UP» and
«DOWN» keys, and confirm with the «set»
key to move to the next parameter.
PLEASE NOTE: It is suggested to switch-
off and switch-on again the instrument
everytime it is changed the configuration
of the parameters: this prevents malfunc-
tioning on regulation and delay time
occuring.
PASSWORD
The password «PA1» allows access to pro-
gramming parameters. In the standard
configuration password is not present.
To enable (value≠0) and assign it the
desired value, access the «Programming»
menu, within the folder with the «diS»
label. If password is enabled, you will see
it at the entrance of the «Programming»
menu (see the «Programming Menu» sec-
tion).
MANUAL ACTIVATION OF THE
DEFROSTING CYCLE
To manually activate the defrosting cycle,
press the «UP» key for 5 seconds.
COPY CARD
The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters. The operation is performed as fol-
lows:
Format
This command allows copy card format-
ting, an operation recommended in case
of first use.
Warning: if the copy card has been pro-
grammed, using the «Fr» the data entered
are erased. This operation cannot be can-
celled.
Upload
This operation loads the programming
parameters from the instrument.
Download
This operation downloads to the instru-
ment the programming parameters.
The operations are performed accessing
the folder identified by the «FPr» label and
selecting, according to the case, «UL», «dL»
or «Fr» commands; the operation is con-
firmed by pressing the «set» key. If the
operation is successful an «y» is displayed,
on the contrary, if it fails a «n» will be dis-
played.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instru-
ment.
Название
Инструкция
Комментарий
Eliwell IC 901 NTC-PTC
Eliwell IC901 NTC-PTC
Eliwell IC 901 — одноступенчатый контроллер температуры. IC901 – прибор с одной точкой срабатывания (работает как в режиме нагревания / охлаждения. Снабжен входным PTC датчиком (NTC может быть выбран параметром) и выходным реле для управления нагрузкой
Eliwell IC 902 NTC-PTC
Eliwell IC 902 NTC-PTC
IC 902 обладает одним функциональным выходом. Для контроля за состоянием и программированием прибора имеется дисплей и четыре кнопки управления
Eliwell IC 915 LX NTC-PTC
Eliwell IC 915 LX NTC-PTC
IC 915 LX – контроллер с двумя точками срабатывания, использующийся для контроля температуры. Cнабжен входом под датчики термостатов PTC/NTC
Eliwell ID 961
Eliwell ID 961
ID 961 — для холодильных установок средней температуры. Температурные датчики РТС / NTC (на выбор) и выходным реле для управления компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора
Eliwell ID 961 LX
Eliwell ID 961 LX
ID 961 LX — для холодильных установок средней температуры. Cнабжены входом под температурные датчики РТС (NTC может выбираться параметром) и выходным реле для управления компрессором. Продолжительность разморозки определяется временными интервалами остановки компрессора
Eliwell ID 970
Eliwell ID 970
ID 970 — для холодильных установок средней или низкой температуры. Датчики PTC / NTC, два выходных реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора
Eliwell ID 970 LX
Eliwell ID 970 LX
ID 970 LX — для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC и двумя выходными реле для управления компрессором и оттайкой. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора
Eliwell ID 971
Eliwell ID 971
ID 971 — контроллер для холодильных установок средней или низкой температуры. Температурные датчики PTC / NTC, два реле для управления компрессором и оттайкой
Eliwell ID 971 LX
Eliwell ID 971 LX
ID 971 LX — для холодильных систем два реле, два датчика, цифровой вход. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Работа вентилятора контроллером не программируется
Eliwell ID 974
Eliwell ID 974
ID 974 — для вентилируемых холодильных установок средней и низкой температуры. Датчики PTC / NTC. Три реле для управления компрессором, вентилятором и оттайкой. Оттайка задается по времени или по достижению температуры испарителя
Eliwell ID 974 LX
Eliwell ID 974 LX
ID 974 LX — для вентилируемых холодильных установок средней и низкой температуры, два входа для датчиков PTC (или NTC); три реле для управления процессором, вентилятором и оттайкой; цикл оттайки задается по времени или по достижению температуры испарителя
Eliwell ID 975 LX
Eliwell ID 975 LX
ID 975 LX — для вентилируемых холодильных установок средней и низкой температуры. Два датчика PTC / NTC. Четыре выходных реле предназначены для управления компрессором, вентилятором, разморозкой и авариями. Аварийное реле может быть запрограммировано для дополнительной нагрузки
Eliwell ID 985 LX
Eliwell ID 985 LX
ID 985 LX — для вентилируемых холодильных установок средней и низкой температуры. Три температурных датчика PTC / NTC. Четыре выходных реле для управления компрессором, вентилятором, разморозкой и авариями (причем аварийное реле может быть запрограммировано для дополнительной нагрузки)
Eliwell ID 961-971-974 Plus
Eliwell ID 961-971-974 Plus
ID PLUS 961 — 971 — 974 Электронные контроллеры статических и вентилируемых холодильных установок
Eliwell EW961-974(аналог ID974)
Eliwell EW 961 — 974
EW961-974 — для невентилируемых холодильных установок средней температуры. Температурные датчики PTC / NTC. Реле для управления холодильным компрессором. Продолжительность циклов разморозки определяется временными интервалами остановки компрессора
Eliwell ID 983-985 LX
EliwellI D 983-985S E CK, ID 983-985 E LX
ID 983-985 LX — для холодильных систем четыре программируемых реле, три датчика NTC / PTC, два цифровых входа. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Возможен вариант использования в режиме один компрессор два воздухоохладителя. Подключается к сети LINK.
Eliwell Energy XT
Eliwell Energy XT
Energy XT — серия программируемых контроллеров фирмы Eliwell, работающих в сферах кондиционирования и хладопроизводства. Energy XT, построен на базе 16-битного микропроцессора
Eliwell EWCM 900 S
Eliwell EWCM 900 S
EWCM 900/S — предназначен для управления машинным залом холодильной установки, в котором находятся компрессоры простого действия, многоступенчатые или различной мощности. Эти приборы также предназначены для управления вентиляторами конденсаторного агрегата. EWCM 900/S с 11 релейными выходами, может быть с входом под напряжением или же с температурным входом (зондом NTC).
Eliwell EWDR 902
Eliwell EWDR 902
EWDR 902 представляет собой серию микропроцессорных, полностью программируемых контроллеров с одной точкой срабатывания. Три различные версии разработаны для следующих применений: EWDR 902/T — для температуры; EWDR 902/R — для относительной влажности; EWDR 902/P — для давления
Eliwell EWDR 905
Eliwell EWDR 905
EWDR 905 представляет собой серию микропроцессорных, полностью программируемых контроллеров с двумя точками срабатывания или Нейтральной Зоной. Три различные версии разработаны для следующих применений: EWDR 905/T — для температуры; EWDR 905/R — для относительной влажности; EWDR 905/P — для давления
Eliwell EWCM 400
Eliwell EWCM 400
Серия EWCM 400 — контроллеры невысокой стоимости, специально разработанные для управления машинным залом холодильной системы. Они могу управлять максимум четырьмя простыми компрессорами и вентиляторами конденсатора установки
Eliwell EWDR 976 NTC
Eliwell EWDR 976 NTC
EWDR 976 NTC – контроллер, разработанный для управления разморозкой нескольких испарителей одной холодильной системы, управляемой только одним прибором серии DIGIFROST® (называемым Мастером) в котором должно иметься реле разморозки и датчик температуры испарителя (EWLC 74, EWPX 971, EWPX 185…).
Eliwell EWDR 975
Eliwell EWDR 975
EWDR 975 – контроллер, специально разработанный для холодильных установок. Он используется в сочетании с другим холодильным контроллером серии DIGIFROST® (за исключением EWPC 961/970 и ID 961/970) для систем с двойным контуром охлаждения, т.е. два компрессора и два испарителя
Eliwell Energy XT PRO
Eliwell Energy XT PRO
Energy XT PRO — серия свободно программируемых контроллеров фирмы Eliwell, которые легко подстраиваются под требования потребителя, работающих в сферах кондиционирования и хладопроизводства. Energy XT PRO, построен на базе 16-битного микропроцессора
Eliwell EWTR HR PR 920
Eliwell EWTR HR PR 920
EWTR 920 – это серия полностью программируемых приборов для применений с двумя рабочими точками; выхода управляются по принципу Вкл./Выкл. Существуют 3 различных версии контроллеров для Температуры EWTR 920, Относительной Влажности EWHR 920 и Давления EWPR 920.
Eliwell EWDR 984
Eliwell EWDR 984
EWDR 984 – для вентилируемых холодильных установок, 3 входа под температурные датчики NTC/PTC, 2 конфигурируемых цифровых входа. Три реле для управления компрессором, разморозкой и вентилятором. Дополнительный конфигурируемый выход 12В/ 20мА для аварий или т.п. Разморозка осуществляется остановкой компрессора на заданное время или достижения порогового значения температуры испарителя
Eliwell IWC 720-730
Eliwell IWC 720-730
IWC720-730 — для оборудования вентилируемых холодильных установок при нормальной или низкой температуре. Настраивается в зависимости от потребностей контроля и управления. Контролирует до трех входов для датчиков температуры. Предусматривает до шести выходных реле для управления компрессором, размораживания, вентиляторов испарителя, сигнализации, регулятора включения и выключения, а также для вспомогательного производства
Eliwell IWС 720-730 RUS
Eliwell IWС 720-730 RUS
Eliwell IWC 740-750
Eliwell IWC 740-750
IWС 740-750 — электронный регулятор для «вентилируемых» холодильных агрегатов
Eliwell EWDR 984 LX
Eliwell EWDR 984 LX
EWDR 984 LX — 3 входа под температурные датчики NTC / PTC, два конфигурируемых цифровых входа и три реле. Используется для холодильного оборудования с активным охлаждением (вентилятор испарителя). Звуковая сигнализация по температурных авариях. Монтаж на DIN-рейку
Eliwell EWRC 300 500 NT
Eliwell EWRC 300 500 NT
Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации. Приборы серии Coldface имеют 3 или 5 конфигурируемых реле в зависимости от модели, 2 конфигурируемых цифровых входа для реле двери и других целей. Имеются модели с часами и годовым календарем и с поддержанием функции записи событий в соответствии с протоколом HACCP.
Eliwell EWRC 300 500 5000 NT
Eliwell_EWRC_300_500_5000NT
Контроллеры серии Coldface EWRC 300/500 NT регулируют температуру в статических или вентилируемых холодильных камерах. Прибор применим для низкотемпературных и среднетемпературных камер включая установки с двойным испарителем и использованием датчика конденсации