Предложите, как улучшить StudyLib
(Для жалоб на нарушения авторских прав, используйте
другую форму
)
Ваш е-мэйл
Заполните, если хотите получить ответ
Оцените наш проект
1
2
3
4
5
Protectionand control
VIP300
Technical manual
technical manual VIP3002
contents1. presentation of the VIP300………………………………………………………32. use and settings …………………………………………………………………….43. choice of sensors and operating ranges ……………………………………94. connection scheme ………………………………………………………………..105. assembly ………………………………………………………………………………116. IDMT tripping curves ………………………………………………………………137. technical characteristics ………………………………………………………….178. testing of the VIP300 and use of the VAP6 ………………………………..20
technical manual VIP300 3
1. presentation of the VIP300
VIP300
Mitop
— simplified wiring scheme —
10Is
t>
I>>
t>>
— phase or earth fault curves —
1,2Is I
t
self-powered protective relayn The VIP300 relay is designed foruse in distribution networks. It may beused as MV/LV transformerprotection, protection at the incomingpoint of industrial installations, andalso as branch feeder protection.n The VIP300 provides protectionagainst phase-to-phase faults andearth faults. The choice of trippingcurves and the multiple settings allowit to be used in a wide variety ofdiscrimination plans.The VIP300 is a self-powered relay,energized by the current sensors; itdoes not require any auxiliary source.It actuates a Mitop release.
phase protectionThe phase protection has twoseparately adjustable settings:n the low setting may be chosen withdefinite time or IDMT. The IDMTcurves are in compliance with the IEC255-3 standard. They are of thestandard inverse, very inverse andextremely inverse types.The low setting may also be usedwith the RI curve.n the high setting is of the definitetime type.
earth protectionThe earth fault protection operates byresidual current measurement: it usesthe sum of the sensor secondarycurrents.Like phase protection, earthprotection has two separatelyadjustable settings.
LL and LH modelsThere are two models of the VIP300:VIP300LL and VIP300LH, They differwith respect to :n operating range.Refer to the chapter entitled «choiceof sensors and operating ranges».n the VIP300LH has a table forsetting «equivalent time multiplier»conversion on the front.
sensorsIn order for the specifiedperformances to be obtained, theVIP300 relay must be used with thefollowing current transformers:n CRa and CRb sensors:(for RM6s 1998 and later).n CSa and CSb sensors of the SFsetcircuit breaker. The CSa and CSbsensors have the same number ofsecondary turns as the CRa and CRbsensors respectively.n 200/1 and 800/1 sensors of theRingmaster:
descriptionn The VIP300 relay is mounted in apolycarbonate injected casing whichprotects it against dripping water anddusty environments.The front is protected by atransparent cover fitted with a sealingjoint. The cover may be lead-sealedto prohibit access to the settings.n Rotating selector switches areused for setting. The phase settingcurrent and earth fault setting currentare set in amperes. This means thatthe scale on the front must beadapted to suit the sensor used. Thisis done by positioning a «setting scalelabel» on the relay at the time ofassembly.n Connections are made on the backusing fast-on clips.
indicationTwo indicators indicate the origin oftripping (phase or earth). They stay inposition after a break in the relaypower supply.Two LEDs (phase and earth) indicatethat the low setting has been overrunand that the time delay is running.
technical manual VIP3004
2. use and settings
front view
I>>
(sec)0.03
0.050.1
0.2 0,40,60,9
1.5
(x Ios)
t>>t> (sec)
0.1
0.05 0.6
0.15 0.20.3
0.40.07x 1
x 10
I>overcurrentphase
curve selection
curve selection
Is
I>
Ios
Io>
to>(sec)
to>>
VIP300LL range: x 1
sensors:
earth fault
Io>
reset
trip
trip
minimum operatingphase current : 10A
(A)
1012
15
1821 24 28
32
36
404550
303540
16
124
8 122025
6
(A)
DT only
(x Is)
31
1.2
1.82.42.7
2.11.5
DT only
(x Ios)
DT
SIVI EI
RI off
(x Is)
34
69 12
1520
off
x 1
x 10
VIP 300
1.2Is 10Is
t>
I>>
t>>
EI, VI, SI
I>
RI
DT
Is
Io>>
DT
SIVI EI
RI off
31
1.2
1.82.4
2.7
2.11.5
3
4
69 12
15
20
off
0.03
0.05
0.10.2 0,4
0,6
0,9
1.5(sec)
0.07
0.05
0.10.15 0.2
0.3
0.4
0.6
VAP6 test plug
1 2 3 4 5 6 7 8 9 10
ba
c
11 12 13 14 15 16 17 18 19 20
e
d
CRa 51007003F0
— front panel —
f
phase protection earth protection other functions1. phase setting zone2. setting overrun indicator3. phase trip indicator4. phase setting current Is5. choice of low setting curve type6. low setting I>7. low setting time delay t>8. multiplying factor (low setting)9. high setting I>>10. high setting time delay t>>
11. earth setting zone12. setting overrun indicator13. earth trip indicator14. earth setting current Ios15. choice of low setting curve type16. low setting Io>17. low setting time delay to>18. multiplying factor (low setting)19. high setting Io>>20. high setting time delay to>>
a. setting scale labelb. sensor and range informationc. indicator resetd. minimum operating currente. VAP6 test plugf. VIP300LL: tripping curves VIP300LH: table for « equivalenttime multiplier » conversion.
technical manual VIP300 5
2. use and settings (cont’d)
tripping curves
1,2 Is 10 Is
t>>
t>
I>>
SI, VI, EI, RIlow setting
4
10
9
5
87
Is
fig 1: phase setting : IDMT low threshold
1,2 Is I>
t>>
t>
I>>
fig 2: phase setting: definite time low threshold
DTlow setting 5
6
9
10
4
87
Is
settings
phase protection settingThe numbers indicated on the curvesopposite are those of the phaseprotection setting switches (refer tothe diagram of the front view).
Set:n setting current Is (4)n type of low setting I> curve (5) IDMT: RI, SI, VI, EI definite time: DTn low setting I> (6)This setting is only active if the lowsetting curve chosen is of the definitetime DT type (fig 2). For the otherchoices, SI, VI, EI, RI (fig 1), theselector switch is disabled.n low setting time delay t> (7) and (8)n high setting I>> (9)n high setting time delay t>> (10)
earth protection settingThe principle is the same as forphase protection.
Set:n setting current Ios (14)n type of low setting Io> curve (15) IDMT: RI, SI, VI, EI definite time: DTn low setting Io> (16)This setting is only active if the lowsetting curve chosen is of the definitetime DT type. For the other choices,SI, VI, EI, RI, the selector switch isdisabled.n low setting time delay to> (17) and(18)n high setting Io>> (19)n high setting time delay to>> (20)
operationThe high and low settings operateseparately. The tripping order resultsfrom the «logical OR» between thetwo settings.
technical manual VIP3006
2. use and settings (cont’d)
phase protection
1. phase protection settingzoneAll the information concerning phaseprotection is grouped together in thedark zone of the upper half of thefront face.
2. setting overrun indicatorWhen the red indicator blinks, itmeans that the phase protection lowsetting time delay is running. Whenthis is the case, if the current doesnot decrease, the relay will trip.n for IDMT curves (SI, VI, EI), theLED lights up when the current isgreater than 1.2 times the settingcurrent Is.n for the IDMT curve (RI), it lights upwhen the current is greater than theIs setting.n for the definite time curve DT, itlights up when the low setting isoverrun.F also refer to «indicator resetbutton».
3. trip indicatorIt is normally black and turns yellowto indicate that the phase protectionhas given a tripping order. It stays inthe same status, even when the relayis no longer energized.
4. choice of setting current IsThe setting current setting rangedepends on the sensor and rangeused: the selector switch scaleshould be adapted to suit the sensorand range using the setting scalelabel.F also refer to «choice of sensorsand operating ranges» chapter.
5. choice of type of low settingcurveDT: definite timeSI: inverse timeVI: very inverse timeEI: extremely inverse timeRI: specific curveoff: low setting is disabled.
6. choice of low setting I>The setting is a multiple of the settingcurrent. It is only active for definitetime settings (selector switch 5 set toDT).If the tripping curve is selected withIDMT (selector switch 5 set to RI, SI,VI, EI), the selector switch has noeffect.
7. setting of low setting timedelay t>.n If the tripping curve is of thedefinite time (DT) type, the selectorswitch sets the low setting time delay.n If the curve is of the IDMT type (RI,SI, VI, EI), the value displayed is thetripping time for a phase currentequal to 10 times the setting current.
8. low setting time delaymultiplying factor.In the x10 position, the time delaydisplayed on selector switch 7 ismultiplied by 10.
9. setting of high setting I>>.The high setting is chosen as amultiple of the setting current.In the «off» position, the high setting isdisabled.
10. setting of high setting timedelay t>>.The time delay is set directly inseconds.
technical manual VIP300 7
2. use and settings (cont’d)
earth protectionThe setting principle is the same asfor phase protection.
11. earth protection settingzoneThe earth protection settings aregrouped together in the dark zone ofthe lower half of the front face.
12. setting overrun indicatorWhen this indicator blinks, it meansthat the earth protection low settingtime delay is running. When this isthe case, if the current does notdecrease, the relay will trip.n for IDMT curves (SI, VI, EI), theLED lights up when the current isgreater than 1.2 times the settingcurrent Ios.n for the IDMT curve (RI), it lights upwhen the current is greater than theIos setting.n for the definite time curve DT, itlights up when the low setting isoverrun.F for the cases above, the LED onlylights up when a phase current isgreater than the minimum operatingcurrent.F also refer to «indicator resetbutton».
13. trip indicatorIt is normally black and turns yellowto indicate that the phase protectionhas given a tripping order. It stays inthe same status, even when the relayis no longer energized.
14. choice of setting current IosThis is the maximum residual currentthat can flow in the network withoutthe protection being triggered.The Ios current setting rangedepends on the sensor and rangeused: the selector switch scaleshould be adapted to suit the sensorand range using the setting scalelabel.F also refer to «choice of sensorsand operating ranges» chapter.
15. choice of type of low settingcurveDT: definite timeSI: inverse timeVI: very inverse timeEI: extremely inverse timeRI: specific curveoff: low setting is disabled.
16. choice of low setting Io>The setting is a multiple of the settingcurrent. It is only active for definitetime settings (selector switch 15 setto DT).If the tripping curve is selected withIDMT (selector switch 15 set to RI, SI,VI, EI), the selector switch has noeffect.
17. setting of low setting timedelay to>.n If the tripping curve is of thedefinite time (DT) type, the selectorswitch sets the low setting time delayn If the curve is of the IDMT type (RI,SI, VI, EI), the value displayed is thetripping time for an earth currentequal to 10 times the setting current.
18. low setting time delaymultiplying factor.In the x10 position, the time delaydisplayed on selector switch 17 ismultiplied by 10.
9. setting of high setting Io>>.The high setting is chosen as amultiple of the setting current Ios.In the «off» position, the high setting isdisabled.
10. setting of high setting timedelay t>>.The time delay is set directly inseconds.
technical manual VIP3008
2. use and settings (cont’d)
other functions
CRb 51007004F0VIP300LL range: x 1
Is
Ios
(A)
6.212.525
3750 75
187218
156
100125
250
6275
94112
131 150 175
200225
250281312
(A)
recto
minimum operatingphase current : 62A
CRb 51007004F0VIP300LL range: x 4
Is
Ios
(A)
2550
100
200 300 400150
8751000
750625
500
250300
375450
525 600 700800900
100011251250
(A)
verso
minimum operatingphase current:250A
— setting scale label —
sensors: sensors:
— how to install the setting scale label —
a. setting scale labeln it should be mounted on theVIP300 when it is assembled on thecircuit breaker. The label indicatesthe scales for the phase settingcurrent and earth protection settingcurrent. It is inserted, from the top,behind the transparent part of thefront face.n each VIP300 comes with a set oflabels. Install the label that matches:- the type of sensor used- the VIP300 model- the range usedn each setting scale label matches asensor and is printed on both sidesfor each of the 2 ranges. The labelmay therefore be turned around if theVIP300 range is changed during theservice life of the installation.F also refer to «assembly» chapter.
b. sensor and range indicationThe text is printed on the settingscale label.When the label is installed in the slot,the text is hidden by an opaque zone.It is not visible to the user.
c. indicator reset buttonThe button is accessible when thetransparent cover is closed. Whenthe button is pressed, 2 actions aretriggered:n it resets (black position) the 2phase and earth trip indicators. Whenthe relay is no longer energized, it isstill possible to reset the indicators forabout 48 hours. After that time, theymay be reset after the VAP6 isplugged in.n it triggers the lighting up of the 2red LEDs (about 3 sec). Thisindicates that: — the relay is energized. The indicatorlights up when the current is greaterthan the minimum operating current. — relay self-testing results are OK.If one of the two conditions is notmet, the indicators do not light up.This function may be used to carryout a basic relay operation test.
d. minimum operating currentThe minimum operating current is thephase current required for the relay tobe energized and operational. It isprinted on each setting scale label.The value given on the setting scalelabel is the single-phase rmsminimum operating current.The minimum operating current isalways the lowest setting currentsetting.
F note regarding minimumoperating current:The VIP300 does not operate belowthe minimum operating current level.As a result, if the earth protectionsare set below the minimum operatingcurrent, they will only take effectwhen there is phase current greaterthan or equal to the minimumoperating current.
e. VAP6 test plugThe test plug is exclusively designedfor connection of the VAP6 which isused for fast, simplified relay testing.The operation may be carried outwhile the relay is operating since theVAP6 and VIP300 provide thepossibility of testing with inhibition ofcircuit breaker tripping.F also refer to the «testing of theVIP300 and use of the VAP6″chapter.
— testing of the VIP300 using the VAP6 —
technical manual VIP300 9
3. choice of sensors and operating ranges
selection principleChoose the sensor to be used andthe VIP300 connection range inaccordance with the desiredoperating range. Refer to the chartsbelow.
sensorsThe VIP300 should be used with thespecified sensors. The relay/sensorassembly must be used together inorder to comply with thecharacteristics, in particular:- operation across the range- response time- accuracy- short-circuit current behaviourIt is compulsory for the 3 sensors tobe of the same type.
sensors specified for VIP300LL:- CRa 200/1 51007003F0 (1)- CRb 1250/1 51007004F0 (1)
sensors specified forVIP300LH:- Ringmaster 200/1 4509996A0- Ringmaster 800/1 4509169A0
(1): for RM6 model 98 and higher.
rangeThe VIP300 relay contains inputtransformers that have anintermediary tap on the primarywinding. Each tap corresponds to arating with a different operating range.
VIP300LL model ranges:- X1- X4VIP300LH model ranges:- X2- X4
VIP300LL model operating ranges
CRa
CRb
10 20K100 1k 10k20 30 60 200 300 600 2k 3k 6k
4k
50
40
62,5 312 6,25K
25K250 1,25K
range x1
range x4
range x4
range x1
10
200
1k
Amps
VIP300LH model operating ranges
Ringmaster 200/1
Ringmaster 800/1
10 20K100 1k 10k20 30 60 200 300 600 2k 3k 6k
4k40
80 400 8K
16K160 800
range x2
range x4
range x4
range x2
200
10020 2k
Amps
operating current Is setting range
selective operating range
For a given operating range, thebottom of the setting current rangerepresents the relay minimumoperating current.
technical manual VIP30010
4. connection scheme
wiring to x1 (or x2) rangeVIP300LL
S1
S2
S1
S2
S1
S2
x 4
x 4
x 4
x 4
P1
P2P1
P2P1
P2
1 2 3
3
4
5
6
7
8
9
1
2
(VIP300LH)
x 1 (x2)
x 1 (x2)
x 1 (x2)
x 1 (x2)
L3
L2
L1
Io
MITOP
+- 15
16
10
11
12
13
14 0 V
wiring to x4 rangeVIP300LL
S1
S2
S1
S2
S1
S2
x 4
x 4
x 4
x 4
P1
P2P1
P2P1
P2
1 2 3
3
4
5
6
7
8
9
1
2
(VIP300LH)
x 1 (x2)
x 1 (x2)
x 1 (x2)
x 1 (x2)
L3
L2
L1
Io
MITOP
+- 15
16
10
11
12
13
14 0 V
The connection is made on the backof the VIP300
connection using fast-on clipsThe standard way to connect theVIP300 is by means of 6.35 mm fast-on clips.
technical manual VIP300 11
5. assembly
cut-out
161 0.5mm
130 0.5mm
— drilling of cut-out —
The VIP300 is flush-mounted in arectangular cut-out made in a metalplate 3 mm thick at the most.
assembly
E
VN
P
n insert the VIP300 in the cut-out andcorrectly position the 2 lower pins (E)of the casing on the edge of themetal plate cut-out.n tighten the screws (V) on the 2mounting lugs accessible via the frontface after having opened thetransparent cover.n after tightening, make sure that thelatch (N) of each lock (visible on therear face) is in the vertical position,pressing against the support plate.F the latch may be put into thevertical position by loosening each ofthe screws (V) before tighteningthem.n the hole (P) may be used to lead-seal the relay after the setting scalelabel is installed and the settings aremade.
installation of the setting scale label
M
n slide the setting scale label intoposition behind the transparent partof the front face.F refer to the section entitled»choice of the setting scale label».n make sure that the informationgiven at the top of the label (M)matches: the sensor used (sensor) the VIP300 model the range used (range)This information is hidden when thelabel is in position.n make sure that it is pushed right tothe bottom of the slot.n to remove the label, use the hole inthe top, if necessary with the help ofthe tip of a pencil or a screwdriver.
technical manual VIP30012
5. assembly (cont’d)
choice of the setting scale label
for VIP 300 LL with CRa sensors for VIP 300 LL with CRb sensors
Is
Ios
minimum operatingphase current : 10A
1012
1518
21 24 2832
3640
4550(A)
303540
16
12
4
8 12
2025
6
(A)
VIP300LL range: x 1
sensors:CRa 51007003F0
recto
sensor:
VIP300LL range: x 4
Is
Ios
48
1624
32 48 6480
160 140120100
(A)
7284 96 112
128144160
1802004048
60
(A)
minimum operatingphase current :40A
verso
CRa 51007003F0
x 1 range x 4 range
Is
Ios
(A)
6.312.52537
50 75
187218
156
100125
250
6375
94112
131 150 175
200225
250281312
(A)
recto
minimum operatingphase current : 63A
Is
Ios
2550
100
200 300 400150
8751000
750625
500
(A)
250300
375450
525 600 700800900
100011251250
(A)
verso
minimum operatingphase current:250A
sensor:
VIP300LL range: x 1
CRb 51007004F0sensor:
VIP300LL range: x 4
CRb 51007004F0
x 1 range x 4 range
for VIP 300 LH with 200/1 RMR sensors for VIP 300 LH with 800/1 RMR sensors
Is
Ios
48
1624
32 48 6480
160140
120100
(A)
7284 96 112
128144160
1802004048
60
(A)
minimum operatingphase current : 40A
verso
sensor:
VIP300LH range: x 4
200/1: 4509996A0
Is
Ios
24
812
16 24 3240
80 706050
(A)
3642 48 56
647280
901002024
30
(A)
minimum operatingphase current : 20A
recto
sensor:
VIP300LH range: x 2
200/1: 4509996A0
x 2 range x 4 range
Is
Ios
(A)
816
3248
64 96
240280
200
128160
320
8096
120144
168 192 224256288
320360400
(A)
minimum operatingphase current : 80A
sensor:
VIP300LH range: x 2
800/1 4509169A0
Is
Ios
1632
64
128 192 25696
560640
480400
320
(A)
160192
240288
336384 448
512576
640720800
(A)
minimum operatingphase current:160A
sensor:
VIP300LH range: x 4800/1 4509169A0
versorecto
x 2 range x 4 range
technical manual VIP300 13
6. IDMT tripping curves
n the curves in this chapter indicatethe IDMT low setting tripping times forthe 16 time delay t> (or to>) settings.
n the phase protection and earthprotection curves are the same.
n the numbers given on the right ofthe curves represent the position ofthe time delay t> (or to>) selectorswitch.(if the multiplying factor x1 / x10 is inthe x10 position, multiply the timesindicated by 10).
SI curve
SI
I/Is
t (s
)
0.01
0.1
1
10
100
1 10 100
0,05
0,07
0,1
0,15
0,2
0,3
0,4
0,6
1,2 Is
technical manual VIP30014
6. tripping curves (cont’d)
VI curve
VI
I/Is
t (s
)
0.01
0.1
1
10
100
1 10 100
0,05
0,07
0,1
0,15
0,2
0,3
0,4
0,6
1,2 Is
technical manual VIP300 15
6. tripping curves (cont’d)
EI curve
EI
I/Is
t (s
)
0.01
0.1
1
10
100
1000
1 10 100
0,050,07
0,1
0,150,2
0,30,4
0,6
1,2 Is
technical manual VIP30016
6. tripping curves (cont’d)
RI curve
RI
I/Is
t (s
)
0.01
0.1
1
10
1 10 100
0,05
0,07
0,1
0,15
0,2
0,3
0,4
0,6
technical manual VIP300 17
7. technical characteristics
phase protection accuracy see noteslow setting I> ± 5% or 0/+2A 1low setting time delay t>
definite timeIDMT
± 2% or ± 20 msclass 5 according to IEC 60255-3 or0/+20ms
2, 82, 8
high setting I>> ± 5%high setting time delay t>> ± 2% or ± 20 ms 2% of pick-up 95%storage time 20 ms
earth protection accuracy see noteslow setting Io> ± 5% or 0/+2A 3, 4, 5low setting time delay to>
definite timeIDMT
± 2% or ± 20 msclass 5 according to IEC 60255-3 or0/+25ms
2, 82, 5, 8
high setting Io>> ± 5%high setting time delay to>> ± 2% or ± 20 ms 2, 8% of pick-up 95%storage time 20 ms
general characteristics valuesteady thermal resistance 240 A
1500 A240 A960 A
with CRa sensorwith CRb sensorwith RMR 200/1 sensorwith RMR 800/1 sensor
1 sec thermal resistance 25 kA/1s25 kA/1s20 kA/1s
with CRa, CRb, RMR800/1sensorswith RMR200/1 sensor onrange x2with RMR200/1 sensor onrange x4
operating frequency 50 Hz ± 10%, 60 Hz ± 10%operating temperature -25° C to +70° Cstorage temperature -40°C to +85°Cweight 1.7 kg
minimum operating current range value see notesVIP300LL + CRa sensor x1 10A 7
x4 40AVIP300LL + CRb sensor x1 62A
x4 250AVIP300LH + RMR 200/1 sensor x1 20A
x2 40AVIP300LH + RMR 800/1 sensor x1 80A
x2 160A
climatic resistance standard severitylow temperature operation IEC 60068-2-1 -25°C, 16hlow temperature storage IEC 60068-2-1 -40°C, 96hhigh temperature operation IEC 60068-2-2 +70°C, 16hhigh temperature storage IEC 60068-2-2 +85°C, 96hfast changes in temperature IEC 60068-2-14 -25°C to +70°C, 5 cyclesoperation in damp heat IEC 60068-2-3 56 days, 93% RHsalt spray IEC 60068-2-52 severity 1
mechanical resistance standard severityvibrations IEC 60255-21-1 class 2shocks and jolts IEC 60255-21-2 class 2earthquakes IEC 60255-21-3 class 2enclosure protection index EN 60529 IP54, (cover closed)fire resistance IEC 60695-2-1 650°C
technical manual VIP30018
7. technical characteristics (cont’d)
electrical resistance standard severitysensor input isolation IEC 60255-5 2 kV rms, 50 Hz, 1 mn1.2/50 µs impulse voltage IEC 60255-5 5 kV, note 61 MHz dampened oscillating wave IEC 60255-22-1 2,5 kV cm, note 6
1 kV dmrapid transient bursts IEC 60255-22-4 4 kV cm and dm, 5 kHz burst, note 61.2/50(8-20 µs) hybrid wave IEC 61000-4-5 2 kV, 42 ohms, note 6electrostatic discharge IEC 60255-22-2 8 kV in air, 6 kV on contactHF electromagnetic field IEC 60255-22-3 30V/m not modulated, 27 to 1000 MHz
EN 50082-2 10 V/m mod. ampl., 80 to 1000 MHzEN 50082-2 10 V/m mod.impuls., 900 MHz
notes
1. Value given for three-phaseVIP300 power supply.For single-phase operation, theaccuracy range is ± 10% or 0/+4A.For the low setting, this does notgenerally represent a real operatingsituation. However, it may occurduring injection testing carried outwith single-phase.The error is mainly due to the non-linearity of the sensors and VIP300input transformers with weak current,the inaccuracy being accentuatedwhen the relay is only supplied byone phase.
2. The accuracy is indicated for afault that occurs when the VIP300 isalready supplied by the current letthrough by the circuit breaker. Theaccuracy is indicated for sinusoidalcurrent. In the event of closing whilea fault is present, the tripping timemay be extended by:
+30 ms at 1.5 Is+20 ms from 2 Is to 10 Is+10 ms above 10 Is
3. Generally speaking, the accuracyranges of earth protection times andsettings are indicated for when theVIP300 is supplied by current that isgreater than or equal to the minimumoperating current. The measurementof a setting for earth protection withsingle-phase supply is therefore notsignificant if the setting is lower thanthe minimum operating current.
4. Value given for three-phaseVIP300 supply. For single-phasetesting, the accuracy is ± 10% or0/+4A. For the low setting, this mayoccur when the earth protection istested with single-phase supply, andno supply by the other phases.
5. In the following specific conditions:- VIP300LL- with CRa sensor- wiring to x1 range- if Ios < 8A- if phase current < 20A
the setting and time delaycharacteristics are:
— low settings: ±10% 0/+4A- class not specified
6. Not applicable to test plug
7. Accuracy ± 10% or ± 1.5A.The value indicates the guaranteedminimum operating current for single-phase operation. With three-phaseoepration, it may be less than thevalue indicated.
8. The tripping times indicated do notinclude the mitop response time. Itstripping time depends on itsmechanical load (for no load, itstripping time is less than 5 ms)
technical manual VIP300 19
7. technical characteristics (cont’d)
dimensions
159
179
139
22
raccordemen
90
1276
technical manual VIP30020
8. testing of the VIP300 and use of the VAP6
presentation of the VAP6
battery test
phase overcurrent
on
test in progress
trip
earth fault
VAP 6
trip inhibition
+ -external mitop
VIP30VIP35VIP300VIP50VIP37
mitopcircuit breaker
earth fault
phaseovercurrent
trip trip
test
VIP11,11RVIP12RVIP13VIP17VIP200,201
circuit breaker
phaseovercurrent
testmitop
externalmitop
inhibition
— VAP6 front panel —
The VAP6 is a portable unit that isconnected to the VIP300 to carry outsimplified testing.The test can be carried out in thefollowing two cases:- the VIP300 is already supplied bythe sensors.- the VIP300 is not supplied. In thiscase, the VAP6 batteries supplypower to the relay.
The test consists of:- starting up the VIP300 central unitself-testing sequence.- injecting a stimulus to simulate aphase fault.- injecting a stimulus to simulate anearth fault.- checking tripping.Frefer to the description of the testin the section entitled «test sequence»F the VAP6 is supplied by batteries.Therefore the parts of the VIP300that run on AC current are notchecked using this method (input andsupply circuits).
push-buttonsn battery test: if the batteries areOK, the «on» indicator lights up whilethe button is pushed.n phase overcurrent: it sends thephase protection test stimulus. Thestimulus is equivalent to 20 times thesetting current Is.n earth fault: it sends the earthprotection test stimulus. The stimulusis equivalent to 20 times the earthsetting current Ios.n trip inhibition: press the «tripinhibition» button if the VIP300 testshould be carried out without trippingof the circuit breaker. Circuit breakertripping is inhibited while the ’tripinhibition» button is pressed, even ifthe tripping order results from a realfault.
indicatorsn on: indicates that the batteries areoperating. Also lights up when thebattery test is carried out by pressing»battery test».n test in progress: confirms sendingof the test stimulus to the VIP300.n trip: it is used to test other relays inthe VIP range. It is not to beconsidered for the VIP300 test. (itlights up for a transient period whenthe VIP300 sends a tripping order;whether or not the circuit breaker isinhibited).
«external mitop» outputIt may be used to connect anauxiliary mitop designed, for instance,to stop a stop watch during operatingtests. The mitop is triggered at thesame time as the circuit breakermitop. It is not inhibited by pressingthe «trip inhibition» button.
batteriesn the batteries are normallydeactivated and are automaticallyactivated when the VAP6 isconnected to the VIP300.They are activated in the followingcases:- pressing the «battery test» button.- direct connection to a VIP3X orVIP5X relay.- connection to the adapter corddesigned for testing of the VIP1X orVIP2X relays.n to install or change the batteries,open the unit by removing the 4screws on the bottom of the unit. Besure to use the correct polarities.
technical characteristicssupply: 3 x 9V 6LR61batteriesweight: 0.45 kgdimensions: 93x157x45
technical manual VIP300 21
8. testing of the VIP300 and use of the VAP6 (cont’d)
VAP6 test sequence
The test may be carried out with orwithout current in the sensors. Duringthe test operations, all the VIP300settings are effective; the relayshould perform in accordance withthe settings. During the test, the relayremains operational and will give atripping order in the event of a fault,unless the «trip inhibition» button ispressed.
n connect the VAP6 to the «VAP6test plug». The VAP6 batteries areactivated and the «on» indicator lightsup.
n press the VIP300 «reset» button.- if the 2 «trip» indicators were yellow,they become black.- the 2 red I> and Io> indicators of theVIP300 light up for about 3s toindicate that the central unit hascorrectly performed self-testing.
n press the «trip inhibition» button ifthe test should be carried out withouttripping of the circuit breaker.Fbe sure to continue pressing the»trip inhibition» button throughout thetime it takes to send the stimulus.
n press the «phase overcurrent»button to send the phase protectiontest stimulus.- continue pressing the buttonthroughout the duration of thestimulus. The stimulus representsabout 20 times the setting current Is.- the VAP6 «test in progress» indicatorlights up to confirm the sending of thestimulus to the VIP300 relay.- the red «I>» indicator of the VIP300blinks during the time delay period.- then the VIP300 phase «trip»indicator turns yellow.- the circuit breaker trips if it is notinhibited.F if the «phase overcurrent» button isheld down after tripping, the VIP300starts the time delay/tripping cycleagain; this is normal operation.In that case:- the VAP6 red «trip» indicator lightsup for a transient period each timethere is a trip.- depending on the time delay setting,the VIP300 red «I>» indicator may beoff or blink rapidly and/or in anirregular manner.
n press «earth fault» to test operationof the earth protection. The stimulusinjected is equal to 20 times thesetting current Ios. Use the sameprocedure as for the phase protectiontest.
n disconnect the VAP6.In order to save batteries, do notleave the VAP6 connected to therelay unnecessarily.
technical manual VIP30022
Notes
technical manual VIP300 23
Notes
technical manual VIP30024
Schneider Electric SA Postal addressF-38050 Grenoble cedex 9Tél : +33 (0)4 76 57 60 60Télex : merger 320842Fhttp://www.schneider-electric.comRcs Nanterre B 954 503 439
Rcs Nanterre B 954 503 439
As standards, specifications and designs changefrom time to time, please ask for informationgiven in this publication
Publishing: Schneider Electric SADesign, production: Schneider Electric SAPrinting:
This document has beenprinted on ecological paper
PCRED399008ENART. 20499 04 / 1999
1 Protection and control VIP300 Technical manual
2 contents 1. presentation of the VIP use and settings choice of sensors and operating ranges connection scheme assembly IDMT tripping curves technical characteristics testing of the VIP300 and use of the VAP technical manual VIP300
3 1. presentation of the VIP300 Mitop VIP300 — simplified wiring scheme — t t> t>> 1,2 10 I>> — phase or earth fault curves — I self-powered protective relay n The VIP300 relay is designed for use in distribution networks. It may be used as MV/LV transformer protection, protection at the incoming point of industrial installations, and also as branch feeder protection. n The VIP300 provides protection against phase-to-phase faults and earth faults. The choice of tripping curves and the multiple settings allow it to be used in a wide variety of discrimination plans. The VIP300 is a self-powered relay, energized by the current sensors; it does not require any auxiliary source. It actuates a Mitop release. phase protection The phase protection has two separately adjustable settings: n the low setting may be chosen with definite time or IDMT. The IDMT curves are in compliance with the IEC standard. They are of the standard inverse, very inverse and extremely inverse types. The low setting may also be used with the RI curve. n the high setting is of the definite time type. earth protection The earth fault protection operates by residual current measurement: it uses the sum of the sensor secondary currents. Like phase protection, earth protection has two separately adjustable settings. LL and LH models There are two models of the VIP300: VIP300LL and VIP300LH, They differ with respect to : n operating range. Refer to the chapter entitled «choice of sensors and operating ranges». n the VIP300LH has a table for setting «equivalent time multiplier» conversion on the front. sensors In order for the specified performances to be obtained, the VIP300 relay must be used with the following current transformers: n CRa and CRb sensors: (for RM6s 1998 and later). n CSa and CSb sensors of the SFset circuit breaker. The CSa and CSb sensors have the same number of secondary turns as the CRa and CRb sensors respectively. n 200/1 and 800/1 sensors of the Ringmaster: description n The VIP300 relay is mounted in a polycarbonate injected casing which protects it against dripping water and dusty environments. The front is protected by a transparent cover fitted with a sealing joint. The cover may be lead-sealed to prohibit access to the settings. n Rotating selector switches are used for setting. The phase setting current and earth fault setting current are set in amperes. This means that the scale on the front must be adapted to suit the sensor used. This is done by positioning a «setting scale label» on the relay at the time of assembly. n Connections are made on the back using fast-on clips. indication Two indicators indicate the origin of tripping (phase or earth). They stay in position after a break in the relay power supply. Two LEDs (phase and earth) indicate that the low setting has been overrun and that the time delay is running. technical manual VIP300 3
4 2. use and settings front view phase overcurrent I> sensors: CRa F0 VIP300LL range: x 1 I> VI SI RI DT EI off DT only I>> off VIP 300 EI, VI, SI DT b a c d trip reset trip minimum operating phase current : 10A curve selection t> (sec) Io> VI EI SI RI off DT 1.2 x 10 x (x ) DT only , , , (sec) t>> Io>> (x ) off RI t> t>> 1.2 I> 10 I>> f Io> earth fault Ios to> curve selection (sec) x 10 x 1 (x Ios) to>> (x Ios) 0.2 0, , , (sec) 1.5 VAP6 test plug e — front panel phase protection earth protection other functions 1. phase setting zone 2. setting overrun indicator 3. phase trip indicator 4. phase setting current 5. choice of low setting curve type 6. low setting I> 7. low setting time delay t> 8. multiplying factor (low setting) 9. high setting I>> 10. high setting time delay t>> 11. earth setting zone 12. setting overrun indicator 13. earth trip indicator 14. earth setting current Ios 15. choice of low setting curve type 16. low setting Io> 17. low setting time delay to> 18. multiplying factor (low setting) 19. high setting Io>> 20. high setting time delay to>> a. setting scale label b. sensor and range information c. indicator reset d. minimum operating current e. VAP6 test plug f. VIP300LL: tripping curves VIP300LH: table for «equivalent time multiplier» conversion. 4 technical manual VIP300
5 2. use and settings (cont d) tripping curves settings 5 low setting SI, VI, EI, RI phase protection setting The numbers indicated on the curves opposite are those of the phase protection setting switches (refer to the diagram of the front view). t> 7 8 Set: n setting current (4) n type of low setting I> curve (5) IDMT: RI, SI, VI, EI definite time: DT n low setting I> (6) This setting is only active if the low setting curve chosen is of the definite time DT type (fig 2). For the other choices, SI, VI, EI, RI (fig 1), the selector switch is disabled. n low setting time delay t> (7) and (8) n high setting I>> (9) n high setting time delay t>> (10) t>> 4 t> 1, I>> fig 1: phase setting : IDMT low threshold 6 low setting 5 DT earth protection setting The principle is the same as for phase protection. Set: n setting current Ios (14) n type of low setting Io> curve (15) IDMT: RI, SI, VI, EI definite time: DT n low setting Io> (16) This setting is only active if the low setting curve chosen is of the definite time DT type. For the other choices, SI, VI, EI, RI, the selector switch is disabled. n low setting time delay to> (17) and (18) n high setting Io>> (19) n high setting time delay to>> (20) 9 operation The high and low settings operate separately. The tripping order results from the «logical OR» between the two settings. t>> ,2 I> I>> fig 2: phase setting: definite time low threshold technical manual VIP300 5
6 2. use and settings (cont d) phase protection 1. phase protection setting zone All the information concerning phase protection is grouped together in the dark zone of the upper half of the front face. 2. setting overrun indicator When the red indicator blinks, it means that the phase protection low setting time delay is running. When this is the case, if the current does not decrease, the relay will trip. n for IDMT curves (SI, VI, EI), the LED lights up when the current is greater than 1.2 times the setting current. n for the IDMT curve (RI), it lights up when the current is greater than the setting. n for the definite time curve DT, it lights up when the low setting is overrun. F also refer to «indicator reset button». 3. trip indicator It is normally black and turns yellow to indicate that the phase protection has given a tripping order. It stays in the same status, even when the relay is no longer energized. 4. choice of setting current The setting current setting range depends on the sensor and range used: the selector switch scale should be adapted to suit the sensor and range using the setting scale label. F also refer to «choice of sensors and operating ranges» chapter. 6. choice of low setting I> The setting is a multiple of the setting current. It is only active for definite time settings (selector switch 5 set to DT). If the tripping curve is selected with IDMT (selector switch 5 set to RI, SI, VI, EI), the selector switch has no effect. 7. setting of low setting time delay t>. n If the tripping curve is of the definite time (DT) type, the selector switch sets the low setting time delay. n If the curve is of the IDMT type (RI, SI, VI, EI), the value displayed is the tripping time for a phase current equal to 10 times the setting current. 8. low setting time delay multiplying factor. In the x10 position, the time delay displayed on selector switch 7 is multiplied by setting of high setting I>>. The high setting is chosen as a multiple of the setting current. In the «off» position, the high setting is disabled. 10. setting of high setting time delay t>>. The time delay is set directly in seconds. 5. choice of type of low setting curve DT: definite time SI: inverse time VI: very inverse time EI: extremely inverse time RI: specific curve off: low setting is disabled. 6 technical manual VIP300
7 2. use and settings (cont d) earth protection The setting principle is the same as for phase protection. 11. earth protection setting zone The earth protection settings are grouped together in the dark zone of the lower half of the front face. 12. setting overrun indicator When this indicator blinks, it means that the earth protection low setting time delay is running. When this is the case, if the current does not decrease, the relay will trip. n for IDMT curves (SI, VI, EI), the LED lights up when the current is greater than 1.2 times the setting current Ios. n for the IDMT curve (RI), it lights up when the current is greater than the Ios setting. n for the definite time curve DT, it lights up when the low setting is overrun. F for the cases above, the LED only lights up when a phase current is greater than the minimum operating current. F also refer to «indicator reset button». 13. trip indicator It is normally black and turns yellow to indicate that the phase protection has given a tripping order. It stays in the same status, even when the relay is no longer energized. 14. choice of setting current Ios This is the maximum residual current that can flow in the network without the protection being triggered. The Ios current setting range depends on the sensor and range used: the selector switch scale should be adapted to suit the sensor and range using the setting scale label. F also refer to «choice of sensors and operating ranges» chapter. 15. choice of type of low setting curve DT: definite time SI: inverse time VI: very inverse time EI: extremely inverse time RI: specific curve off: low setting is disabled. 16. choice of low setting Io> The setting is a multiple of the setting current. It is only active for definite time settings (selector switch 15 set to DT). If the tripping curve is selected with IDMT (selector switch 15 set to RI, SI, VI, EI), the selector switch has no effect. 17. setting of low setting time delay to>. n If the tripping curve is of the definite time (DT) type, the selector switch sets the low setting time delay n If the curve is of the IDMT type (RI, SI, VI, EI), the value displayed is the tripping time for an earth current equal to 10 times the setting current. 18. low setting time delay multiplying factor. In the x10 position, the time delay displayed on selector switch 17 is multiplied by setting of high setting Io>>. The high setting is chosen as a multiple of the setting current Ios. In the «off» position, the high setting is disabled. 10. setting of high setting time delay t>>. The time delay is set directly in seconds. technical manual VIP300 7
8 2. use and settings (cont d) other functions recto sensors: CRb F0 VIP300LL range: x Ios minimum operating phase current : 62A verso sensors: CRb F0 VIP300LL range: x Ios — setting scale label minimum operating phase current:250a how to install the setting scale label — a. setting scale label n it should be mounted on the VIP300 when it is assembled on the circuit breaker. The label indicates the scales for the phase setting current and earth protection setting current. It is inserted, from the top, behind the transparent part of the front face. n each VIP300 comes with a set of labels. Install the label that matches: — the type of sensor used — the VIP300 model — the range used n each setting scale label matches a sensor and is printed on both sides for each of the 2 ranges. The label may therefore be turned around if the VIP300 range is changed during the service life of the installation. F also refer to «assembly» chapter. b. sensor and range indication The text is printed on the setting scale label. When the label is installed in the slot, the text is hidden by an opaque zone. It is not visible to the user. c. indicator reset button The button is accessible when the transparent cover is closed. When the button is pressed, 2 actions are triggered: n it resets (black position) the 2 phase and earth trip indicators. When the relay is no longer energized, it is still possible to reset the indicators for about 48 hours. After that time, they may be reset after the VAP6 is plugged in. n it triggers the lighting up of the 2 red LEDs (about 3 sec). This indicates that: — the relay is energized. The indicator lights up when the current is greater than the minimum operating current. — relay self-testing results are OK. If one of the two conditions is not met, the indicators do not light up. This function may be used to carry out a basic relay operation test. d. minimum operating current The minimum operating current is the phase current required for the relay to be energized and operational. It is printed on each setting scale label. The value given on the setting scale label is the single-phase rms minimum operating current. The minimum operating current is always the lowest setting current setting. F note regarding minimum operating current: The VIP300 does not operate below the minimum operating current level. As a result, if the earth protections are set below the minimum operating current, they will only take effect when there is phase current greater than or equal to the minimum operating current. e. VAP6 test plug The test plug is exclusively designed for connection of the VAP6 which is used for fast, simplified relay testing. The operation may be carried out while the relay is operating since the VAP6 and VIP300 provide the possibility of testing with inhibition of circuit breaker tripping. F also refer to the «testing of the VIP300 and use of the VAP6» chapter. — testing of the VIP300 using the VAP6-8 technical manual VIP300
9 3. choice of sensors and operating ranges selection principle Choose the sensor to be used and the VIP300 connection range in accordance with the desired operating range. Refer to the charts below. sensors The VIP300 should be used with the specified sensors. The relay/sensor assembly must be used together in order to comply with the characteristics, in particular: — operation across the range — response time — accuracy — short-circuit current behaviour It is compulsory for the 3 sensors to be of the same type. sensors specified for VIP300LL: — CRa 200/ F0 (1) — CRb 1250/ F0 (1) sensors specified for VIP300LH: — Ringmaster 200/ A0 — Ringmaster 800/ A0 (1): for RM6 model 98 and higher. range The VIP300 relay contains input transformers that have an intermediary tap on the primary winding. Each tap corresponds to a rating with a different operating range. VIP300LL model ranges: — X1 — X4 VIP300LH model ranges: — X2 — X4 VIP300LL model operating ranges CRa 10 range x1 range x k 4k CRb 62, ,25K range x ,25K range x4 25K k 2k 3k 6k 10k 20K Amps VIP300LH model operating ranges Ringmaster 200/1 range x k 40 range x k Ringmaster 800/ K range x range x4 16K k 2k 3k 6k 10k 20K Amps operating current setting range selective operating range For a given operating range, the bottom of the setting current range represents the relay minimum operating current. technical manual VIP300 9
10 4. connection scheme wiring to x1 (or x2) range VIP300LL(VIP300LH) The connection is made on the back of the VIP300 P1 P1 S1 P2 S1 S x 1 (x2) x 4 x 1 (x2) x 4 L3 L2 connection using fast-on clips The standard way to connect the VIP300 is by means of 6.35 mm faston clips. 8 x 1 (x2) P1 S1 P2 S2 7 x 4 L1 P2 S2 1 2 x 4 x 1 (x2) Io V 15 MITOP wiring to x4 range VIP300LL(VIP300LH) 4 x 1 (x2) 3 x 4 L3 P1 S1 6 x 1 (x2) P1 S1 P2 S2 5 x 4 L2 8 x 1 (x2) P1 S1 P2 S2 7 x 4 L1 P2 S2 1 2 x 4 x 1 (x2) Io V 15 MITOP technical manual VIP300
11 5. assembly cut-out mm mm The VIP300 is flush-mounted in a rectangular cut-out made in a metal plate 3 mm thick at the most. — drilling of cut-out — assembly E N V P n insert the VIP300 in the cut-out and correctly position the 2 lower pins (E) of the casing on the edge of the metal plate cut-out. n tighten the screws (V) on the 2 mounting lugs accessible via the front face after having opened the transparent cover. n after tightening, make sure that the latch (N) of each lock (visible on the rear face) is in the vertical position, pressing against the support plate. F the latch may be put into the vertical position by loosening each of the screws (V) before tightening them. n the hole (P) may be used to leadseal the relay after the setting scale label is installed and the settings are made. installation of the setting scale label M n slide the setting scale label into position behind the transparent part of the front face. F refer to the section entitled «choice of the setting scale label». n make sure that the information given at the top of the label (M) matches: the sensor used (sensor) the VIP300 model the range used (range) This information is hidden when the label is in position. n make sure that it is pushed right to the bottom of the slot. n to remove the label, use the hole in the top, if necessary with the help of the tip of a pencil or a screwdriver. technical manual VIP300 11
12 5. assembly (cont d) choice of the setting scale label for VIP 300 LL with CRa sensors for VIP 300 LL with CRb sensors recto verso recto verso sensors: CRa F0 VIP300LL range: x sensor: CRa F0 VIP300LL range: x sensor: CRb F0 VIP300LL range: x sensor: CRb F0 VIP300LL range: x minimum operating phase current : 10A minimum operating phase current :40A minimum operating phase current : 63A minimum operating phase current:250a Ios Ios Ios Ios x 1 range x 4 range x 1 range x 4 range for VIP 300 LH with 200/1 RMR sensors for VIP 300 LH with 800/1 RMR sensors recto verso recto verso sensor: 200/1: A0 VIP300LH range: x sensor: 200/1: A0 VIP300LH range: x sensor: 800/ A0 VIP300LH range: x sensor: 800/ A0 VIP300LH range: x minimum operating phase current : 20A minimum operating phase current : 40A minimum operating phase current : 80A minimum operating phase current:160a Ios Ios Ios Ios x 2 range x 4 range x 2 range x 4 range 12 technical manual VIP300
13 6. IDMT tripping curves n the curves in this chapter indicate the IDMT low setting tripping times for the 16 time delay t> (or to>) settings. n the phase protection and earth protection curves are the same. n the numbers given on the right of the curves represent the position of the time delay t> (or to>) selector switch. (if the multiplying factor x1 / x10 is in the x10 position, multiply the times indicated by 10). SI curve SI 1, t (s) 1 0,6 0,4 0, ,2 0,15 0,1 0,07 0, I/ technical manual VIP300 13
14 6. tripping curves (cont d) VI curve VI 1, t (s) 1 0, ,4 0,3 0,2 0,15 0,1 0,07 0, I/ 14 technical manual VIP300
15 6. tripping curves (cont d) EI curve EI 1, t (s) ,6 0,4 0,3 0,2 0,15 0,1 0,07 0, I/ technical manual VIP300 15
16 6. tripping curves (cont d) RI curve RI ,6 t (s) 0,4 0,3 0,2 0, ,1 0,07 0, I/ 16 technical manual VIP300
17 7. technical characteristics phase protection accuracy see notes low setting I> ± 5% or 0/+2A 1 low setting time delay t> definite time IDMT ± 2% or ± 20 ms class 5 according to IEC or 0/+20ms high setting I>> ± 5% high setting time delay t>> ± 2% or ± 20 ms 2 % of pick-up 95% storage time 20 ms earth protection accuracy see notes low setting Io> ± 5% or 0/+2A 3, 4, 5 low setting time delay to> definite time IDMT ± 2% or ± 20 ms class 5 according to IEC or 0/+25ms 2, 8 2, 8 2, 8 2, 5, 8 high setting Io>> ± 5% high setting time delay to>> ± 2% or ± 20 ms 2, 8 % of pick-up 95% storage time 20 ms general characteristics value steady thermal resistance 240 A 1500 A 240 A 960 A 1 sec thermal resistance 25 ka/1s 25 ka/1s 20 ka/1s operating frequency 50 Hz ± 10%, 60 Hz ± 10% operating temperature -25 C to +70 C storage temperature -40 C to +85 C weight 1.7 kg with CRa sensor with CRb sensor with RMR 200/1 sensor with RMR 800/1 sensor with CRa, CRb, RMR800/1 sensors with RMR200/1 sensor on range x2 with RMR200/1 sensor on range x4 minimum operating current range value see notes VIP300LL + CRa sensor x1 10A 7 x4 40A VIP300LL + CRb sensor x1 62A x4 250A VIP300LH + RMR 200/1 sensor x1 20A x2 40A VIP300LH + RMR 800/1 sensor x1 80A x2 160A climatic resistance standard severity low temperature operation IEC C, 16h low temperature storage IEC C, 96h high temperature operation IEC C, 16h high temperature storage IEC C, 96h fast changes in temperature IEC C to +70 C, 5 cycles operation in damp heat IEC days, 93% RH salt spray IEC severity 1 mechanical resistance standard severity vibrations IEC class 2 shocks and jolts IEC class 2 earthquakes IEC class 2 enclosure protection index EN IP54, (cover closed) fire resistance IEC C technical manual VIP300 17
18 7. technical characteristics (cont d) electrical resistance standard severity sensor input isolation IEC kv rms, 50 Hz, 1 mn 1.2/50 µs impulse voltage IEC kv, note 6 1 MHz dampened oscillating wave IEC ,5 kv cm, note 6 1 kv dm rapid transient bursts IEC kv cm and dm, 5 khz burst, note 6 1.2/50(8-20 µs) hybrid wave IEC kv, 42 ohms, note 6 electrostatic discharge IEC kv in air, 6 kv on contact HF electromagnetic field IEC V/m not modulated, 27 to 1000 MHz EN V/m mod. ampl., 80 to 1000 MHz EN V/m mod.impuls., 900 MHz notes 1. Value given for three-phase VIP300 power supply. For single-phase operation, the accuracy range is ± 10% or 0/+4A. For the low setting, this does not generally represent a real operating situation. However, it may occur during injection testing carried out with single-phase. The error is mainly due to the nonlinearity of the sensors and VIP300 input transformers with weak current, the inaccuracy being accentuated when the relay is only supplied by one phase. 2. The accuracy is indicated for a fault that occurs when the VIP300 is already supplied by the current let through by the circuit breaker. The accuracy is indicated for sinusoidal current. In the event of closing while a fault is present, the tripping time may be extended by: +30 ms at ms from 2 to ms above Generally speaking, the accuracy ranges of earth protection times and settings are indicated for when the VIP300 is supplied by current that is greater than or equal to the minimum operating current. The measurement of a setting for earth protection with single-phase supply is therefore not significant if the setting is lower than the minimum operating current. 4. Value given for three-phase VIP300 supply. For single-phase testing, the accuracy is ± 10% or 0/+4A. For the low setting, this may occur when the earth protection is tested with single-phase supply, and no supply by the other phases. 5. In the following specific conditions: — VIP300LL — with CRa sensor — wiring to x1 range — if Ios < 8A — if phase current < 20A the setting and time delay characteristics are: — low settings: ±10% 0/+4A — class not specified 6. Not applicable to test plug 7. Accuracy ± 10% or ± 1.5A. The value indicates the guaranteed minimum operating current for singlephase operation. With three-phase oepration, it may be less than the value indicated. 8. The tripping times indicated do not include the mitop response time. Its tripping time depends on its mechanical load (for no load, its tripping time is less than 5 ms) 18 technical manual VIP300
19 7. technical characteristics (cont d) dimensions raccordemen technical manual VIP300 19
20 8. testing of the VIP300 and use of the VAP6 presentation of the VAP6 external mitop + — on test in progress trip earth fault test phase overcurrent trip inhibition VIP30 VIP35 VIP300 VIP50 VIP37 VIP11,11R VIP12R test VIP13 VIP17 phase VIP200,201 overcurrent battery test phase overcurrent earth fault trip trip inhibition circuit breaker mitop external mitop VAP 6 — VAP6 front panel — circuit breaker mitop The VAP6 is a portable unit that is connected to the VIP300 to carry out simplified testing. The test can be carried out in the following two cases: — the VIP300 is already supplied by the sensors. — the VIP300 is not supplied. In this case, the VAP6 batteries supply power to the relay. The test consists of: — starting up the VIP300 central unit self-testing sequence. — injecting a stimulus to simulate a phase fault. — injecting a stimulus to simulate an earth fault. — checking tripping. Frefer to the description of the test in the section entitled «test sequence» F the VAP6 is supplied by batteries. Therefore the parts of the VIP300 that run on AC current are not checked using this method (input and supply circuits). push-buttons n battery test: if the batteries are OK, the «on» indicator lights up while the button is pushed. n phase overcurrent: it sends the phase protection test stimulus. The stimulus is equivalent to 20 times the setting current. n earth fault: it sends the earth protection test stimulus. The stimulus is equivalent to 20 times the earth setting current Ios. n trip inhibition: press the «trip inhibition» button if the VIP300 test should be carried out without tripping of the circuit breaker. Circuit breaker tripping is inhibited while the trip inhibition» button is pressed, even if the tripping order results from a real fault. indicators n on: indicates that the batteries are operating. Also lights up when the battery test is carried out by pressing «battery test». n test in progress: confirms sending of the test stimulus to the VIP300. n trip: it is used to test other relays in the VIP range. It is not to be considered for the VIP300 test. (it lights up for a transient period when the VIP300 sends a tripping order; whether or not the circuit breaker is inhibited). «external mitop» output It may be used to connect an auxiliary mitop designed, for instance, to stop a stop watch during operating tests. The mitop is triggered at the same time as the circuit breaker mitop. It is not inhibited by pressing the «trip inhibition» button. batteries n the batteries are normally deactivated and are automatically activated when the VAP6 is connected to the VIP300. They are activated in the following cases: — pressing the «battery test» button. — direct connection to a VIP3X or VIP5X relay. — connection to the adapter cord designed for testing of the VIP1X or VIP2X relays. n to install or change the batteries, open the unit by removing the 4 screws on the bottom of the unit. Be sure to use the correct polarities. technical characteristics supply: 3 x 9V 6LR61 batteries weight: 0.45 kg dimensions: 93x157x45 20 technical manual VIP300
21 8. testing of the VIP300 and use of the VAP6 (cont d) VAP6 test sequence The test may be carried out with or without current in the sensors. During the test operations, all the VIP300 settings are effective; the relay should perform in accordance with the settings. During the test, the relay remains operational and will give a tripping order in the event of a fault, unless the «trip inhibition» button is pressed. n connect the VAP6 to the «VAP6 test plug». The VAP6 batteries are activated and the «on» indicator lights up. n press the VIP300 «reset» button. — if the 2 «trip» indicators were yellow, they become black. — the 2 red I> and Io> indicators of the VIP300 light up for about 3s to indicate that the central unit has correctly performed self-testing. n press the «trip inhibition» button if the test should be carried out without tripping of the circuit breaker. Fbe sure to continue pressing the «trip inhibition» button throughout the time it takes to send the stimulus. n press the «phase overcurrent» button to send the phase protection test stimulus. — continue pressing the button throughout the duration of the stimulus. The stimulus represents about 20 times the setting current. — the VAP6 «test in progress» indicator lights up to confirm the sending of the stimulus to the VIP300 relay. — the red «I>» indicator of the VIP300 blinks during the time delay period. — then the VIP300 phase «trip» indicator turns yellow. — the circuit breaker trips if it is not inhibited. F if the «phase overcurrent» button is held down after tripping, the VIP300 starts the time delay/tripping cycle again; this is normal operation. In that case: — the VAP6 red «trip» indicator lights up for a transient period each time there is a trip. — depending on the time delay setting, the VIP300 red «I>» indicator may be off or blink rapidly and/or in an irregular manner. n press «earth fault» to test operation of the earth protection. The stimulus injected is equal to 20 times the setting current Ios. Use the same procedure as for the phase protection test. n disconnect the VAP6. In order to save batteries, do not leave the VAP6 connected to the relay unnecessarily. technical manual VIP300 21
22 Notes 22 technical manual VIP300
23 Notes technical manual VIP300 23
24 Schneider Electric SA Postal address F Grenoble cedex 9 Tél : +33 (0) Télex : merger F Rcs Nanterre B As standards, specifications and designs change from time to time, please ask for information given in this publication Publishing: Schneider Electric SA Design, production: Schneider Electric SA Printing: This document has been printed on ecological paper Rcs Nanterre B PCRED399008EN ART / technical manual VIP300
VIP
-300
®
Pupillometer
Instructions for Use
Introduction
The NeurOptics® VIP®-300 Pupillometer offers clinicians quantitative infrared
technology to objectively and accurately measure pupil size in an advanced
design. The system acquires images using self contained infrared and visible
illumination sources and a digital camera. It analyzes the captured image data
and displays a summary of the measurement in the LCD window. The NeurOptics
VIP-300 Pupillometer uses a menu driven graphical user interface (GUI), with
a color touchscreen LCD screen for data display. A keypad completes the user
interface and enables manual entry of individual patient identification (ID).
Indications for Use
The VIP-300 Pupillometer is a handheld optical scanner which measures pupil size at different background illuminations.
The results obtained from the Pupillometer scans are used for information only and are not to be used for clinical
diagnostic purposes. It should only be operated by properly trained clinical personnel, under the direction of a qualified
physician.
Contraindications
Avoid use when the orbit structure is damaged, or surrounding soft tissue is edematous or has an open lesion.
Table of Contents
…….. ……………………………….. … ….
. .. . . . .. . . …………… ……………………………….. …. …
. .. . . . …………… ……………………………….. …. …
. . .. . . . .. . . . .. . . ………….. ……………………………….. …. …
………. ………………………………… … …
………………………………… … …. ..
. . .. . . . …………………………………………… …. … .
. . . …. …………………………………………… … …
. .. . . . .. . . . ……………………………………………. …. …
NeurOptics® VIP®-300 Pupillometer System — Instructions for Use © 2019 NeurOptics, Inc.
NeurOptics® VIP®-300 Pupillometer System — Instructions for Use © 2019 NeurOptics, Inc.
2
2
2
…………….. …. …
3
3
Appendix A
4
5
Appendix B
5
6
Appendix C
6
VIP
-300 Pupillometer
®
. .. . .. . .. .. . .. . .. . .. . .. .. . .. . .. . .. . .. . .. .. . .. . .. . .. . .. .. . .. . .. . ..
. .. . .. . .. . .. . .. .. . .. . .. . .. . .. . .. .. . .. . .. . .. . .. .
. .. . .. .. . .. . .. . .. . .. . .. .. . .. . .. . .. . .. .. . .. . .. . .. . .. . .. .. .
.. . .. . .. . .. . .. .. . .. . .. . .. . .. . .. .. . .. . .. . .. . .. .. .. .. . .. .. . .. . ..
. .. . .. .. . .. . .. . .. . .. .. . .. . .. . .. . … .. . .. . .. . .. ..
. . .. . .. . .. .. . .. . .. . .. . … .. . .. . .. .. . .
6
7
8
9
9
10
.. .. . .. . .. .. . .
10
1