CERBERUS® AlgoRex

Installation guidelines for fire detection

systems collective, interactive,

AnalogPLUS

Planning and realization

Specific national regulations are not integrated in this document

Fire & Security Products

Siemens Building Technologies Group

loading

Related Manuals for Siemens CERBERUS AlgoRex Series

Summary of Contents for Siemens CERBERUS AlgoRex Series

  • Page 1
    CERBERUS® AlgoRex Installation guidelines for fire detection systems collective, interactive, AnalogPLUS Planning and realization Specific national regulations are not integrated in this document Fire & Security Products Siemens Building Technologies Group…
  • Page 2
    Data and design subject to change without notice. / Supply subject to availability E Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche…
  • Page 3: Table Of Contents

    ……….Acceptance test and handing over the system to the customer ..12.2001 Fire & Security Products Siemens Building Technologies Group…

  • Page 4
    12.2001 Fire & Security Products Siemens Building Technologies Group…
  • Page 5
    This document is intended for planning engineers in all national sales organiza- tions. Local standard practices, regulations, languages etc that vary from this doc- ument must be taken into account and and documented by the national sales orga- nizations. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 6: Planning

    Fire detection system control unit Response indicator (Model …) Signalling, e.g. mimic panel, Special devices terminal etc. (Model …) (Model …) Fig. 2 Planning symbols (ISO/DIS 6790.2) Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 7
    Input / output module Electromagnetic compatibility Electromagnetic influence Fire detection system Fire detection system control unit Explosion hazard area Extra low voltage Voltage <50V Low voltage Voltage <1000V Shunt-Zener-Diode barrier Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 8: Basic Wiring Layout Of A Fire Detection System

    Fuse Door magnet line CT.. Door magnet line Line to remote transmission system for alarms and faults Extra-low voltage 16…30V Low voltage 110…240V Fig. 3 Basic fire detection system layout Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 9: Fire Detection System Line Network

    All equipment is largely protected against EMI. Nevertheless, the following precautions are necessary: Maintain the greatest possible distances from thyristor control cables, high voltage lines, lightning protection systems, transmitter cables etc. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 10
    Not recommended for new systems Upper level Ground floor È È È È È DC1192 È È È È È 1,5mm 240V~/10A CT.. CC/CI.. Basement level Fig. 4 Block diagram «collective» detection system Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 11
    È È È (HD) È È È (HD) (HD) (HD) (HD) Detection line (HD) false ceiling Fire detection system control unit Response indicator line (HB) raised floor Fig. 5 Collective wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 12
    DC1135 Ground floor DC1134 DC1135 DC1192 È È È È È È È È 1,5mm 240V~/10A CT.. CC/CI.. Basement level DC1134 DC1135  Fig. 6 Block diagram detection system AnalogPLUS Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 13
    È È È (HD) È È È (HD) (HD) (HD) (HD) (HD) Loop line (HD) false ceiling Fire detection system control unit Stub line (HB) raised floor  Fig. 7 AnalogPLUS wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 14
    Not recommended for new systems Upper level DC1154 Ground floor DC1192 È È È È È È È È DC1154 1,5mm 240V~/10A CT.. CC1140 Basement level DC1154 Fig. 8 Block diagram «interactive» detection system Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 15
    È È È (HD) È È È (HD) (HD) (HD) (HD) (HD) Loop line (HD) false ceiling Fire detection system control unit Stub line (HB) raised floor Fig. 9 Interactive wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 16
    Remote transmission equipment or danger management systems mounted separately from the control unit must be wired according to the corresponding manufacturer’s instructions. 1.3.14 Standards In general, the standard IEC 950 also applies (International Electrical Commission) Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 17: Installation

    If required, two different designation plates are available for the marking of detectors. They are attached under the detector base after installation. As component parts of a fire detection system, terminal boxes, distributor boxes, loop- ing-in boxes must be marked accordingly. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 18: Installing The Equipment

    The response indicator in the base must be easily visible from the alarm investigation route. Response indicator Fig. 11 Response indicator clearly visible See product packing sheets, for further details. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 19
    Í Í Í Í Í Í Í Í Í Í Í Fig. 13 Making the rubber membrane air-tight Important: Push the cable through the rubber membrane, or make holes with an awl. Do not cut holes or slits! Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 20
    Equipment for explosion-hazard areas must be installed and earthed according to docu- ment e1204, «Fire detection in explosion-hazard areas». Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…
  • Page 21: Wiring Check

    The installer is obliged to hand over to the commissioning engineer a correctly installed and tested supply network. Any deficiencies are normally eliminated and the work charged to the installer. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 22: Commissioning

    The acceptance procedure varies from country to country. It can be done by an accep- tance inspector or by the customer himself. The system is handed over to the customer who is given thorough training based on com- prehensive operating instructions. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001…

  • Page 23
    Fire & Security Products Back Siemens Building Technologies Group 12.2001…
  • Page 24
    Siemens Building Technologies AG Alte Landstrasse 411 CH 8708 Männedorf Tel. +41 1 − 922 61 11 +41 1 − 922 64 50 www.cerberus.ch Fire & Security Products Back Document no. e1453b Manual DS11 Siemens Building Technologies Group 12.2001 Edition 12.2001…

SIEMENS OOH740 Cerberus PRO Логотип автоматических пожарных извещателей Cerberus FIT

SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT

SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT producttt

информация о продукте

Автоматические пожарные извещатели CerberusTM PRO / CerberusTM FIT, модели OOH740 и OOHC740, устойчивы к
внешние и мешающие воздействия, такие как пыль, волокна, насекомые, влага, экстремальные температуры, электромагнитные помехи, агрессивные пары, вибрация, искусственные аэрозоли и нетипичные явления пожара. Они ударопрочные и обеспечивают защиту от сабо.tagе. Эти извещатели отличаются обработкой сигналов с помощью технологии ASA (Advanced Signal Analysis), поведением обнаружения в зависимости от времени и процесса, а также высокой степенью устойчивости к сбоям в силовой электронике. Они также имеют защищенную электронику и высококачественные компоненты, сложные датчики и электронный контроль, а также встроенный линейный сепаратор, который определяет местонахождение неисправной части на шине детектора встроенных линий питания. Модель OOH740 также может использоваться в линии коллективных извещателей или в линии обычных извещателей. Эти детекторы безвредны для окружающей среды, изготовлены из материалов многократного использования, а электронные детали и синтетические материалы легко отделяются друг от друга.

Инструкции по использованию продукта

Мультисенсорный пожарный извещатель OOH740 предназначен для раннего обнаружения пламенных возгораний твердых и жидких веществ, а также тлеющих пожаров. Его также можно использовать для раннего и надежного обнаружения пожара в среде с ложными явлениями. Извещатель может быть настроен программным обеспечением как мультисенсорный дымовой извещатель, извещатель дыма или тепловой извещатель. Выбираемое поведение обнаружения обеспечивается наборами параметров ASA для конкретных приложений. Этот извещатель можно использовать на адресной линии извещателей, в общей линии извещателей или в обычной линии извещателей.|
Извещатель пожара и угарного газа OOHC740 также является мультисенсорным пожарным извещателем с дополнительным датчиком угарного газа, который повышает чувствительность точечного извещателя и его устойчивость к ложным явлениям.
Он работает с использованием электрохимической ячейки CO и отправляет техническое сообщение, если температура или концентрация CO превышают / падают ниже заданных пределов. Тревога концентрации СО передается на независимый канал технической тревоги СО, и извещатель имеет независимую обработку сигнала СО для канала тревоги СО и сигнала СО для обнаружения пожара. Выбираемое извещателем поведение обнаружения канала тревоги CO не зависит от наборов параметров ASA для обнаружения пожара.
Технология AS™. Для автоматически адресуемой шины извещателей C-NET коллективная/традиционная (только OOH740)

  • Обработка сигналов с помощью технологии ASA.
  • Поведение обнаружения, управляемое событиями
  • Оценка критериев тепла, тепла для OOH740 и газа для OOHC740
  • Быстрое реагирование на все пожары, в результате которых образуется угарный газ (CO) для OOHC740
  • Отдельное обнаружение токсичного CO для OOHC740
  • Высокоразвитый иммунитет к обманчивым явлениям
  • Готовность к будущим требованиям благодаря программируемости
  • Адрес выдается автоматически при вводе в эксплуатацию
  • Поддерживает функциональное тестирование без помех с помощью технологии DFTtechnology™ (испытание без помех) (OOH740)

Объекты

Дизайн

Устойчив к воздействию окружающей среды и мешающих воздействий, таких как пыль, волокна, насекомые, влага, экстремальные температуры, электромагнитные помехи, агрессивные пары, вибрация, искусственные аэрозоли и нетипичные явления пожара

Особенности
  • Ударопрочный, защита от сабоtage
  • Обработка сигналов с помощью технологии AS (Advanced Signal Analysis)
  • Поведение обнаружения, зависящее от времени и процесса
  • Высокая степень устойчивости к сбоям в силовой электронике
  • Защищенная электроника, качественные компоненты
  • Сложные датчики и электронный мониторинг
  • Встроенный разделитель линий, который находит неисправную деталь на шине извещателей контрольной панели и изолирует между двумя извещателями
  • Поддерживает автоматическое тестирование детектора с помощью DFTtechnology™ (OOH740)
  • Встроенный индикатор тревоги (AI), видимость 360°
  • К каждому извещателю можно подключить до двух внешних индикаторов тревоги.
  • Адрес выдается автоматически при вводе в эксплуатацию
  • Одно и то же основание извещателя можно использовать для всех типов извещателей, для накладных и скрытых линий питания.
  • Только OOH740: Может также использоваться на линии коллективных извещателей или на обычной линии извещателей.

Экологичные

  • Экологически чистая обработка
  • Многоразовые материалы
  • Электронные детали и синтетические материалы легко отделяются друг от друга.

Используйте

Мультисенсорный пожарный извещатель OOH740, нейронный ASA
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 1 Мультисенсорный пожарный извещатель, состоящий из:

  • Точечный детектор
  • Пылезащитный колпачок детектора для защиты точечного детектора на этапе строительства

Функции:

  • Работает по принципу рассеянного света с двумя датчиками, оптическим рассеянием вперед и назад
  • Оптоэлектронная измерительная камера, которая блокирует нежелательный посторонний свет, но обеспечивает превосходное обнаружение как светлых, так и темных частиц дыма.
  • Два дополнительных тепловых датчика повышают устойчивость точечного извещателя к ложным явлениям.
  • Программное обеспечение может быть настроено как мультисенсорный дымовой извещатель, дымовой извещатель или тепловой извещатель.
  • Выбираемое поведение обнаружения благодаря наборам параметров ASA для конкретных приложений

Используйте:

  • Для раннего обнаружения возгораний твердых и жидких веществ, а также тлеющих пожаров.
  • Для раннего и надежного обнаружения пожара в среде с ложными явлениями
  • Может использоваться на адресной линии извещателей, общей линии извещателей или обычной линии извещателей.
Извещатель пожара и угарного газа OOHC740, нейронный ASA
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 2 Мультисенсорный пожарный извещатель, состоящий из:

  • Точечный детектор
  • Пылезащитный колпачок детектора для защиты точечного детектора на этапе строительства

Функции:

  • Работает по принципу рассеянного света с двумя датчиками, оптическим рассеянием вперед и назад
  • Оптоэлектронная измерительная камера, которая блокирует нежелательный посторонний свет, но обеспечивает превосходное обнаружение как светлых, так и темных частиц дыма.
  • Два дополнительных тепловых датчика и дополнительный датчик CO повышают чувствительность точечного извещателя и его устойчивость к ложным явлениям.
  • Техническое сообщение, контроль окружающей среды: Техническое сообщение, если температура или концентрация CO превышают/ниже заданных пределов
  • Функции с использованием электрохимической ячейки CO
  • Тревога концентрации CO передается на независимый технический канал тревоги CO.
  • Независимая обработка сигнала CO для канала тревоги CO и сигнала CO для обнаружения пожара
  • Выбираемое поведение обнаружения канала тревоги CO, независимо от набора параметров ASA для обнаружения пожара
  • Выбираемое поведение обнаружения благодаря наборам параметров ASA для конкретных приложений

Используйте:

  • Для раннего обнаружения тлеющих пожаров, которые выделяют CO (например, возгорание матрацев в домах).
  • Помещения с повышенным воздействием CO, например, котельные, установки для сжигания, ферментационные заводы, гаражи, автомобильные мастерские, стойла для животных, химические лаборатории или производственные площадки.
  • Для надежного обнаружения пожара в среде с ложными явлениями
  • Может использоваться адресовано
База извещателя DB721
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 3 Функции:

  • Универсальная база для всех точечных детекторов серии Cerberus™ PRO FD720

Используйте:

  • Для утопленных линий подачи
  • Для накладных линий электроснабжения с кабелями до макс. Ø 8 мм

База извещателя DB721 имеет шлейфовый контакт. При использовании DB721 линия извещателей также не прерывается, если в основании извещателя не установлен точечный извещатель.

База извещателя DB721D
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 3 Функции:

  • Коллективный режим
    • Универсальная база для точечного извещателя OOH740 в коллективном режиме (с БС 5839-1)
  • Адресный режим
    • Универсальная база для точечного извещателя OOH740 серии Cerberus™ PRO FD720
    • При использовании в адресном режиме диод должен быть удален

Используйте:

  • Для утопленных линий подачи
  • Для накладных линий электроснабжения с кабелями до макс. Ø 8 мм
    База извещателя DB721D имеет шлейфовый контакт. При использовании DB721D линия извещателей также не прерывается, если в основании извещателя не установлен точечный извещатель.
База извещателя DB722
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 4 Функции:

  • Универсальное основание с уплотнением основания для точечных извещателей OH720 и OP720 серии Cerberus™ PRO FD720

Используйте:

  • Для утопленных линий подачи
  • Для накладных линий электроснабжения с кабелями до макс. Ø 8 мм

База извещателя DB722 имеет шлейфовый контакт. При использовании DB722 линия извещателей также не прерывается, если в основании извещателя не установлен точечный извещатель.

База извещателя DB110 (набор параметров 1)
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 3 Функции:

  • Универсальная база для всех точечных извещателей серий 110 и OOH740
  • Выбирает набор параметров 1 в точечном детекторе

Используйте:

  • Для утопленных линий подачи
  • Для накладных линий электроснабжения с кабелями до макс. Ø 8 мм
Основание оповещателя DBS720
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 5 Функции:

  • Адресная база сирены для акустической сигнализации
  • Совместимость со всеми точечными извещателями серии Cerberus™ PRO FD720 Дополнительную информацию о базе звукового оповещателя DBS720 можно найти в документе A6V10218037.

Предполагаемое использование

Автоматические пожарные извещатели OOH740 и OOHC740 могут использоваться только на линии извещателей C-NET в системе обнаружения пожара FS720 или FC360.
Автоматический пожарный извещатель OOH740 также может использоваться на линии коллективных извещателей или на обычной линии извещателей.

Введите текстview

Тип Обозначение Номер заказа Вес (кг]
ОХ740 Мультисенсорный пожарный извещатель, ASA С54320-Ф7-А3 0.124
OOHC740 Детектор пожара и угарного газа, ASA С54320-Ф8-А3 0.128
DB721 Основание извещателя с петлевым контактом С54319-Ф11-А1 0.052
ДБ721Д Основание извещателя с петлевым контактом С54319-Ф15-А1 0.054
DB722 База детектора С54319-Ф19-А1 0.052
DB110 База извещателей (коллективная) С54372-Ф5-А1 0.052
DBS720 Звуковая база С54319-Ф5-А1 0.090
Аксессуары
BA720 Базовое крепление С54319-Ф20-А1 0.051
BA721 Базовое крепление мокрое С54319-Ф29-А1 0.272
ФДБЗ291 Табличка с обозначением A5Q00002621 0.002
ДБЗ1193А Табличка с обозначением БПЗ: 4864330001 0.076
RS720 Уплотнение основания детектора С54319-Ф8-А1 0.012
LP720 Блокирующее устройство извещателя С54319-Ф9-А1 0.001
ФДБХ291 Блок обогрева детектора A5Q00004439 0.015
ДБЗ1194 Защитная клетка БПЗ: 4677110001 0.138
ДБЗ1190-АА Микроклемма 0.28…0.5 мм² БПЗ: 4677080001 0.001
ДБЗ1190-АБ Соединительные клеммы 0.5…2.5 мм² БПЗ: 4942340001 0.001
ПСР720-1 Резистор набора параметров 33k С54319-Ф16-А1 0.001
ПСР720-2 Резистор набора параметров 68k С54319-Ф17-А1 0.001

Аксессуары

Базовое крепление BA720
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 6 Функции:

  • Для прокладки накладных каналов (макс. 20 мм) и кабельных каналов (макс. 25 x 15 мм)
  • Быстрое крепление основания извещателя: основание извещателя защелкивается в креплении основания BA720.
Базовое приспособление мокрое BA721
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 7
  • Влажное крепление основания с дополнительным встроенным резиновым уплотнением для монтажа во влажной или влажной среде.
  • Для достижения более высокой степени защиты
  • Для монтажа во влажной или влажной среде
  • Требуется при использовании блока обогрева детектора FDBH291
  • Требуется при использовании защитной клетки DBZ1194
  • Устанавливается между основанием извещателя и потолком
  • Быстрое крепление основания извещателя: основание извещателя просто защелкивается во влажном креплении основания BA721.
Защитная клетка DBZ1194
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 8
  • Для защиты точечного детектора от повреждений
  • Может быть установлен только в сочетании с мокрым основанием BA721.
Нагреватель извещателя FDBH291
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 9
  • Для извещателей рабочей точки в критических условиях окружающей среды, в условиях гололеда или при опасности конденсации влаги. БывшийampСферы применения: Холодильные камеры, чердаки, погрузочныеampс, сырные погреба
  • Оптимальная работа гарантируется только в сочетании с мокрым основанием BA721.
  • Температура точечного извещателя повышается примерно на 2 °C по сравнению с рабочей температурой, что позволяет избежать конденсации влаги на извещателе.
  • Быстрый монтаж: нагревательный элемент извещателя защелкивается в основании извещателя.
Паспортная табличка FDBZ291
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 10
  • Для маркировки с адресом местонахождения
  • Может использоваться только без уплотнения основания извещателя FDBZ295
Паспортная табличка DBZ1193A
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 12
  • Для маркировки с адресом местонахождения
  • Может использоваться только с мокрым основанием BA721.
Уплотнение базы извещателя RS720
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 13
  • Для достижения более высокой степени защиты IP
  • Устанавливается между основанием извещателя и потолком
Резистор набора параметров 33к PSR720-1
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 16 Функции:

  • Готовый резистор с плоскими штекерами для использования в DB110 и DB721D. Вводит OOH740 в набор параметров 1.
Резистор набора параметров 68к PSR720-2
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 17 Функции:

  • Готовый резистор с плоскими штекерами для использования в DB110 и DB721D. Вводит OOH740 в набор параметров 2.
Микротерминал DBZ1190-AA и соединительный терминал DBZ1190-AB
SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 18
  • Микротерминал DBZ1190-AA
    • Сечение кабеля до макс. 0.5 мм²
  • Клемма подключения DBZ1190-AB
    • Сечение кабеля до макс. 2.5 мм²
    • Для подключения двух внешних индикаторов тревоги или экрана кабеля

Документация по продукту

ID документа Название
008115 Установка Детектор обогрева FDBH291
A6V10200373 Установка Основание извещателя с петлевым контактом DB721, DB722, основание извещателя DB720, основание оповещателя DBS720, уплотнение основания извещателя RS720, устройство блокировки извещателя LP720, крепление к основанию BA720
A6V10203222 Технический паспорт Испытательное оборудование и аксессуары FDUL221, DX791, RE6, RE7T, RE8ST, RE8STCO, FDUM29x, LE3, StabexHF
A6V10218037 Техническое руководство Основание оповещателя DBS720
A6V10229261 Список совместимости (для линейки продуктов Cerberus™ PRO)
A6V10305793 Техническое руководство Автоматические пожарные извещатели OOH740, OOHC740
A6V10393192 Список совместимости (для линейки продуктов Cerberus™ FIT)
A6V10406006 Монтаж Крепление к основанию, мокрое BA721, табличка с обозначением извещателя DBZ1193A, защитный кожух DBZ1194, защитный кожух EMC FDBZ294
A6V10882301 Список совместимости (для линейки продуктов FC360)

Заметки

Установка

Простой монтаж

  • Универсальная база извещателя
    • Две точки отвода для бокового ввода кабеля на поверхность.
      Макс. диаметр кабеля: 8 мм.
    • Сверхбольшое отверстие для одиночного скрытого ввода кабеля.
  • Сверхдлинные монтажные прорези позволяют повторно использовать существующие отверстия от других систем.
  • Винтовые клеммы для проводников до макс. 1.6 мм²
  • Место для вспомогательных клемм:
    • 2 микротерминала DBZ1190-AA и
    • 2 соединительных клеммы DBZ1190-AB

Извещатель можно легко ввинтить в основание вручную или с помощью переходника извещателя DX791 и соответствующего адаптера FDUD491.
Внутренний индикатор тревоги расположен по центру извещателя, что делает ненужным выравнивание точечного извещателя.SIEMENS OOH740 Cerberus PRO Автоматические пожарные извещатели Cerberus FIT 19

1 База детектора 5 Монтажные щели
2 Вспомогательные клеммы DBZ1190‑AA, DBZ1190‑AB 6 Точечный детектор
3 Винтовые клеммы для линии извещателей и внешнего индикатора тревоги 7 Индикатор внутренней тревоги
4 Отверстие для ввода кабеля

Распоряжение

Устройство считается электронным устройством, подлежащим утилизации в соответствии с Европейской директивой, и его нельзя утилизировать вместе с бытовыми отходами.

  • Используйте только назначенные каналы для утилизации устройств.
  • Соблюдайте все местные и действующие законы и постановления.
  • Утилизируйте разряженные батареи в специально отведенных пунктах сбора.

Технические данные

ОХ740 OOHC740
Рабочий объемtagе (модулированный) 12…33 В пост. тока 12…33 В пост. тока
Рабочий ток (в состоянии покоя) ~170…250 мкА ~300…380 мкА
Макс. количество внешних индикаторов тревоги, которые можно подключить 2 2
Рабочая Температура -25… + 55 ° С -10… + 50 ° С
Температура хранения -30… + 70 ° С -20… + 55 ° С
Влажность воздуха (допускается кратковременная конденсация влаги) ≤95 % отн. ≤95 % отн.
Протокол связи C-NET, коллективный или обычный С-НЕТ
Цвет ~RAL 9010 чисто-белый ~RAL 9010 чисто-белый
Вес 0.100 кг 0.100 кг
Категория защиты (IEC 60529) IP40 IP40
Категория защиты (IEC 60529) с уплотнением основания извещателя RS720/BA721 IP44 IP44
Стандартный ЕН 54‑5, ЕН 54‑7, ЕН 54‑17, ЕН 54-5, ЕН 54-7, ЕН 54-17,
EN 54-29 EN 54-29
Соответствует требованиям
согласно EN 54-31
Сертификаты
VdS G211070 G211047
ЛКПБ 126бв/04 126бв/08
FM 3051081
DNV GL (морской) MEDB00003UK
Допустимая скорость ветра Максимум. 5 м/с Максимум. 5 м/с
Совместимость с системой C-NET ФК720, ФК360
Коллективная совместимость системы ФК10/ФК120

Габаритные чертежи

Выдан
Сименс Швейцария Лтд.
Умная инфраструктура
Глобальный штаб
Тейлерштрассе 1а
Поезд CH-6300
+41 58 724 2424 XNUMX(XNUMX)XNUMX-XNUMX-XNUMX
www.siemens.com/buildingtechnologies

Документы / Ресурсы

Рекомендации

  • www.siemens.com
    Строительные технологии — Товары и услуги — Global
  • Page 1
    FC721 Fire control panel Technical Manual Building Technologies A6V10211100_f_en_— 2015-12-15 Control Products and Systems…
  • Page 2
    Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2015-12-15 Document ID: A6V10211100_f_en_— © Siemens Switzerland Ltd, 2009 2 | 118 Building Technologies A6V10211100_f_en_— Fire Safety 2015-12-15…
  • Page 3: Table Of Contents

    Table of contents About this document …………….7 Applicable documents …………….. 9 Download center ………………9 Technical terms and abbreviations ………….. 9 Revision history ………………10 How displays are represented in the document ……….11 Safety ………………..12 Safety instructions ………………12 Safety regulations for the method of operation ………..14 Standards and directives complied with…………16 Release Notes ……………….16 Cyber security disclaimer …………….16…

  • Page 4
    C-NET detector line ………………. 57 6.5.1 Connectable C-NET devices …………58 6.5.2 C-NET topology and connection ……….62 6.5.3 Wiring principle behind C-NET devices ……..64 Structure and function…………….66 Indication and operating elements………….. 66 Extra indication and operating devices …………68 7.2.1 Mimic display driver FT2001 …………
  • Page 5
    10.8 Detailed commissioning steps …………..95 10.8.1 Preparing ‘Station’ for commissioning ……….95 10.8.2 Preparing ‘Station’ for commissioning –without BDV installation …96 10.8.3 Auto-configuring ‘Station’………….96 10.8.4 Auto-configuring the detector line ……….97 10.8.5 Loading automatically created configuration to the PC….98 10.8.6 Adapting configuration …………..98 10.8.7 Switch off ………………99 10.8.8…
  • Page 6
    6 | 118 Building Technologies A6V10211100_f_en_— Fire Safety 2015-12-15…
  • Page 7: About This Document

    About this document Applicable documents 1 About this document Goal and purpose The information provided in this technical manual is a summary of the key procedures and functions required to assemble, install, commission, and service the FC721 fire control panel system. The aim of this technical manual is to provide experienced and qualified personnel with a quick guide to the necessary processes.

  • Page 8
    About this document Applicable documents Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE — = multilingual or international A6V10215123_a_en_— A6V10315123_a_—_— Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD). Conventions for text marking Markups Special markups are shown in this document as follows:…
  • Page 9: Applicable Documents

    1.2 Download center You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address: http://siemens.com/bt/download Enter the document ID in the ‘Find by keyword’ input box. κ You will also find information about search variants and links to mobile applications (apps) for various systems on the home page.

  • Page 10: Revision History

    About this document Revision history 1.4 Revision history The reference document’s modification index applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, have the modification index ‘d’ instead of ‘a’ if the reference document already has this modification index.

  • Page 11: How Displays Are Represented In The Document

    About this document How displays are represented in the document Version Edition date Brief description 2010-07 Edition for MP3.0 XS ● Amendments to MP3.0 ● Amendments to PMI & mainboard FCM2027 ● Various minor changes ● Naming amended 2009-05 Technical manual FC721 1.5 How displays are represented in the document With very few exceptions, the fire control panels and fire terminals are displayed in this document in tables.

  • Page 12: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ●…

  • Page 13
    Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger…
  • Page 14: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,…

  • Page 15
    Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 16: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.

  • Page 17: System Overview

    System overview Cyber security disclaimer 3 System overview Cerberus PRO fire control panels FC721 are operated as standalone control panels. FC721 fire control panels cannot be networked with one another or with other FS720 fire control panels. Cerberus PRO fire control panels FC721 support operation of the CNET detector line as a loop or stub.

  • Page 18: Station Types

    System overview Station types 3.1 Station types Overview of the fire control panel FC721 and options FC721 in housing (Eco) FC721-ZZ FC721-YZ FC721-HZ Standard operating unit Operating unit with integrated LED Operating unit with integrated indicator (24 indicator groups, each EVAC-NL operating unit according with a red/green and yellow LED) to the requirements for the…

  • Page 19: Planning

    Planning FC721 system limits and options 4 Planning 4.1 FC721 system limits and options FC721 System limits Detector line Max. C-NET addresses 126 *(1 loop or 2 stubs) Number of loops or stubs 1 loop or 2 stubs Number of devices per loop Max.

  • Page 20: Functions

    Planning Functions 4.2 Functions This chapter describes the most important functions that can be supported by the fire detection system. Decision on alarm The danger signals of the detectors are evaluated by the zone. The decision on alarm is made at zone level. Decision on alarm can be configured as follows for each zone: ●…

  • Page 21: Defining Controls

    Planning Functions 4.2.1 Defining controls Connections for controls are available on the following components / control panels: ● Fire control panels FC721 ● Input module FDCI221 ● Input module FDCI222 ● Input/output module FDCIO222 ● Input/output module FDCIO222 ● Input/output module FDCIO223 ●…

  • Page 22: Mounting

    Mounting Mounting and assembling a station 5 Mounting 5.1 Mounting and assembling a station Before mounting and installation, check all the fire detection installation components visually for damage caused by improper transport. Cerberus Figure 3: Unpacking and checking ● Components with clear signs of damage must not be used in the station or operated as fire detection installation components.

  • Page 23: Mounting Instructions

    Mounting Mounting instructions 5.2 Mounting instructions The station’s product insert contains an mounting model to assist with mounting. The dimensions needed and details of the mounting points are shown on the mounting model. Details on mounting and installation can be found in the reference documents.

  • Page 24: Surface-Mounted Assembly

    Mounting Mounting instructions 5.2.1 Surface-mounted assembly ● Any surface irregularities can be compensated with washers or wooden wedges. ● The rear panel is attached to the wall using screws with a diameter of 6 mm. ● The supplied edge protection strip must be placed around rectangular breakout openings.

  • Page 25
    Mounting Mounting instructions Cerberus Figure 4: Mounting of the FC721 Recommended display height approx. 1.6 to 1.7 m Width of the FC721: 430 mm Distance from door of at least one door leaf width Height of the FC721: ● 398 mm ●…
  • Page 26
    Mounting Mounting instructions Assembling the FC721 and additional housing (option) The FC721 is supplied inside the Eco housing. An additional empty housing (Standard) can be assembled and connected for a larger battery capacity. This has space for an additional 150 W power supply and larger batteries.
  • Page 27
    Mounting Mounting instructions Mounting steps 1. Break out the required openings for feeding the cables at the bottom of the FC721 and the mounting holes for assembling the housing. 2. Break out the required openings for feeding cables and the mounting holes for housing assembly at the top on the rear panel of the extra housing.
  • Page 28: Mounting And Wiring The Operating Unit

    Mounting Mounting instructions 5.2.2 Mounting and wiring the operating unit From IP5, the PMI & mainboard FCM2027 is used. You will find detailed information in document A6V10210368. Figure 6: View of an FC721 with open operating unit Connection (X3) for the ribbon cable on the periphery board Hinge Cable routing to the optional components Cable ties for fixing the cables…

  • Page 29
    Mounting Mounting instructions Figure 7: Detail view of the hinge of the operating unit Cut-out section on the rear panel for the hinge of the operating unit Hinge of the operating unit Screw for securing the hinge Mounting steps 1. From the rear side, hang the operating unit by inserting the hinges (2) into the openings in the rear panel of the housing (1).
  • Page 30
    Mounting Mounting instructions Figure 8: Inserting the inscription strips into the operating unit Inscription LEDs Inscription standard keys 2 Inscription standard keys 1 Inscription station type 30 | 118 Building Technologies A6V10211100_f_en_— Fire Safety 2015-12-15…
  • Page 31: Led Module

    Mounting LED module 5.3 LED module The LED module installed in the FC721-YZ contains 24 groups, each with one red/green and one yellow LED. Any events can be assigned to the LEDs. Each LED may be configured as a static or flashing indicator. Normally the LED indicator is used as a zone indicator.

  • Page 32: Evac-Nl Operating Unit Fto2007-N1 [Nl] (Fc721-Hz Only)

    Mounting EVAC-NL operating unit FTO2007-N1 [NL] (FC721-HZ only) 5.4 EVAC-NL operating unit FTO2007-N1 [NL] (FC721- HZ only) The EVAC-NL operating unit [NL] is an evacuation control unit for the functions required in the Netherlands. It enables the operation of a maximum number of 10 evacuation zones.

  • Page 33: Options

    Mounting Options 5.5 Options 5.5.1 Fitting extra relay Figure 9: Mounting of two relays Fixing screws for the DIN rail Relays 1 + 2 DIN rail End clamp for the relays Mounting steps 1. Insert the relays (3) on the DIN rail (2) and press them down until they latch. 2.

  • Page 34: Installing An Rs232/Rs485 Module

    Mounting Options 5.5.2 Installing an RS232/RS485 module This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. No more than one single interface module (RS232 or RS485) can be installed in an FC721.

  • Page 35
    Mounting Options Figure 11: Installation of the serial modules RS232 module in slot X14 RS485 module in slot X19 2x fixing screw X14 Slot for RS232 module on the operating unit Mounting links on support plate X19 Slot for RS485 module on the operating unit Nut for screwed cable gland Connection terminal on RS232 module Screwed cable gland…
  • Page 36
    Mounting Options Mounting steps 1. Mount the cable gland (5) with the nut (4) on the flange between the fastening tabs (3). 2. Plug the serial module (1 or 6) into the corresponding connector (X14 or X19). 3. Secure the serial module to the fastening tabs (4) using the two screws (2). 4.
  • Page 37
    Mounting Options 5.5.2.2 X2 on RS485 module Designation Description RS485_A Line A RS485_B Line B Not connected Not connected Admissible cable cross-section: 0.2…1.5 mm² RS485_A RS485_B T1 First participant Tn Last participant *) Stub lines must not exceed 20 m! ●…
  • Page 38: Install Shield Connection Terminal Blocks

    Mounting Options 5.5.3 Install shield connection terminal blocks Figure 12: Mounting of the shield connection terminal blocks Shield connection terminal block Philips screws M 3/6 Camp bar Mounting steps 1. Secure the clamp bar (2) above the rectangular cable breakout opening on the right with two screws (3) 2.

  • Page 39: Cable Kit (Communication)

    Mounting Options 5.5.4 Cable kit (communication) The cable kit (communication) FCA2014-A1 is used as an intermediate piece for wiring the external lines to the modules on the operating unit. The connecting cables supplied are fully assembled and have a length of 1110 mm. The cable kit is mounted in the top right of the housing instead of the shield connection terminal blocks.

  • Page 40: Insert License Key

    Mounting Options 5.5.5 Insert license key The license key (S1) FCA2033-A1 is inserted in the corresponding holder on the rear of the operating unit. Figure 14: Using the license key on the operating unit with PMI & mainboard FCM2027 Figure 15: Using the license key on the operating unit with PMI & mainboard FCM2004 Holder for the license key License keys Inserting…

  • Page 41: 19″ Mounting Kit

    Mounting Options 5.5.6 19″ mounting kit The 19″ mounting kit FHA2016-A1 serves as a retainer for installing a station into a 19″ rack or into a 19″ cabinet. To fix a station, the two retainers enclosed with the kit must be mounted. The mounting instructions described below apply to all housing types.

  • Page 42: Installation

    Installation Options 6 Installation The following installation instructions refer to the specifications of the EN 54 standard and the manufacturer’s recommendations. The installation may only be undertaken by an electrician. Detailed instructions can be found in the system documentation. ● Use a suitable cable, e.g., NYM 3 x 1.5 mm (max.

  • Page 43: Protection Elements

    Installation Protection elements 6.1 Protection elements Electro-magnetic influence and over-voltages may lead to faults in the fire detection installation. Protection elements minimize these faults. All stations are equipped with fine protection and EMC filters in the factory. This applies to the components listed below: ●…

  • Page 44: Operation With Battery Backup

    Installation Supply concept 6.2.1 Operation with battery backup The ↑ stations are normally operated with a power supply unit and batteries. The power supply unit feeds the hardware with galvanically isolated system voltage, simultaneously charging the batteries. Together with the batteries, the power supply unit assumes the function of an uninterruptible power supply unit.

  • Page 45: Position Of Printed Circuit Boards / Components

    Installation Position of printed circuit boards / components 6.3 Position of printed circuit boards / components Position of components in the FC721 Batteries Power supply 70 W Mains connection terminals (L1,N,PE) Periphery board (1-loop) Type plate (enclosed, must be attached to the outside of the control panel housing at a clearly visible point) Options (extract)

  • Page 46: Power Supply — Mains Voltage Connection

    Installation Power supply — mains voltage connection 6.4 Power supply — mains voltage connection When supplied from the factory, the power supply’s internal cabling is already connected. Power supplies available ● Standard: DC 24 V / 2.5 A, power 70 W, max. battery capacity which can be connected 17 Ah (in the FC721, no more than 7 Ah due to a lack of space) ●…

  • Page 47
    Installation Power supply — mains voltage connection Connecting mains voltage WARNING High voltage! Danger to life! Risk of electric shock ● Before connecting the mains voltage ensure that it is not energized and is locked to prevent it being activated. 1.
  • Page 48
    Installation Power supply — mains voltage connection Additional empty housing If a power supply (150 W) is needed, this must be accommodated in an additional empty housing (Standard) together with the batteries. Figure 20: Housing (Standard) for additional batteries 48 | 118 Building Technologies A6V10211100_f_en_— Fire Safety…
  • Page 49: Emergency Power Supply

    Installation Power supply — mains voltage connection 6.4.1 Emergency power supply Should the AC mains voltage fail, the emergency power supply will be provided by the connected batteries with no interruptions. The emergency power bridging time depends on the control panel’s quiescent and alarm current and the battery capacity used.

  • Page 50: Batteries

    Installation Power supply — mains voltage connection 6.4.2 Batteries Calculating the battery capacity Determine the battery capacity with the following formula: = (I ) * k Batt R total A total Battery capacity in [Ah] Batt Sum of operating current of all consumers in quiescent condition [A] R total Sum of operating current of all consumers in alarm condition [A] A total…

  • Page 51
    Installation Power supply — mains voltage connection Determining the battery type Determine the battery type on the basis of the calculated battery capacity (see table). Designation Type Capacitance Order number Battery (12 V, 7 Ah, VDS) FA2003-A1 7 Ah A5Q00019353 Battery (12 V, 12 Ah, VDS) FA2004-A1 12 Ah…
  • Page 52: Periphery Board

    Installation Power supply — mains voltage connection 6.4.3 Periphery board Position of connection terminals on periphery board (1-loop) of FC721 fire control panel. F601 F501 F400 F401 X400 Figure 22: View of periphery board (1-loop) Connection of power unit Ribbon cable plug connection to PMI & mainboard (operating unit on pivot frame) Monitored outputs for acoustic signal transmitter, alarm and fault messages…

  • Page 53: Alarm Relay

    Installation Power supply — mains voltage connection 6.4.3.1 Relay for fault and alarm (RT activation) Allocation of connection terminals on periphery board (1-loop) of FC721. A cable cross-section of 0.2 to 1.5 mm can be connected to the terminals. Designation Description FAU_NC Break contact fault (normally closed)

  • Page 54
    Installation Power supply — mains voltage connection 6.4.3.2 Monitored outputs for alarm and fault (FT activation) Connection terminals on the periphery board (1-loop) of FC721. A cable cross- section of 0.2 to 1.5 mm can be connected to the terminals. Designation Description FAU_OUT…
  • Page 55
    Installation Power supply — mains voltage connection 6.4.3.3 Connection of monitored acoustic signal transmitters Connection terminals on the periphery board (1-loop) of FC721. A cable cross- section of 0.2 to 1.5 mm can be connected to the terminals. Designation Description FAU_OUT Output fault VSYS_O…
  • Page 56
    Installation Power supply — mains voltage connection 6.4.3.4 Configurable inputs/outputs Connection terminals on periphery board of FC721 station. A cable cross-section of 0.2 to 1.5 mm can be connected to the terminals. Designation Description GND_01 (–) supply output 1 DC 20 V – DC 30 V/1 A VSYS_01 (+) supply output 1 I/O4…
  • Page 57: C-Net Detector Line

    Installation C-NET detector line 6.5 C-NET detector line Up to 126 devices, such as automatic fire detectors, manual call points, transponders, and other C-NET components, can be connected to the C-NET detector line. The connection of the C-NET detector line is on the periphery board. Most line devices, such as fire detectors, are supplied with the operating voltage required directly by the C-NET.

  • Page 58: Connectable C-Net Devices

    Installation C-NET detector line 6.5.1 Connectable C-NET devices The table below contains a list of all devices which can be connected to the C-NET detector line. It also highlights which devices feature an alarm indicator (AI) and to which an external alarm indicator (Ext. AI) or a sounder base (DBS720) can be connected.

  • Page 59
    Installation C-NET detector line Device type Type Description ↑ AI Ext. AI DBS 720 Manual call point FDM221 Direct activation for indoor applications – – Indirect activation (large housing) – FDM223 FDM223H FDM223-Ex Indirect activation (large housing) for – areas at risk of explosion FDM224 Indirect activation (large housing) –…
  • Page 60
    Installation C-NET detector line Device type Type Description ↑ AI Ext. AI DBS 720 Line separator FDCL221 – – Line separator for the correct connection of several stub lines at one point on a loop FDCL221-M Multi line separator module for the –…
  • Page 61
    Installation C-NET detector line Device type Type Description ↑ AI Ext. AI DBS 720 FDOOT271 – Neural radio fire Optical-thermal fire detector with radio detector (SWING) transmission to the radio gateway FDCW241 Radio manual call FDM273 Indirect activation via radio gateway –…
  • Page 62: C-Net Topology And Connection

    Installation C-NET detector line 6.5.2 C-NET topology and connection Permissible topology for the C-NET The C-NET can be wired in the topology shown below. Regardless of the topology (loop, stub or loop with sub-stub), the C-NET system limits, such as length, cable resistor, number of users etc., must be observed.

  • Page 63
    Installation C-NET detector line The connection terminals for the C-NET are on the periphery board. Figure 24: Position of C-NET connection terminal on the periphery board ● Max. 126 C-NET devices are permitted on the C-NET connection (block of 4 terminals).
  • Page 64: Wiring Principle Behind C-Net Devices

    Installation C-NET detector line Cable types As a result of national standards and requirements, installation may require a particular cable type. Note the respective requirements and planning documents. The following cable types can always be used for cabling the detector line: ●…

  • Page 65
    Installation C-NET detector line Cerberus Figure 27: Wiring example of C-NET detector devices on stub (1) If shielded connection cables are used, the cable shielding must be connected on one side. * The number of connectable C-NET devices and the max. line length depend on the device connection factor.
  • Page 66: Structure And Function

    Structure and function Indication and operating elements 7 Structure and function 7.1 Indication and operating elements Fire control LED module Floor repeater Floor repeater Cerberus panel FC721 FTO2008 terminal display Remote FT2010 FT2011 Indication Alarm Pre-alarm Fault Isolation Test mode Technology Activation Information (Note)

  • Page 67
    Structure and function Indication and operating elements The FC721 has an integrated operation and indicator field which can be used to operate, maintain and (with limitations) configure the station. Cerberus Figure 28: Operation and indicator field front of Cerberus fire control panel Display, illuminated with plain text display Cursor keypad for navigation/selection of menu items Menu button…
  • Page 68: Extra Indication And Operating Devices

    Structure and function Extra indication and operating devices 7.2 Extra indication and operating devices The FT2010 floor repeater terminal and FT2011 floor repeater display allow for the decentralized indication of the most important events in the fire detection system and limited operation. Both devices can be connected to the C-NET directly as bus users.

  • Page 69: Mimic Display Driver Ft2001

    Structure and function Connecting external alarm indicators 7.2.1 Mimic display driver FT2001 The mimic display driver is a parallel LED indication for the system-wide signaling of events and is connected to the C-NET detector line. The LED are built in a ground plan panel. 7.3 Connecting external alarm indicators Some C-NET devices have an output where normally an ↑…

  • Page 70: Software

    Structure and function Software 7.4 Software The following software is available for planning, configuration and commissioning: For programming the object- and customer-specific control panel functions. FXS7212 Cerberus Engineering Tool FX7220 Cerberus Remote Indicates a graphic representation of a station’s PMI, provided that the PC is connected to the station.

  • Page 71: Operation Functions

    Operation functions Selection and opening / execution 8 Operation functions The following chapters contain descriptions of important functions for directly operating the ↑ site. You will find information on the system functions in the corresponding chapter. 8.1 Selection and opening / execution After calling up the main menu and any other list, the first entry in the list is selected.

  • Page 72: Indication Of The Position And Length Of The List

    Operation functions Indication of the position and length of the list 8.3 Indication of the position and length of the list There is a vertical bar along the side of a list when the list is longer than can be indicated on the display.

  • Page 73: Entry Of Numbers And Letters

    Operation functions Entry of numbers and letters 8.6 Entry of numbers and letters You can use the keyboard to enter numbers and letters in input dialogs. Numeric entry ● The number of underscores corresponds to the number of possible positions for the entry.

  • Page 74: Connectivity And Communication With ‘Station

    Connectivity and communication with ‘Station’ Setting Windows firewall 9 Connectivity and communication with ‘Station’ A PC does not have to be directly connected to a ↑ ‘Station’ to be able to communicate with a ‘Station’ in the ↑ ‘Site’. The PC can be connected to any place in the Ethernet.

  • Page 75: Windows 7 / Windows 8 / Windows 10

    Setting Windows firewall 9.1.2 Windows 7 / Windows 8 / Windows 10 There are different ways of setting up firewall rules in Windows 7/8/10. The following settings apply for Siemens PCs which use group guidelines controlled by the domain. NOTICE The following settings must be made under Local Security Policy.

  • Page 76: Connecting The Pc To The Station

    Connectivity and communication with ‘Station’ Connecting the PC to the station 5. Set the following values: – ‘Protocol type’: ‘UDP’ – ‘Local port’: ‘Specific Ports’, and enter the value range ‘50067-50070’ in the box. – ‘Remote port’: ‘All Ports’ 6. Confirm with ‘OK’. …

  • Page 77: Disconnecting The Pc From The Station

    Connectivity and communication with ‘Station’ Disconnecting the PC from the station 9.3 Disconnecting the PC from the station As the IP address is bound to the MAC address while there is a connection between the PC and the ↑ ‘Station’ and as it remains in the cache even in the case of a short break in the connection of ≤2 min., you must observe the following instructions.

  • Page 78: Initializing ‘Station

    Connectivity and communication with ‘Station’ Initializing ‘Station’ 9.5 Initializing ‘Station’ ● Each ↑ ‘Station’ in a system with several networked ‘Stations’ must have a unique address. ● Once a ‘Station’ has been started for the first time or once the firmware on the main CPU has been updated, a ‘Station’ has the address ‘1’.

  • Page 79
    Connectivity and communication with ‘Station’ Initializing ‘Station’ Initialize ‘Station’ NOTICE Connection module (card cage) FCA2006-A1 defective or installed incorrectly Control panels identified incorrectly, e.g. FC726 identified as FC724. ● Check that the connection module (card cage) FCA2006-A1 is installed correctly. NOTICE Faulty initialization for networked station During initialization, the station must not be connected to the network or any other…
  • Page 80: Loading Configuration From The Pc To The Station

    Connectivity and communication with ‘Station’ Loading configuration from the PC to the station 9.6 Loading configuration from the PC to the station You can use the ‘Download site’ function to load the configuration of one ↑ ‘Site’ from the Cerberus-Engineering-Tool on the PC into the ‘Station’. NOTICE Different network configuration in Cerberus-Engineering-Tool and networked ↑…

  • Page 81
    Connectivity and communication with ‘Station’ Loading configuration from the PC to the station ϖ The ↑ ‘Site’ is opened in Cerberus-Engineering-Tool. ϖ The PC is connected to the ‘Station’. ϖ Networked ‘Stations’ are initialized. ϖ ‘Station’ and Cerberus-Engineering-Tool have the same ‘Site’ ID. ϖ…
  • Page 82: Loading Configuration From The Station To The Pc

    Connectivity and communication with ‘Station’ Loading configuration from the station to the PC 9.7 Loading configuration from the station to the PC The ‘Upload site’ function can be used to load the configuration of a ↑ ‘Site’ to Cerberus-Engineering-Tool on the PC. ϖ…

  • Page 83
     The progress is displayed in the ‘Create backup embedded configuration’ window. Backup file ● The backup file is saved in the following directory as standard: C:ProgramDataSiemensFX7230[Softwareversion]SitesembeddedBackups ● The backup file has the following name: <‘Site’ name>_<backup counter>(_incomplete).fsc Example: Test_Site_007_incomplete.fsc –…
  • Page 84: Commissioning

    Commissioning Creating a backup of the ‘Site’ configuration 10 Commissioning This chapter describes initial commissioning of the Cerberus PRO fire control panel (individual control panel, not networked). ● Activating access level ● Start auto-configuration ● Display C-NET line devices ● Enter customer texts for the control panel, C-NET and individual line devices via the control panel keypad Figure 31: Line tester FDUL221…

  • Page 85: Activating Access Level

    Commissioning Activating access level 10.1 Activating access level The ‘Station’ is protected against unauthorized operation by access levels. Authorization for access level 3 is needed for the functions described below. If the authorization code is not entered, operation is only possible in access level 1 (guest), e.g., for acknowledging the control panel buzzer or scrolling through the display messages.

  • Page 86: Auto-Configuration Of Control Panels

    Commissioning Auto-configuration of control panels 10.2 Auto-configuration of control panels This function requires the control panel, components, and C-NET to have been correctly installed. Once auto-configuration is complete, the control panel is ready for detection with limitations. A fire is recognized by the connected fire detectors and displayed on the control panel.

  • Page 87: Auto-Configure Line

    Commissioning Auto-configuration of control panels 10.2.1 Auto-configure line The ‘Line’ element category in the ‘Maintenance’ menu facilitates the reading-in of the current topology, for example. This creates part of the elements in the ‘Detection tree’. NOTICE Overwriting an existing configuration Parts of an existing customer-specific configuration are lost.

  • Page 88
    Commissioning Auto-configuration of control panels Display for auto-configuration Main menu Access level 3 Exit with <C> Message summary Element search Functions Event memory Favorites Login/logout Topology Settings/administration Function Function On/Off test Select ‘Topology’, continue with <ok> κ Topology Access level 3 Exit with <C>…
  • Page 89: Displaying C-Net Devices

    Commissioning Displaying C-NET devices 007 Elements Module 2 ‘C-NET line card (onboard/FCL2001)’ Line Line Line Line Line Line Line Line Upper Lower More level level Options Select ‘Line 1’, continue with ‘More Options’ <softkey 3> κ Selecting option Execute commands Show details Select ‘Execute commands’, continue with <ok>…

  • Page 90
    Commissioning Displaying C-NET devices 4. Select the corresponding ‘C-NET line card (onboard/FCL2001)’ Module and press the ‘Lower level’ <softkey>.  All lines of ‘C-NET line card (onboard/FCL2001)’ are indicated. 5. Select a line and press ‘More Options» <softkey>.  The ‘Select option’ window is open. 6.
  • Page 91: Entering/Changing Customer Text

    Commissioning Entering/Changing customer text 10.4 Entering/Changing customer text You can enter customer text for any element on the control panel, independently of Cerberus-Engineering-Tool. Once customer text has been entered or changed, the updated display is only shown the next time the element is accessed. Entering or changing customer text does not lead to a reboot.

  • Page 92: Changing Access Authorization Pin

    Commissioning Changing access authorization PIN 10.6 Changing access authorization PIN After successful commissioning, the 4-digit access authorization (PIN) for the corresponding access level must be changed. Keep the new PIN in a safe place. If the PIN is lost, a system reset must be undertaken to the station’s factory setting. The control panel configuration, including all customer data, is cleared in the process.

  • Page 93
    Commissioning Changing access authorization PIN ‘Create PIN’ ϖ You have the required authorization level. 1. Select ‘Main menu’ > ‘Settings/administration’ > ‘Manage PINs’. 2. Select the ‘Create PIN’ menu item. 3. Enter an admissible access level. 4. Enter the PIN in accordance with the input fields and confirm with <ok>. …
  • Page 94: Restart The Station

    Commissioning Restart the station 10.7 Restart the station The configuration of the ↑ ‘Station’ remains the same. There are the following ways in which to restart the ↑ ‘Station’: ● Via the menu on the display ● PMI & mainboard FCM2004 and FCM2027: With the ‘S32’ button ●…

  • Page 95: Detailed Commissioning Steps

    Commissioning Detailed commissioning steps ↑ CPU card 1. Briefly press the ‘S8’ button on the CPU card until a ‘R’ is displayed on the LED matrix display. 2. As soon as the ‘R’ is displayed, press and hold the ‘S8’ button for approx. 2 s to confirm the selection.

  • Page 96: Preparing ‘Station’ For Commissioning -Without Bdv Installation

    Commissioning Detailed commissioning steps 10.8.2 Preparing ‘Station’ for commissioning –without BDV installation 1. Connect the cables for the ↑ detector lines and the peripheral devices. 2. Connect the power supply (mains and batteries).  The ↑ ‘Station’ starts and reads in the internal hardware. …

  • Page 97: Auto-Configuring The Detector Line

    Commissioning Detailed commissioning steps 10.8.4 Auto-configuring the detector line NOTICE Incorrect order for reading in a ↑ loop, no isolation of second ‘Line’ Error when reading in a loop The C-NET detector lines are detected as ↑ stubs during the first system startup, e.g., ‘Line’ 11, ‘Line’ 12 (2-digit line number), even if they are connected as a loop.

  • Page 98: Loading Automatically Created Configuration To The Pc

    Commissioning Detailed commissioning steps 10.8.5 Loading automatically created configuration to the PC The description in this chapter only applies if a configuration has not yet been loaded to the ‘Station’ and if the ↑ BDV was installed at the ‘Station’ after the ‘Station’ was started for the first time.

  • Page 99: Switch Off

    Commissioning Detailed commissioning steps 10.8.7 Switch off 10.8.7.1 Safety during switch-off WARNING System parts that have been switched off make it impossible to acquire and process alarms or faults! Fire may spread unhindered. ● Deploy staff to monitor the deactivated area. ●…

  • Page 100: Restarting The Detector Line

    Commissioning Detailed commissioning steps 10.8.8.2 Switch on zone 1. Select ‘Topology’ > ↑ ‘Detection tree’ > ‘Area’ > ↑ ‘Section’ > ‘Zone’ in the main menu. 2. Press the ‘More Options’ softkey and select ‘Execute commands’. 3. Select the ‘On’ command. …

  • Page 101: Freezing Outputs

    Commissioning Detailed commissioning steps 10.8.10 Freezing outputs You can freeze outputs with connected fire dampers to prevent them from being activated if the ‘Station’ or line is restarted or in the event of a module reset. A restart is required if a modified configuration is loaded to the ‘Station’. Duration of freeze The output freeze lasts until the next restart or module reset.

  • Page 102: Read In Devices On Detector Line

    Commissioning Detailed commissioning steps 10.8.12 Read in devices on detector line NOTICE Incorrect order for reading in a ↑ loop Error when reading in a loop. The C-NET detector lines are detected as ↑ stubs during the first system startup, e.g., ‘Line’ 11, ‘Line’ 12 (2-digit line number), even if they are connected as a loop.

  • Page 103: Remove The Elements

    Commissioning Detailed commissioning steps 10.8.15 Remove the elements If you have uninstalled an C-NET device for good, the corresponding elements, e.g. the ‘Cerberus-Engineering-Tool’ must be removed from the logical structure trees in Zone. You can search for elements using the ‘Find’ function. You will find more information in document A6V10210424.

  • Page 104: Switching On Test Mode

    Commissioning Detailed commissioning steps 10.8.17 Switching on test mode 1. Select ‘Topology’ > ↑ ‘Detection tree’ in the main menu. 2. Select the element you want to switch to test mode: ‘Area’, ‘Section’, or ‘Zone’ 3. Press the ‘More Options’ softkey and select ‘Execute commands’. 4.

  • Page 105: Rectify Localization Errors

    Commissioning Detailed commissioning steps Switching ‘Zone’ to ↑ normal operation There is a shortened procedure for switching individual ‘Zones’ to normal operation: 1. Select ‘Message summary’ > ‘Test message’ in the main menu. 2. Select the displayed ‘Zone’ in test mode and press the ‘Execute Commands’ softkey.

  • Page 106: Remove Or Replace Non-Stationary C-Net Devices

    Remove or replace non-stationary C-NET devices Temporarily remove an individual non-stationary C-NET device 11 Remove or replace non-stationary C-NET devices If an C-NET device is removed, the loop contact prevents the C-NET line from being interrupted and thereby prevents a fault message. The work described in this chapter may be performed when the C-NET line is switched on.

  • Page 107: Temporarily Removing Multiple Non-Stationary Devices

    Remove or replace non-stationary C-NET devices Temporarily removing multiple non-stationary devices 11.2 Temporarily removing multiple non-stationary devices The procedure in this chapter applies both for the base with loop contact and the base without loop contact. For the purpose of painting work, it may be necessary to temporarily remove the C- NET devices in a room.

  • Page 108: Removing Devices, Performing Tasks And Re-Inserting Devices

    Remove or replace non-stationary C-NET devices Permanently removing non-stationary C-NET devices 11.2.2 Removing devices, performing tasks and re-inserting devices Mark the allocation of the devices to the respective base to avoid additional work steps. 1. Remove the devices from their bases. 2.

  • Page 109: Replacing Non-Stationary C-Net Devices Of The Same Type

    Remove or replace non-stationary C-NET devices Replacing non-stationary C-NET devices of the same type 11.4 Replacing non-stationary C-NET devices of the same type Procedure ● Switching on test mode ● Replace C-NET device ● Switch on normal operation ● Connect PC to the ‘Station’ ●…

  • Page 110: Replacing Non-Stationary C-Net Devices Of Different Types

    Remove or replace non-stationary C-NET devices Replacing non-stationary C-NET devices of different types 11.5 Replacing non-stationary C-NET devices of different types Procedure ● Detach C-NET device ● Delete C-NET device on Person Machine Interface ● Installing a new C-NET device ●…

  • Page 111: Testing The Installation

    Testing the installation Testing 12 Testing the installation The fire detection installation can be switched to ‘Test’ operation mode to check it is functioning properly. 12.1 Testing FS720 offers various test functions for efficient testing of devices and logical functions. Some test methods can be combined, others have to be carried out individually.

  • Page 112: Checking Functions

    Testing the installation Checking functions 12.2 Checking functions The table below shows the recommended intervals for checking functions. National specifications always take priority. For details of the function test, refer to the ‘Applicable documents’ chapter. Function Activity Interval (years) Software Check date and time.

  • Page 113: Glossary

    Glossary Glossary External alarm indicator Optical element for displaying the fire location, Abbreviation for ‘alarm indicator’. which is at some distance from the detector. It is normally mounted in the room at the point where Alarm indicator the corresponding detector is accessible. Visual display to signal an alarm or pre-alarm.

  • Page 114
    Glossary Stub Detector line which is only connected to the fire control panel on one side. In the event of an open line or short-circuit, it may no longer be possible for all fire detectors to communicate with the fire control panel. Zone Level in the detection tree.
  • Page 115: Index

    Index Index Entering characters Alarm indicator, external ……..69 Keypad …………73 Auto-configuration Entry of characters Detector line ……….. 97 Numbers, letters (customer text) ….. 73 Station …………96 External alarm indicator ……..69 Backup …………82 Favorites …………72 Battery backup ……….

  • Page 116
    Index Normal operation ……….. 104 Scrolling Numeric key Indication of the position and length of the list . 72 Shortcut …………72 Scroll bars …………72 Scroll in option lists, command lists, element category lists …….. 71 Operating function Scrolling …………71 Date and time ……….
  • Page 117
    Index Windows 7 Zone Firewall …………75 Switch off ……….99, 107 Windows firewall ……….74 Switching on ……… 100, 108 Windows XP Firewall …………74 117 | 118 A6V10211100_f_en_— Building Technologies Fire Safety 2015-12-15…
  • Page 118
    Issued by © Siemens Switzerland Ltd, 2009 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: A6V10211100_f_en_— Manual FS720 Edition: 2015-12-15…

Оглавление

  • Область применения
    • Преимущества и недостатки
    • Принцип работы
    • Виды сигнализации Сименс
    • Краткая инструкция по подключению
    • Видео: Система противопожарной защиты Cerberus Pro

Продукция компании «Сименс» не нуждается в рекламе. Все что она производит от чайников до турбин для электростанций, являются изделиями высочайшего качества. Относительно недавно компания создало подразделение по производству систем безопасности, которое успешно развивается.

Они разработали различного типа дымовые датчики, контрольные панели, сигнализационное оборудование. Пожарная сигнализация «Сименс» серии Cerberus является одним из результатов их деятельности.

Область применения

Системы безопасности компании Siemens могут применяться практически на любых объектах, начиная от небольших офисов до больших производственных сооружений включая тоннели метро. Это возможно благодаря построению иерархической многоуровневой системы с тысячами датчиков, располагаемых на большой площади.

Пожарная сигнализация Siemens на крупном объекте

Пожарная сигнализация Siemens на крупном объекте

Использование интеллектуальных дымовых, аспирационных датчиков собственной разработки, модулей ввода/вывода eb322a, b322 позволяет пожарной сигнализацией Siemens эффективно защищать большие торговые и развлекательные центры, музеи. Применение системы FibroLaser III на основе оптоволокна дает достоверную информацию о пожарной ситуации в тоннелях и кабельных коллекторах.

Преимущества и недостатки

Системы пожарной сигнализации Siemens отличаются высокой надежностью и минимумом ложных срабатываний. С помощью нескольких типов контрольных панелей можно построить широкую однородную сеть или многоуровневую иерархическую структуру. Универсальное программное обеспечение позволяет с ее помощью настраивать любые устройства производимые компанией.

Достаточно научиться настраивать один блок, наладка других устройств, происходит по одному сценарию. Применение нескольких протоколов обмена информации повышает быстродействие, надежность комплекса и упрощает монтаж. Имеется возможность передачи данных по оптоволокну.

Разработаны дымовые и аспирационные датчики беспроводной связи с сетью C-NET, что позволяет быстро менять конфигурацию системы по мере надобности.

К недостаткам пожарных сигнализаций производства «Сименс» можно отнести высокую стоимость.

Принцип работы

Системы пожарной безопасности Siemens являются адресными. Все элементы в комплексе имеют микропроцессорное управление и при включении им автоматически присваиваются индивидуальные номера. Между собой они объединяются по сети.

Для связи контрольных панелей между собой используется быстродействующий протокол C-WEB. На этом уровне может создаваться распределенная однородная система пожарной безопасности. Вся информация с контрольных панелей поступает на центральный пульт управления по сети Ethernet, что обеспечивает высокую скорость обмена данными.

Пульт управления пожарной сигнализации Siemens

Пульт управления пожарной сигнализации Siemens

Все извещатели, начиная от кнопок тревоги и заканчивая дымовыми датчиками, подключаются к контрольной панели по специальной сети C-NET. Пожарная панель управления производит постоянный контроль состояния и сбор информации со всех датчиков. В случае возникновения аварийных ситуаций она подает управляющие сигналы на модуль выходных сигналов, управляющий станцией пожаротушения.

При неисправности извещателей информация передается на центральный пульт. Осуществляется контроль замыкания линии на землю. Программное обеспечение позволяет оперативно изменять конфигурацию системы.

Виды сигнализации Сименс

Система АПС «Сименс» Cerberus PRO является интеллектуальной пожарной сигнализацией предназначенной для различных объектов. Она имеет микропроцессорное управление, может управляться с компьютера по сети Ethernet, соответствует европейским стандартам EN54-2, EN54-4, имеет российский сертификат соответствия.

Имеет развитое программное обеспечение, позволяющее дистанционно изменять конфигурацию системы и загружать диагностические микропрограммы в удаленные модули. Позволяет работать по нескольким протоколам обмена, подключать до 64 контрольных панелей в одном комплексе. По сети C-NET обеспечивает скорость обмена информацией 312 кбит/с.

Система АПС «Сименс» Cerberus PRO

Система АПС «Сименс» Cerberus PRO

Пожарная сигнализация Siemens Cerberus ECO была разработана специально для завоевания российского рынка в области бюджетных систем. Она рассчитана на небольшие помещения, офисы, гостиницы, магазины. Система полностью русифицирована, цены на оборудование зафиксированы в рублях. В обычной конфигурации используется одна контрольная панель и несколько извещателей, в зависимости от конфигурации сооружения.

Пожарная сигнализация Siemens Cerberus ECO

Пожарная сигнализация Siemens Cerberus ECO

ПС Sinteso надежная система безопасности, рассчитанная на большие распределенные объекты. Контрольные панели и протокол обмена FCnet разработаны в соответствии с EN54-2, EN54-4. Высокий уровень надежности, достигнут за счет применения новейших извещателей Sinteso™ (FDnet). Для станций управления в системе применяется BACnet-интерфейс. Сеть FDnet позволяет обслуживать 126 устройств в одном шлейфе, применять Т-образные ответвления.

Длина сети FDnet допускается до 96 км, между контрольными панелями до 3км (по оптоволокну). При использовании сети Ethernet система способна управляться из любой точки мира. Обычно идет в комплексе с системами автоматического пожаротушения.

ХС10 представляет собой систему обнаружения возгорания и управления пожаротушением. Может работать с двумя типами безадресных датчиков и с любыми системами пожаротушения независимо от тушащего вещества. Обеспечивает автономную работу установки пожаротушения и интегрируется в сложные комплексы безопасности.

Система FibroLaser III предназначена для раннего оповещения о случаях возгорания на объектах типа тоннелей, где у людей отсутствуют пути эвакуации, кроме зоны пожара. Принцип действия основан на измерении прозрачности оптоволокна в зависимости от изменения окружающей температуры. Имеет высокую помехозащищенность от электромагнитных помех, устойчив к внешним воздействиям.

Краткая инструкция по подключению

Монтаж пожарной сигнализации Siemens Cerberus производится по простой инструкции, как в случае обычной системы безопасности. Панель управления подключается к сети напряжением 220 В. Извещатели, подключаемые к данной панели, питание получают по двухпроводному кабелю сети C-NET. Сначала устанавливаются базы датчиков, подключаются кабели, затем вкручиваются сами извещатели.

Схема подключения пожарной сигнализации Siemens

Схема подключения пожарной сигнализации Siemens

При подаче питания на контрольную панель происходит включение всех датчиков, автоматическое присвоение им уникальных адресов. Конфигурирование системы осуществляется с панели или компьютера, на который приходит информация от всех блоков комплекса. Программное обеспечение унифицировано для всех элементов оборудования, что значительно упрощает монтаж и наладку системы.

Видео: Система противопожарной защиты Cerberus Pro

Это тоже интересно:

  • Пожарная мотопомпа мп 600 инструкция
  • Подшивка свесов кровли софитами инструкция
  • Пожарная машина из спичечных коробков пошаговая инструкция
  • Подшивка потолка вагонкой своими руками пошаговая инструкция
  • Пожарная безопасность на производстве охрана труда инструкция

  • Понравилась статья? Поделить с друзьями:
    0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии